Attachment 1_Salient Characteristic.pdf

PDF 37 KB Posted

Attached to
Motorized Court Dividers (Ellsworth AFB) (Updated to add Attachment 4_Q&A with Pictures)
Solicitation number
FA469023Q0042
Issued by

About this file

This memorandum provides specifications for two motorized top roll court dividers for a fitness center. The dividers must be 70 feet wide and 29.83 feet tall with the lower 8 feet consisting of 19 or 22 ounce fire-retardant and mildew-resistant vinyl fabric. Seams must be electronically welded. Curtains weighing up to 500 pounds will be operated by one internal tubular motor while heavier curtains will require two synchronized motors equipped with up and down limit switches. The related federal contract opportunity is solicitation number FA469023Q0042 for motorized court dividers at Ellsworth Air Force Base. Offerors are to provide products meeting the specifications outlined in the memorandum.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

11 August 2023

Memo Fitness Center Motorized Top Roll Court Dividers

*Two (2) 4040XL CURTAIN VINYL - TOP ROLL -

70.00 Ft Wide By 29.83 Ft High / 8 Ft of Vinyl at 19 Oz.

2 4043-60-25-PARTS 110V 60Hz

CURTAINSTRUCTURE -

TOP ROLL (2 MOTOR) - 70.00 Ft Wide By 29.83 Ft High

Vendor Model/Reference#: Performance Sports Systems / 2 - 4040XL and

2-4043-60-25-PARTS OR EQUAL

The specifications of the dividers:

OVERHEAD STRUCTURE

The divider curtain should be supported from the roof structure by directly attaching to the underneath side of roof truss.

Maximum attachment height shall not exceed 35'.

Bridge pipe may be required when truss spans exceed 14'.

MATERIAL

The total divider measurement should be 70'0" wide, 29.83'0" tall with the lower 8'0" being solid 19 oz.

or 22 oz. polyester reinforced, fire retardant and mildew resistant vinyl fabric.

Seams shall be electronically welded with a full contact weld.

Curtain shall stop 2" above finished floor.

DRIVE STRUCTURE

Curtains up to 500 lbs shall be operated by one internal tubular motor.

Curtains over 500 lbs shall be operated by two synchronized internal tubular motors.

Each motor shall be equipped with integral up and down limit switches.

Each asynchronous motor is maintenance free, permanently lubricated, features overheating protection and has sturdy electrical and mechanical design for long life.