Attachment_1_Salient Characteristics.pdf

PDF 134 KB Posted

Attached to
PAD MOUNT TRANSFORMERS
Solicitation number
FA4610_PadMountTransformers_SS
Issued by

About this file

This document is a detailed specification sheet for three-phase pad-mounted transformers for Vandenberg Space Force Base. The specifications cover five transformer models ranging from 112.5 kVA to 750 kVA, with primary voltages of 12.0 kV or 12.47 kV and secondary voltages of 120/208V or 480V. Key requirements include all stainless-steel construction (304L or 316L grade), dead-front construction, copper windings, mineral oil-filled (Non-PCB) with FR-3 Fluid, a two-position load break primary switch, 5-position tap changer, and compliance with 2016 DOE Efficiency Standards. Additional specifications mandate Munsell-Green exterior painting, a guaranteed average coil winding temperature rise of 65°C, and DGA testing to verify conformance with ANSI C57.12.00 and ANSI C57.12.90 standards.

The document is part of a Sources Sought Notice for the 30th Contracting Squadron, seeking to identify potential contractors for five medium voltage pad-mounted transformers. The acquisition targets NAICS code 335311 with a size standard of 800 employees, and aims to determine small business participation. Interested vendors are encouraged to demonstrate their qualifications and ability to meet the detailed transformer specifications, with the goal of potentially establishing a small business set-aside procurement.

View the file

Other files

File Type Posted
Attachment_2_Sources Sought.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS 0F REQUESTED THREE PHASE PAD MOUNTEDTRANSFORMERS

Transformer Specs for:

112.5 kVA 12kV:120/208V

150 kVA 12 kV:120/208V

300 kVA 12 kV:480V

500 kVA 12.47 kV:480V

750 kVA 12kV:480V

Pad Mount Transformers

• All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.), stainless-steel grade shall be 304L or 316L (if available).

• “Pentahead” cabinet locking mechanism/device.

• Dead-Front construction (HV-200A load break elbows with shield adapters).

• Externally clamped LV bushings with threaded copper stud for full load current below 2,100.

amperes – NEMA spades shall be provided per ANSI hole requirements.

• Radial feed.

• Loop feed must be reviewed and approved by the government.

• KVA Rating: As required.

• Primary Voltage: 12.0 kV Delta for Main and North Base and 12.470 kV for South base

• Secondary Voltage: As required.

• 3-Phase Transformer.

• Frequency: 60Hz.

• HV/LV Windings: Copper.

• Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.

• Standard impedance.

• Mild steel high-voltage/low-voltage compartment barriers.

• Cooling fins.

• Proper grounding provisions.

• Dial type gauges for oil temperature, liquid level and pressure/vacuum.

• Bay-O-Net fuses & current-limiting fuses: properly sized – additionally, the transformer should be equipped with three spare fuses.

• Two-position “ON/OFF” load break primary switch

• 5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)

• Automatic pressure relief device mounted on the terminal compartment.

• Oil drain valve with sampling device, and an oil-fill/oil-level plug.

• Nameplate and NEMA safety labels: include a “UL Listed” symbol on ratings label and nameplate.

• Compliant with 2016 DOE Efficiency Standard.

• Four (4) lifting lugs.

• Entire exterior of the pad-mount transformer and terminal components shall be painted with a Munsell-Green, outdoor color-finish.

• Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient air temperature of 30°C when operated at rated voltage and load conditions.

• Provide DGA test to verify conformance to performance requirements as outlined in the latest revisions of ANSI C57.12.00 and ANSI C57.12.90.

File details come from the government source that posted it. Updated .