Site_visit_and_RFP_QA_2.pdf
PDF 110 KB Posted
- Attached to
- C2F Mx & Repair Bldg 1000
- Solicitation number
- FA4600-16-R-0010
About this file
Q&A 2
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_2.pdf | ||
| Site_and_RFP_visit_QA_1.pdf | ||
| FA4600-16-R-0010_Amendment_1.pdf | ||
| CDRLS.zip | ZIP file | |
| J3_QASP.pdf | ||
| J18_DD_254_Cont_Sht.pdf | ||
| J13__PPQ_Cvr_Ltr.docx | DOCX document | |
| J7_DODI_8582.01.pdf | ||
| J5_SF328.pdf | ||
| J11_OFCCP_EEOC_Clrnc_Req.doc | DOC document | |
| J10_Wg_Dtrmntn_Rev_17.pdf | ||
| J12_Pst_Perf_Info_(PPI)_Doc.doc | DOC document | |
| J8_DODM_5200.01 _Vol._4.pdf | ||
| FA4600-16-R-0010.pdf | ||
| J2_Pricing_Model.xlsx | XLSX spreadsheet | |
| J20_SGFP_Attachment.pdf | ||
| J17_Client_Auth_Ltr.docx | DOCX document | |
| J14_Pst_Prsnt_Perf_Qstnr.docx | DOCX document | |
| J18_DD254_S.pdf | ||
| J4_CoI.pdf | ||
| J16_Sub-KT_Tm_Consent_Ltr.docx | DOCX document | |
| J1_-_Maps_drw_eqp_list.pdf | ||
| J19_Local_Inst.rtf | RTF text file | |
| J18_DD254_TS.pdf | ||
| J6_NDA_Agrmnt.pdf | ||
| J21_EAL_Template.xlsx | XLSX spreadsheet | |
| J15_Pst_Perf_Trkng_Rec.docx | DOCX document | |
| J9_KT_Val.xls | XLS spreadsheet |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
08 Dec 16
MEMORANDUM FOR C2F Maintenance & Repair Requirement
FROM: Tricia Abel, Contract Administrator
SUBJECT: FA4600-16-R-0010, C2F Mx & Repair Bldg 1000, Site-Visit and Solicitation Questions 2
1. Below are additional questions and answers from the site visit and solicitation:
Question 1: What is the voltage demarcation point with 55 CES and the contractor?
Gov’t Response: Electrical demarcation point –
1. 55 CES is responsible for:
a. All medium voltage (13.8 kV) service entrance including the first service entrance 13.8kV/480v transformers (2 ea.).
b. All generators and the circuit breakers remote operated from the Powerplant.
2. Contractor is responsible for:
a. All the facility electric system less than 600 V including conductors to the secondary side of the
13.8kV/480v service entrance transformers..
Question 2: Is there no commercial network? (concerning the computer systems the contractors will use in their Operation Room)
Gov’t Response: The contractor will be allowed to use the STRATCOM NIPR networks but will not have access to commercial internet within the facility.
From the vendor questions on the solicitation:
Question 3. RFP Page 38, Section 1.4.1 What Government Furnished Equipment [GFE] will the Contractor be given to use at the beginning of the contract?
Gov’t Response: This answer is unavailable at this time.