Attachment 1 - Technical Specifications_Rev 1.pdf
PDF 604 KB Posted
- Attached to
- LRS Chiller B6237 Federal contract opportunity
- Solicitation number
- FA460825QC050
About this file
This document is a detailed Model Number Descriptions guide for Trane Air-Cooled Scroll Packaged Chillers. The guide provides a comprehensive breakdown of a 50-digit model number system that allows precise configuration of chiller units, with each digit representing a specific feature or specification. Key configurable aspects include unit size (ranging from 20 to 130 tons), voltage options (200V to 575V), manufacturing location (Pueblo, CO), efficiency levels, agency listings, refrigerant charge type, evaporator applications, water connections, condenser materials, pump types, wireless connectivity options, and performance testing configurations. The document enables precise customization of industrial cooling equipment by providing a systematic method for specifying exact unit characteristics through a standardized numbering convention.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 1 - FA460825QC050.pdf | ||
| Attachment 3 - Provisions and Clauses.pdf | ||
| Attachment 1 - Technical Specifications.pdf | ||
| Attachment 2 - Brand Name Class Justification and Approval.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CG-PRC017T-EN 13
Model Number Descriptions
Unit Model Number
Digit 1, 2, 3, 4 — Unit Model
CGAM = Air-Cooled Scroll Packaged Chiller
Digit 5, 6, 7 — Nominal Tonnage
020 = 20 Tons 026 = 26 Tons 030 = 30 Tons 035 = 35 Tons 040 = 40 Tons 052 = 52 Tons 060 = 60 Tons 070 = 70 Tons 080 = 80 Tons 090 = 90 Tons 100 = 100 Tons 110 = 110 Tons 120 = 120 Tons 130 = 130 Tons
Digit 8 — Unit Voltage
A = 200V/60Hz/3 phase B = 230V/60Hz/3 phase D = 380V/60Hz/3 phase F = 460V/60Hz/3 phase G = 575V/60Hz/3 phase
Digit 9— Manufacturing Location
2 = Trane Commercial Systems, Pueblo, CO USA
Digits 10, 11 — Design Sequence
** = Factory assigned
Digit 12 — Unit Type
2 = High Efficiency 3 = Extra Efficiency
Digit 13 — Agency Listing
X = No Agency Listing A = Special ASME/Canadian Pressure Vessel Code E = ETL Listed/Certified to CSA/Conforms to UL
Digit 14 — Pressure Vessel Code
X = BPHE— exempt from ASME 1 = Special ASME/Canadian Pressure Vessel Code
Digit 15 — Unit Application
B = High Ambient (32-125°F/0-52°C) D = Wide Ambient (0-125°F/-18-52°C) J = Extreme Low Ambient — down to -20°F (-28.9° C)
Digit 16— Refrigerant Isolation Valves
2 = Refrigerant isolation valve(discharge valve)s
Digit 17 — Structural Options
A = Standard Unit Structure
Digit 18 — Freeze Protection (Factor- Installed Only)
X = Without Freeze Protection 1 = With Freeze Protection (External T-Stat control)
Digit 19 — Insulation
A = Factory Insulation - All Cold Parts B = Insulation for High Humidity/Low Evap Temp
Digit 20 — Factory Charge
3 = Full Factory Refrigerant Charge R-454B 4 = Nitrogen Charge — R-454B Field Supplied
Digit 21 — Evaporator Application
A = Standard Cooling (40 to 65°F/4.4 to 18°C) B = Low Temperature Process (10 to 40°F/-12.2 to 4.4°C) C = Ice-Making - Hardwired Interface (20 to 65°F/-7 to 18°C) D = Low leaving water (below 10°F/-12.2°C)
Digit 22 —Water Connections
1 = Grooved Pipe Connection
Digit 23 — Condenser Fin Material
A = Lanced Aluminum Fins D = Lanced Aluminum Fins with CompleteCoat™
Digit 24 — Condenser Heat Recovery
X = No Heat Recovery
Digit 25 — Not Used
X
Digit 26 — Starter Type
A = Across the Line Starter/Direct On Line
Digit 27 — Incoming Power Line Connection
1 = Single Point Power Connect
Digit 28— Power LIne Connection Type
A = Terminal Block C = Circuit Breaker Standard Fault D = Circuit Breaker with High Fault Rated Control Panel E = Circuit Breaker with High Fault Rated Control Panel with Energy Meter
Digit 29 — Enclosure Type
2 = Enclosure type UL 60335 Rated for Outdoor Applications
Digit 30 — Unit Operator Interface
B = Tracer® AdaptiView™ TD7
Digit 31 — Remote Interface (Digital Comm)
X = No Remote Digital Communication 2 = LonTalk®/Tracer® Summit Interface 4 = BACNet® Interface
Digit 32 — External Chilled/Hot Water and Current Demand Limit Setpoint
X = No External Chilled Water Setpoint A = External Chilled Water and Demand Limit Setpoint 4-20 mA B = External Chilled Water and Demand Limit Setpoint 2-10 Vdc
Digit 33 — Percent Capacity
X = Without Percent Capacity 1 = With Percent Capacity
Digit 34 — Programmable Relays
X = No Programmable Relays A = With Programmable Relays
Digit 35 — Pump Type
X = No Pumps and No Contactors 8 = Dual High Head Pump
FA460825QC050
Attachment 1
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
14 CG-PRC017T-EN
Digit 36 — Pump Flow Control
X = No Pump Control B = Pump Flow Controlled by the Variable Speed Drive
Digit 37 — Buffer Tank
X = No Buffer Tank 1 = Buffer Tank
Digit 38 — Short Circuit Rating
X = No Short Circuit Rating A = Default A Short Circuit Rating B = High A Short Circuit Rating
Digit 39 — Installation Accessories
X = No Installation Accessories 1 = Elastomeric Isolators 5 = Elastomeric Pads
Digit 40 —Water Strainer
A = With Water Strainer Factory Installed
Digit 41 — Sound Attenuator Package
3 = Super Quiet 5 = Comprehensive Acoustic Package
Digit 42 — Appearance Options
X = No Appearance Options A = Architectural Louvered Panels B = Half Louvers
Digit 43 — Exterior Finish
1 = Standard Paint
Digit 44 — Label, Literature Language
B = Spanish and English D = English E = French and English
Digit 45 — Phase Reversal Protection
1 = Phase Reversal Protection 2 = Convenience Outlet and Phase Reversal Protection
Digit 46 — Shipping Package
X = No Skid (Standard) A = Unit Containerization Package B = Shipped with tarp Covering Full Unit C = Unit Containerization Package and Tarp
Digit 47 — Performance Test Options
X = No Performance Test 1 = Customer Inspecition 2 = One-Point Test with Report 3 = Witness One-PointTest with Report 4 = Operational Test with Water
Digit 48 — Flow Switch Setpoint
C = Flow Switch Setpoint 15 F = Flow Switch Setpoint 35 H = Flow Switch Setpoint 45 L = Flow Switch Setpoint 60
Digit 49 —Wireless Connectivity Options
X = None A = Wi-Fi® B = LTE Modem C = Air-Fi™ D = Wi-Fi and LTE Modem E = Wi-Fi and Air-Fi F = LTE Modem and Air-Fi G = Wi-Fi, LTE Modem and Air-Fi
Digit 50 — Specials
X = None S = Special
Note: If a digit is not defined, it may be held for future use.
Model Number Descriptions
FA460825QC050
Attachment 1
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
| FY25 2 CES-CEO Form 9 planning - B6237 80-ton 200 Volt Chiller LRS.pdf |
| FY25 2 CES-CEO 2CONS_Coordination_Checklist B6237 080-ton 200 Volt Chiller Replacement.pdf |
| FY25 2 CES-CEO Chiller Specifications B6237 80-ton 200 Volt CGAM Chiller.pdf |
| Tech Eval 3 - 25QC050 (LRS Chiller B6237).pdf |
| Offer 3 Techical Evaluation Template - Copy.pdf |
| Offer 3 Technologisty Quote - 25QC050.pdf |
| Tech Eval 2 - 25QC050 (LRS Chiller B6237).pdf |
| Offer 2 Techical Evaluation Template.pdf |
| Accentz Quote - 25QC050_Redacted.pdf |
| Tech Eval 1 - 25QC050 (LRS Chiller B6237).pdf |
| offer 1 Techical Evaluation Template.pdf |
| Offer 1 Westex Quote - 25QC050.pdf |
| Tech Eval 3 - 25QC043 (96th Bomb Squadron Chiller B6603)-Signed Unacceptable.pdf |
| Offer 3 Techical Evaluation Template - Copy - Copy.pdf |
| Offer 3 Stateline Solution Quote - 25QC043.pdf |
| Tech Eval 2 - 25QC043 (96th Bomb Squadron Chiller B6603)-Signed Unacceptable.pdf |
| Offer 2 Techical Evaluation Template - Copy.pdf |
| Offer 2 Technologisty Quote - 25QC043.pdf |
| Tech Eval 1 - 25QC043 (96th Bomb Squadron Chiller B6603)-Signed Unacceptable.pdf |
| Offer 1 Techical Evaluation Template.pdf |
| Offer 1 Accentz Quote - 25QC043.pdf |
| Tech Eval 1 - 25QC053 (Fire Station 1 Chiller B6426)-Signed Acceptable.pdf |
| Techical Evaluation Template.pdf |
| Accentz Quote - 25QC053_Redacted.pdf |
| Tech Eval 1 - 25QC054 (Youth Center Chiller)-Signed Unacceptable.pdf |
| Tech Eval 1 - 25QC054 (Youth Center Chiller).pdf |
| Accentz Quote - 25QC054_Redacted.pdf |
File details come from the government source that posted it. Updated .