About this file

This document contains the Salient Characteristics for the procurement of three (3) 25 Ton Heating, Ventilation, and Air Conditioning (HVAC) portable, skid mounted units for the 21st Satellite Operations Squadron (21 SOPS), Detachment 1 located in Diego Garcia, British Indian Ocean Territory. The units must meet specific requirements including cooling capacity, power supply, air flow, refrigerant, and operating conditions. The vendor will be responsible for providing a list of preventive maintenance materials and critical spare parts. The three HVAC units will be shipped to Vandenberg Space Force Base, with 21 SOPS and 30LRS coordinating the final delivery to Diego Garcia. This procurement is issued as a 100% Small Business Set-Aside under NAICS code 423730, with quotes due by July 10, 2024 at 12:00 PM PST. The contract will be Firm Fixed Price.

View the file

Other files for this federal contract opportunity

Other files attached to Amendment 003 21 SOPS 25 Ton HVAC Units, newest first.
File Type Posted
Portable_AC_Unit_Layout.pdf PDF
FA461024Q00330001.pdf PDF
Amendment 0002_ FA461024Q0033_ RFI Responses.pdf PDF
Attachment - FA461024Q0033 Statement of Objectives.pdf PDF
Solicitation - FA461024Q0033.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

1.0 The 21st Satellite Operations Squadron (SOPS) has the requirement to procure three (3) 25 Ton

Heating, Ventilation, and Air Conditioning (HVAC) portable, skid mounted units for 21 SOPS, Detachment 1 located in Diego Garcia, British Indian Ocean Territory (BIOT).

2.0 The minimum specifications for each of the 25TON HVAC portable, skid mounted units are as follows:

Stackable Metal Frame with Forklift Pockets Cooling Capacity - 300,000 BTU Power Supply - 3 Phases / 480v / 60hz Max Air Flow - 10,100 CFM (Evaporator) Refrigerant - R-410A or equivalent Operating Condition - 64-113 F

2.1 Units will be pad mounted at ground level and ducted to supply and return wall penetrations.

2.2 Units will be powered by separate, 125amp, 480v/60hz breakers.

2.2.1 Units must come with built-in breaker.

2.3 Provide a list and 12-month supply of materials needed to conduct manufacture recommended preventive maintenance schedule (Examples include but are not limited to disposable air filters, fan belts, motor belts, grease etc..)

2.4 Provide a list of critical spares and provide one additional replacement for each of these parts.

2.4.1 List of critical spares should include most commonly replaced parts with an expected lead time of longer than 8 weeks (Examples include but are not limited to motors, refrigerant containers etc..)

2.5 Multiple collars of various sizes to be used with the ducting (20”, 18”, 12”, and 10”)

2.5.1 Silver air ducting tape (6 rolls) (non-webbed/not grey duct tape)

2.5.2 Pressure rated soft sealant to reinforce against air leaks at connecting points.

2.5.3 Large 26” length zip ties (4 packages)

3.0 The vendor will be shipping the three (3) 25 TON HVAC units to:

3.1 21 SOPS

Vandenberg Tracking Station 1 Bishop Road, Building 23225 Vandenberg SFB, CA 93437 Directions to VTS: 34.82439431894701, -120.50339016175612

3.2 Primary POC:

Name: Christopher Babauta Office # (805) 606-1605 Email: christopher.babauta.1@spaceforce.mil Alternate POC:

Name: Evangeline Reyes Office # (805) 606-8355 Email: evangeline.reyes@spaceforce.mil

4.0 21 SOPS will work with 30LRS to ship the three (3) 25 Ton HVAC units to Diego Garcia via Government freight and MilAir.