1250Kw Generator Salient Characteristics v2

Solicitation #: FA462522Q0003

Amendment 0001

1. 1250 DQFAD OR EQUAL, Diesel Genset

2. 1250‐kilowatt

3. 277/480 volts AC

4. 3‐phase

5. 60 hertz

6. Alternator‐60Hz, 3 Phase, Wye,

7. 2400‐gallon double‐walled sub‐base fuel tank ‐ UL142 Compliant 1

8. Compliance‐Fuel Tank ‐ Listing, ULC‐S601‐07, Listing‐UL 2200

9. Fuel supply & return lines, primary & secondary vents, with emergency vents

10. Emission certification = Tier 2

11. External battery charger, but NO battery

12. PowerCommand 3.3 Controller ‐ NO Touch Screen Controller

13. LCD control display ‐ Control Display Language‐English

14. Alarm‐Audible, Engine Shutdown

15. Emergency stop switch

16. MODBUS compatible and activated

17. Standard Startup and Testing by manufacturer’s technician with warranty

18. No installation requirements – will be installed by end user

19. Engine air cleaner

20. Engine Cooling‐Radiator, Enhanced High Ambient Air Temperature, Ship Fitted 1

21. Sight Glass‐Coolant Level ‐ Shutdown‐Low Coolant Level 1

22. Coolant heater ‐ 208/240/480 Volts AC, maintain temperature between 100‐120‐degrees

23. Output circuit breaker with bottom entrance – Left side (back of engine facing radiator)

24. Weather housing ‐ Steel Sound Attenuated Level 2 Enclosure, hinged doors, with Exhaust

System

25. Manuals – operation, maintenance, & parts

26. Certified Test Record

27. Provide overall dimensions for equipment to include length, width, height & weight

1553685814A Highlight