RFIs on FA4664-16-T-0004 Solicitat ion:

Question 1: Please provide the contact information for the base South Coast Air Quality Management representative Response 1: Melissa Sanchez (909)396-2355

Question 2: The clean room is required to have over head sprinklers, will the contractor be required to install notification signaling from the clean room back to the hangar fire alarm panel?

Response 2: Yes

Question 3: Clean room specification is calling out for “walls 3” thick” the industry standard for modular rooms is 2” walls insulated with 800 degree rock wool. Can the contractor provide 2” insulated walls?

Response 3: Yes

Question 4: In the clean room can we substitute the ceiling tiles with 18-gauge powder coated white steel panels for the ceiling? This will allow for easier cleaning and help with the truss structure necessary to support the A/C system and assist with overhead fire suppression and installation of the overhed lighting Response 4: Yes

Question 5: What is the maximum weight load in the oven?

Response 5: No more than 500 lbs.

Question 6: Please define cure oven “wheel guides” Response 6: Recessed tracks in the floor to facilitate our racks to be moved in and out.

Question 7: Can the breathing air purifier be moved (by contractor) to the back wall to allow more clearance for the blast room?

Response 7: Yes