Attachment 4 - Questions and Answers.pdf

PDF 796 KB Posted

Attached to
Barksdale AFB - Cathodic Protection Survey Service Federal contract opportunity
Solicitation number
FA460823QS052
Issued by
Department of the Air Force Global Strike Command

About this file

This document contains questions and answers regarding cathodic protection surveys for two underground storage tanks at Barksdale Air Force Base. The questions and answers provide limited information about the tanks, including their construction years and available drawings. It is unknown if the tanks currently have cathodic protection systems or if as-built drawings or commissioning reports exist for any such systems. The related federal contract opportunity is for cathodic protection survey services at Barksdale AFB, solicited by the Department of the Air Force Global Strike Command under solicitation number FA460823QS052. Specific requirements, response dates, and other salient details are not provided.

View the file

Other files for this federal contract opportunity

Other files attached to Barksdale AFB - Cathodic Protection Survey Service, newest first.
File Type Posted
Attachment 1 - Performance Work Statement PWS v2.pdf PDF
Attachment 2 - Wage Determination (15-5191).pdf PDF
Attachment 3 - Considerations.pdf PDF
23QS052 - Combo Synopsis 2 Cathodic Protection 2.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 4 – Questions & Answers – FA460823QS052

Q: Do you have information on these two tanks?

A: Information that is listed for the tanks is IAW the Performance Work Statement (PWS).

Included are the drawings for Tank 8100 and 8077.

Q: When were they constructed?

A: Tank 8077: 1997

‐ See attached picture of nameplate

Attachment 4 – Questions & Answers – FA460823QS052

Tank 8100: 2008 ‐ See attached picture of nameplate

Q: Are the currently afforded cathodic protection?

A: Tank 8077: information about equipment that is known is included in the PWS.

Tank 8100: Not able to identify any test points or equipment at the tank. Ideally, survey will be able to determine.

Q: If so, does tank 8077 have an external cathodic protection system also?

A: Unknown if this tank has a rectifier or an anode bed. This needs to be assessed as part of the survey.

Q:Iftheyhavecathodicprotection,doyouhaveasbuiltdrawingsandacommissioning
reportforeachnewcathodicprotectionsystem?

A: Barksdale AFB does not have “as built” drawings or commissioning reports for the cathodic protection on either of these tanks cathodic protection systems.