Questions and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA4800-11-T-0013-0001.doc | DOC document | |
| Site Visit Meeting Minutes.docx | DOCX document | |
| FA4800-11-T-0013 Site Visit.docx | DOCX document | |
| FA4800-11-T-0013.docx | DOCX document | |
| Attachment 2 - Performance Plan.docx | DOCX document | |
| Attachment 1 - PWS.docx | DOCX document | |
| Attachment 3 - Wage Determination.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
1. Item 001 = What are the dimensions of the 60 each exhaust fans?
The exhaust fans range from small 12"x12" to 48"x48" there are no kitchen exhaust fans just general exhaust fans.
2. Item 002 = How many of each size of the AHU's from 0.5 to 30 tons are included?
(Example: 0.5 ton = 6 each, 30 ton = 10 each, etc.)
The number of air handlers is not relevant we just need the pricing of our description
3. Item 003 = How many of each size of the AH's from 30 to 100 tons are included?
(Example: 30 ton = 6 each, 100 ton = 10 each, etc.)
The number of air handlers is not relevant we just need the pricing of our description
4. Item 004 = What are the dimensions of the VAV's?
They are all different sizes.
5. Item 005 = What are the dimensions of the water source heat pumps and where are they located? Rooftop, Ground, inside the buildings?
The water source heat pumps range in size from 1.5 ton to 15 ton and about 80% are located in the ceilings and the rest are in mechanical rooms.
6. Item 006 = What are the dimensions of the Supply, Return and Exhaust Ducts?
The dimensions of the supply and return ducts vary.
7. Item 010 = What are the dimensions of the fan coil units and is there access points on either side for cleaning?
They vary in size also from 1/2 ton to 3 tons and some have access and some do not.
8. Item 012 = What are the dimensions of the insulated supply and return ducts and is the internal insulation exposed?
The dimensions vary and the insulation is exposed.
9. Paragraphs 1.1.2.3, 1.1.3.2, 1.1.3.6, 1.1.7.2, 1.1.8.1.1, 1.1.9.1, 1.1.9.2 and 1.1.12.2 indicates work to be accomplish in accordance with NADCA standards. Does this solicitation require the contractor to be a member of NADCA and have ASCS's (Air Systems Cleaning Specialist) on staff and or on-site?
No you do not need to be a member of NADCA, but will use their standards.
10. If mold contamination is found does this solicitation require the contractor to have VSMR (Ventilation System Mold Remediator) trained and approved by NADCA?
No special training for mold will be required.