Questions and Answers 2.pdf

PDF 65 KB Posted

Attached to
Trailer Mounted Air Cooled Chiller
Solicitation number
FA4661-24-Q-0004
Issued by

About this file

This document contains questions and answers regarding a trailer mounted air cooled chiller solicitation. The solicitation is for a 20-ton trailer mounted chiller with an internal pump and freeze protection package from the manufacturer. Acceptable refrigerants are 134a, 410A, or 545b. Storage and containment for hoses and conductors is required. Freeze protection for internal chiller components and piping between the pump and chiller must be provided. Insulation of piping between the pump and chiller is also expected. A motor starter, rather than a variable frequency drive, will control the pump. The solicitation number is FA4661-24-Q-0004 and is being issued by the Department of the Air Force Global Strike Command.

View the file

Other files

File Type Posted
Questions and Answers 3.pdf PDF
Questions and Answers.pdf PDF
Attachment 2 FAR 52.212-5.pdf PDF
Attachment 3 - Specifications.pdf PDF
Attachment 1 Provisions and Clauses.pdf PDF
FA4661-24-Q-0004 RFQ.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUESTIONS AND ANSWERS 2

- The scope states that the chiller is to be charged with 134a refrigerant, however the unit shown utilizes 545b refrigerant, is this acceptable? 410A is what we want but 545b will be ok

- Is there an expectation for a bypass setup for situations that utilize building pumps? No

- Is there an expectation for a rack or cage of some kind for hose storage/containment? yes

- Is there an expectation for a rack or cage of some kind for conductor storage/containment? yes

- Is the 115vfreeze protection expected to be provided by manufacturer for internal chiller freeze protection or is this in reference to the piping between the pump and chiller? Yes chiller freeze protection

- Is the expectation to provide a transformer mounted to the trailer for the 115v freeze protection? The chiller should have the freeze protection package that provides this from the control panel by the manufacture

- What is the expectation regarding piping insulation between the pump and the chiller? The pump will and will be inside the chiller be insulated from the manufactuer .. I am asking for a fully contained chiller 20ton with and internal pump all together and a freeze protection package from the manufacturer as part of the specs

- Is there an expectation of a VFD to control the pump or just a motor starter? Motor starter