16195 Electrical Identification.pdf

PDF 32 KB Posted

Attached to
RECOVERY - SGBP080089 - Repair Air Circulation Hi-Bay Fac
Solicitation number
FA4600-09-B-0001
Issued by

About this file

Attachment #1 Specs

View the file

Other files

File Type Posted
16 OF 19.dwf DWF file
15 OF 19.dwf DWF file
Amendment 2.doc DOC document
19 OF 19.dwf DWF file
14 OF 19.dwf DWF file
01 OF 19.dwf DWF file
Amendment 1.doc DOC document
08-0089 Section 1C Dec 2007.pdf PDF
08-0089 Section 1B Dec 2007.pdf PDF
16 OF 19.dwf DWF file
Atch 7 NCIC Data.doc DOC document
15985 Sequence of Operation.pdf PDF
04 OF 19.dwf DWF file
01 OF 19.dwf DWF file
11 OF 19.dwf DWF file
Atch 6 offeror checklist.doc DOC document
02 OF 19.dwf DWF file
15810 Fans.pdf PDF
15 OF 19.dwf DWF file
16120 Wires and Cables.pdf PDF
Cover.pdf PDF
16010 General Electrical.pdf PDF
Atch 4 General Decision Number.doc DOC document
17 OF 19.dwf DWF file
TOC.pdf PDF
18 OF 19.dwf DWF file
15000 Mechanical General Provisions.pdf PDF
15971 Final Electric Control Systems & Facilities Management.pdf PDF
14 OF 19.dwf DWF file
19 OF 19.dwf DWF file
16143 Wiring Devices.pdf PDF
03 OF 19.dwf DWF file
08-0089 Section 1A Dec 2007.pdf PDF
13 OF 19.dwf DWF file
Solicitation.doc DOC document
06 OF 19.dwf DWF file
10 OF 19.dwf DWF file
12 OF 19.dwf DWF file
16110 Raceways.pdf PDF
15050 Basic Mechanical Materials and Methods.pdf PDF
16190 Supporting Devices.pdf PDF
09 OF 19.dwf DWF file
05 OF 19.dwf DWF file
082080 Sec B AF66.pdf PDF
16135 Electrical Boxes and Fittings.pdf PDF
07 OF 19.dwf DWF file
08 OF 19.dwf DWF file
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

16195-1

082080 2009 by FEI

SECTION 16195

ELECTRICAL IDENTIFICATION

PART 1 - GENERAL

1.1 SUMMARY

A. Extent of electrical identification is indicated by drawings.

B. Types of electrical identification specified in this section include the following:

1. Electrical power, control, and communication conductors.

2. Operational instructions and warnings.

3. Equipment/system identification signs.

PART 2 - PRODUCTS

2.1 ELECTRICAL IDENTIFICATION MATERIALS

A. General: Except as otherwise indicated, provide manufacturer's standard products of categories and types required for each application. Where more than one (1) single type is specified for an application, selection is Installer's option, but provide single selection for each application.

B. Engraved Plastic-Laminate Signs:

1. General: Provide engraving stock melamine plastic laminate, complying with FS L-P-387, in sizes and thicknesses indicated, engraved with engraver's standard letter style of sizes and wording indicated, black face and white core (letter color) except as otherwise indicated, punched for mechanical fastening except where adhesive mounting is necessary because of substrate.

a. Thickness: 1/16-inch, for units up to 20 sq. in. or 8-inch length; 1/8-inch for larger units.

b. Fasteners: Self-tapping stainless steel screws, except contact-type permanent adhesive where screws cannot or should not penetrate substrate.

2.2 LETTERING AND GRAPHICS

A. General: Coordinate names, abbreviations and other designations used in electrical identification work, with corresponding designations shown, specified or scheduled. Provide numbers, lettering and wording as indicated or, if not otherwise indicated, as recommended by manufacturers or as required for proper identification and operation/maintenance of electrical systems and equipment. Comply with

ANSI A13.1 pertaining to minimum sizes for letters and numbers.

PART 3 - EXECUTION

3.1 APPLICATION AND INSTALLATION

A. General Installation Requirements:

16195-2

082080 2009 by FEI

1. Install electrical identification products as indicated, in accordance with manufacturer's written instructions and requirements of NEC.

2. Coordination: Where identification is to be applied to surfaces, which require finish, install identification after completion of painting.

3. Regulations: Comply with governing regulations and requests of governing authorities for identification of electrical work.

B. Operational Identification and Warnings:

1. General: Wherever reasonably required to ensure safe and efficient operation and maintenance of electrical systems, and electrically connected mechanical systems and general systems and equipment, including prevention of misuse of electrical facilities by unauthorized personnel, install self-adhesive plastic signs or similar equivalent identification, instruction or warnings on switches, contactors, outlets and other controls, devices and covers of electrical enclosures. Where detailed instructions or explanations are needed, provide plasticized tags with clearly written messages adequate for intended purposes.

C. Equipment/System Identification:

1. General: Install engraved plastic-laminate sign on each major unit of electrical equipment in building; including central or master unit of each electrical system including communication/control/signal systems. Except as otherwise indicated, provide single line of text, 1/2-inch high lettering on 1-1/2-inch high sign (2-inch high where two (2) lines are required), white lettering in black field. Provide text matching terminology and numbering of the Contract Documents and shop drawings. Provide signs for each unit of the following categories of electrical work.

a. Electrical cabinets and enclosures.

b. Access panel/doors to electrical facilities.

c. Contactors.

2. Include description of served area on each sign.

3. Install signs at locations indicated or, where not otherwise indicated, at location for best convenience of viewing without interference with operation and maintenance of equipment.

Secure to substrate with fasteners, except use adhesive where fasteners should not or cannot penetrate substrate.

D. Cable/Conductor Identification:

1. General: Apply cable/conductor identification in each box/enclosure/cabinet, except where another form of identification (such as color-coded conductors) is provided. Match identification with marking system used in panelboards, shop drawings, contract documents, and similar previously established identification for project electrical work.

END OF SECTION