16120 Wires and Cables.pdf

PDF 39 KB Posted

Attached to
RECOVERY - SGBP080089 - Repair Air Circulation Hi-Bay Fac
Solicitation number
FA4600-09-B-0001
Issued by

About this file

Attachment #1 Specs

View the file

Other files

File Type Posted
16 OF 19.dwf DWF file
15 OF 19.dwf DWF file
Amendment 2.doc DOC document
19 OF 19.dwf DWF file
14 OF 19.dwf DWF file
01 OF 19.dwf DWF file
Amendment 1.doc DOC document
08-0089 Section 1C Dec 2007.pdf PDF
08-0089 Section 1B Dec 2007.pdf PDF
16 OF 19.dwf DWF file
Atch 7 NCIC Data.doc DOC document
15985 Sequence of Operation.pdf PDF
04 OF 19.dwf DWF file
01 OF 19.dwf DWF file
11 OF 19.dwf DWF file
Atch 6 offeror checklist.doc DOC document
02 OF 19.dwf DWF file
15810 Fans.pdf PDF
15 OF 19.dwf DWF file
Cover.pdf PDF
16010 General Electrical.pdf PDF
Atch 4 General Decision Number.doc DOC document
17 OF 19.dwf DWF file
TOC.pdf PDF
18 OF 19.dwf DWF file
15000 Mechanical General Provisions.pdf PDF
15971 Final Electric Control Systems & Facilities Management.pdf PDF
14 OF 19.dwf DWF file
19 OF 19.dwf DWF file
16143 Wiring Devices.pdf PDF
03 OF 19.dwf DWF file
08-0089 Section 1A Dec 2007.pdf PDF
13 OF 19.dwf DWF file
Solicitation.doc DOC document
06 OF 19.dwf DWF file
10 OF 19.dwf DWF file
12 OF 19.dwf DWF file
16110 Raceways.pdf PDF
15050 Basic Mechanical Materials and Methods.pdf PDF
16190 Supporting Devices.pdf PDF
09 OF 19.dwf DWF file
05 OF 19.dwf DWF file
082080 Sec B AF66.pdf PDF
16135 Electrical Boxes and Fittings.pdf PDF
07 OF 19.dwf DWF file
16195 Electrical Identification.pdf PDF
08 OF 19.dwf DWF file
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

16120-1

082080 2009 by FEI

SECTION 16120

WIRES AND CABLES

PART 1 - GENERAL

1.1 SUMMARY

A. Extent of electrical wire and cable work is indicated by drawings. Wires and cables shall be single, insulated conductors, field-installed in continuous raceways.

B. Types of electrical wire, cable and connectors specified in this section include the following:

1. Copper conductors.

2. Tap type connectors.

3. Wirenut connectors.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products of one (1) of the following

(for each type of wire, cable and connector):

1. Wire and Cable:

a. Apex Wire and Cable Corp.

b. American Insulated Wire Corp.

c. American Wire and Cable Co.

d. Belden Div; Cooper Industries.

e. Brand-Rex Div; Pyle National Co.

f. Cerro Wire and Cable Corp.

g. Cleveland Insulated Wire Co.

h. General Cable Corporation.

i. Helix Wire Corporation.

j. Houston Wire

k. Indiana Insulated Wire Inc.

l. Laribee Wire Manufacturing Co., Inc.

m. Madison Wire and Cable Corp.

n. Okonite Co.

o. Pirelli Cable Corp.

p. Radix Wire Co.

q. Rome Cable Corp.

r. Southwire Company.

s. Triangle PWC, Inc.

2. Connectors:

a. AMP, Inc.

b. Appleton Electric Co; Emerson Electric Co.

c. Buchanan Co.

d. Burndy Corporation.

e. Brand-Rex Div. Pyle National Co.

16120-2

f. Electrical Products Div; Midland-Ross Corp.

g. General Electric Co.

h. Gould, Inc.

i. Ideal Industries, Inc.

j. Leviton Mfg Company.

k. 3M Company

l. O-Z/Gedney Co.

m. Southport Industries Inc.

n. Square D Company.

o. Thomas and Betts Corp.

2.2 WIRES, CABLES AND CONNECTORS

A. General: All reference to size in these specifications or on drawings is for copper conductors. Provide electrical wires, cables and connectors of manufacturer's standard materials, as indicated by published product information; designed and constructed as recommended by manufacturer, for a complete installation and for application indicated. Except as otherwise indicated, provide copper conductors with conductivity of not less than 98% at 20 o C (68 o F).

B. Building Wires: Provide factory-fabricated wires of sizes, ampacity rating, and materials for applications and services indicated. Where not indicated, provide proper wire selection as determined by Installer to comply with project's installation requirements, NEC and NEMA Standards.

C. Cables: Provide UL-type factory-fabricated cables of sizes, ampacity ratings, and materials and jacketing/sheathing as indicated for services indicated. Where not indicated, provide proper selection as determined by Installer to comply with installation requirements, NEC and NEMA Standards.

D. Connectors: Provide UL-type factory-fabricated, metal connectors of sizes, ampacity ratings, materials, types and classes for applications and for services indicated. Where not indicated, provide proper selection as determined by Installer to comply with project's installation requirements, NEC and NEMA

Standards.

PART 3 - EXECUTION

3.1 INSTALLATION OF WIRES AND CABLES

A. General: Install electrical cables, wires and wiring connectors as indicated, in compliance with applicable requirements of NEC, NEMA, UL and NECA's "Standard of Installation" and in accordance with recognized industry practices.

B. The minimum size wire shall be 10 AWG. All wire No. 10 shall be solid, all No. 8 and larger shall be stranded. Provide a green insulated ground conductor for all circuits.

C. All feeder and branch circuit wiring shall be type THHN/THWN, except THWN-2 or XHHW-2 shall be used in wet locations.

D. Pull conductors simultaneously where more than one (1) is being installed in same raceway.

E. Use pulling compound or lubricant, where necessary; compound used must not deteriorate conductor or insulation. Use of soap will not be permitted as pulling lubricant.

F. Insulation on conductors shall be permanently marked with wire size, insulation type, voltage range and manufacturer's name. The insulation on conductors shall be color coded as follows:

16120-3

1. 120/208-volt circuit (match existing): Phase A - Black; Phase B - Red; Phase C - Blue.

2. 277/480-volt circuit (match existing): Phase A - Brown; Phase B - Orange; Phase C - Yellow.

G. The phase conductors shall be tagged and shall remain the same throughout the circuit.

H. Switch legs shall be color coded to distinguish them from Hot or Phase Conductors.

I. Switch legs occurring in the same box or enclosure shall be color coded separately.

J. Exceptions to the color coding as listed above shall be as follows:

1. Wiring for special systems shall be color coded or labeled as required by the manufacturer.

K. Use pulling means including, fish tape, cable, rope and basket weave wire/cable grips which will not damage cables or raceway.

L. Keep conductor splices to minimum.

M. Install splices and taps which possess equivalent-or-better mechanical strength and insulation ratings than conductors being spliced.

N. Use splice and tap connectors which are compatible with conductor material.

O. All splices and taps shall be made in outlet, junction and pull boxes. Splices on circuit wiring shall be of the pigtail type using solderless connectors. Larger sizes of conductors requiring uninsulated connectors of the bolt type shall be taped with pressure sensitive vinyl tape.

P. For branch circuit wiring, conductor fill per conduit run shall not contain more than eight (8) current carrying wires, provided the wire size is derated as required by the National Electrical Code. Conduits containing both circuit switch legs and/or traveler wires may contain more than the number stated above, providing the conduit is of adequate size and the wire size is derated as required by the National

Electrical Code. Whenever a 120-volt, single phase branch circuit is over 70-feet in length or a 277-volt, single phase branch circuit is over 150-feet, and the load is in excess of 50% of the branch circuit protective device, the conductors shall be increased one (1) size to the first outlet box unless specifically noted otherwise. For special systems conductor fill of conduit is per manufacturers specifications furnished with each system, noted on the drawings or shall be as required by code.

Q. Tighten electrical connectors and terminals, including screws and bolts, in accordance with manufacturer's published torque tightening values. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL

Standard 486A and B.

3.2 FIELD QUALITY CONTROL

A. Prior to energizing circuitry, check installed wires and cables with megohm meter to determine insulation resistance levels to ensure requirements are fulfilled.

B. Prior to energizing, test wires and cables for electrical continuity and for short-circuits.

C. Subsequent to wire and cable hook-ups, energize circuitry and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units and then retest to demonstrate compliance.

16120-4

END OF SECTION