ENGINEERING REVIEW COMMENTS
DATE: Page _1_ of _2_ Pages
BASE:
Barksdale AFB
PROJECT TITLE: ADD/ALTER RECREATIONAL
VEHICLE (RV) STORAGE LOT
PROJECT NUMBER:
AWUB-09-0176
___ Title 1- B 35% DESIGN 65% DESIGN 95% DESIGN 100% DESIGN
NAME OF REVIEWER
Allen Plavny
ORGANIZATION/SECTION
2 CS/SCOM
PHONE NUMBER: 318-456-6617 / cell# 318-208-2133
COMMERCIAL:
DSN:
Architectural Mechanical Electrical Civil Other COMM.
Legend (For ACTION Column)
A - APPROVED D - DISAPPROVED C - CONCUR E - EXCEPTION
ITEM
NO.
DRAWING NO.
OR
PARA NO.
COMMENT
ACTION
1 Elect. Details
DETAIL – A: TYPICAL GATE SYSTEM DIAGRAM, ADD the following as note E5, Install a 12 pair PE89 (shielded) copper cable from building 7055 to a weatherproof NEMA Enclosure. Terminate cable at both ends on protector terminal P/N R66P25QC (EMERSON) with GAS protector Modules installed P/N 104410147 (AVAYA) (24 each) Mount terminal block to a plywood backboard within NEMA enclosure at gate location, (in building 7055 terminate the cable in the Comm. room on plywood backboard. At both locations terminal blocks shall be mounted on standoff brackets P/N S89B. Within the weatherproof NEMA enclosure also install an Allen Tel modular surface mount jack Model AT468-4 or equivalent. Exact placement terminal apparatus items to be coordinated with 2
CS.
2 Elect. Details
DETAIL – A: TYPICAL GATE SYSTEM ADD the following as note - Provide/install a one inch diameter schedule 40 conduit from Handhole 602 conduit to NEMA enclosure (conduit shall be sealed inside and outside of handhole with a concrete based grout).
Provide/install 1inch EMT conduit from Weatherproof NEMA enclosure to IT control cabinet housing AM3Plus equipment.