Questions and answers for FA480119Q1002, 5 December 2019
1. Is there an electrical schematic?
a. Please see the attached documents labeled, "Control Box Electronic Diagram" and "Halmar Series 2Z SCR Model 8T Power Box Electrical
Drawings". Electrical drawings of the furnace itself are not available. The full instruction manual for the Power Box can be made available if necessary. The data drawing recording graph (see page 7) will be included in the new control box.
2. Are there pictures of the interior and exterior of the furnace?
a. Please see the images on the following pages.
3. What is the existing Programmable Logic Controller (PLC) manufacturer and model if applicable? Please provide the Logic program printout if applicable.
a. A PLC is not applicable.
4. What are the type, size, manufacturer and specifications of the transformer?
a. Please see the images on the following pages. The current transformer does not have any labels or markings. A new transformer must be at least 80KVA, step down transformer. It can be offset and not located directly beneath the furnace.
5. Are there furnace operation instructions?
a. The instruction manual for the furnace is not available.