This document is a Statement of Salient Characteristics for a Building 618 Roof Snow and Ice Retention System at Little Rock Air Force Base.

The Government requires a complete, non-penetrating, mechanically clamped snow and ice retention system for Building 618's vertical standing-seam metal roof. The system must be compatible with 24-gauge or thicker steel roof panels with standing seams of minimum 1.0-inch height and must mitigate falling snow and ice hazards above building entrances, accessible routes, and egress paths. The system shall attach exclusively to standing seams using stainless-steel mechanical clamps and cup-point set screws, with no roof penetrations, adhesive pads, or components that compromise the roof warranty. Each seam clamp must demonstrate a documented holding capacity of at least 1,500 pounds when installed on 24-gauge standing seams with a minimum installation torque of 90 inch-pounds.

Required materials include clamps and set screws of solid Type 304 or Type 316 stainless steel; extruded 6061-T6 structural-grade aluminum rails with factory-applied architectural coating or anodized finish compatible with existing roof color; and extruded aluminum ice stoppers (plastic or polycarbonate not acceptable). Rails must be structural hollow-core members measuring 1.25 to 2.00 inches in height and 1.00 to 1.75 inches in depth, with 6 to 8-foot section lengths. Ice stoppers shall extend vertically 2.25 to 3.50 inches below the rail, terminating within 0.25 inch of the roof pan. The proposed system must provide a minimum of 720 linear feet of continuous coverage and accommodate 0.75 to 1.0 inch of thermal movement through concealed internal sliding expansion sleeves. Each offeror must submit a project-specific layout and bill of materials identifying the proposed configuration, component quantities, attachment methods, and load distribution. Estimated quantities include 600 clamps, 1,200 set screws, 960 ice stoppers, 750 self-drilling fasteners, and 120 internal expansion splices for the 720-foot installation.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

Building 618 Roof Snow and Ice Retention System

1. Requirement The Government requires a complete roof snow and ice retention system for Building 618, which supports the Fuselage Training Facility. The system shall mitigate falling snow and ice hazards above building entrances, accessible routes, and egress paths.

The system shall be compatible with the existing vertical standing-seam metal roof and shall be provided as a complete, ready-to-install assembly. The proposed system shall meet all requirements stated below.

2. Roof Compatibility and Installation Method The system shall:

• Be a 100-percent non-penetrating, mechanically clamped system designed for vertical standing-seam metal roofs.

• Be compatible with steel roof panels of not less than 24-gauge thickness and standing seams with a minimum height of 1.0 inch.

• Use no roof penetrations, adhesive pads, glue-down components, or other attachment methods that could compromise the roof system or manufacturer warranty.

• Attach to the standing seams using stainless-steel mechanical clamps and cup-point set screws.

• Securely grip the seam without puncturing or damaging the roof protective paint, coating, or Galvalume surface.

3. Functional Requirements The snow and ice retention system shall:

• Provide a continuous horizontal barrier to retain accumulated snow and ice on the roof.

• Include vertical under-rail ice stoppers designed to prevent sheet ice from sliding beneath the rail.

• Reduce the risk of snow or ice shedding onto entrances, accessible ramps, pedestrian routes, and building egress areas.

• Allow snow and ice to melt and drain in manageable increments rather than releasing as large masses.

• Support compliance with applicable Architectural Barriers Act accessibility and NFPA 101 egress considerations.

4. Structural and Performance Requirements The system shall be designed to withstand applicable local snow and wind shear loads for Little Rock Air Force Base in accordance with UFC 3-301-01 and ASCE 7.

At a minimum:

• Each seam clamp shall have documented laboratory testing demonstrating a holding capacity of not less than 1,500 pounds per clamp when installed on 24-gauge steel standing seams.

• Clamp testing shall reflect installation torque of not less than 90 inch-pounds.

• Rail splices shall incorporate concealed internal sliding expansion sleeves or equivalent expansion capability.

• The expansion system shall accommodate not less than 0.75 inch to 1.0 inch of thermal movement.

• The offeror shall provide a project-specific layout showing rail placement, clamp spacing, and load distribution across the roof system.

5. Material Requirements

5.1 Clamps and Set Screws

• Clamps and set screws shall be constructed of solid Type 304 or Type 316 stainless steel.

• Each clamp shall use a minimum of two 3/8-inch stainless-steel cup-point set screws.

• Zinc-plated steel, carbon steel, plastic, or other materials susceptible to galvanic incompatibility or corrosion are not acceptable.

5.2 Rails

• Rails shall be manufactured from extruded 6061-T6 structural-grade aluminum alloy.

• Rails shall have a factory-applied architectural coating or anodized finish compatible with the existing roof color.

• Field painting is not acceptable.

• The system shall not require field-fabricated sheet-metal inserts or manually cut components for normal installation.

5.3 Ice Stoppers

• Ice stoppers shall be constructed of extruded aluminum suitable for outdoor roof-service conditions.

• Plastic or polycarbonate ice stoppers are not acceptable.

• Ice stoppers shall attach to the rail only and shall not contact or penetrate the roof deck.

6. Dimensional Requirements

6.1 Rail Profile

Rails shall be structural hollow-core members with the following dimensions:

• Height: 1.25 inches to 2.00 inches.

• Depth/width: 1.00 inch to 1.75 inches.

• Section length: 6 to 8 feet.

6.2 Clamps

Clamps shall have:

• Overall width: 1.00 inch to 2.00 inches.

• Standing-seam slot width: 0.50 inch to 0.75 inch.

• At least two 3/8-inch stainless-steel cup-point set screws.

6.3 Ice Stoppers

Ice stoppers shall:

• Extend vertically 2.25 inches to 3.50 inches below the rail.

• Terminate within 0.25 inch of the roof pan.

• Be configured to prevent thin sheet ice from passing beneath the rail.

7. Required System Components The contractor shall provide all components necessary for a complete and ready-to-install system, including at a minimum:

1. Extruded aluminum rails.

2. Non-penetrating stainless-steel standing-seam clamps.

3. Stainless-steel cup-point set screws, minimum two per clamp.

4. Fully concealed internal sliding expansion sleeve splices.

5. Aluminum ice stoppers mounted to the rail only.

6. Self-drilling fasteners for ice-stopper attachment, maximum size 1/4-inch-14 x 3/4-inch.

7. Specialty 3/16-inch Allen installation bits.

8. All incidental hardware required for installation and system operation.

8. Estimated Quantities and Alternate Solutions The quantities and component counts below are based on a known, commercially available system configuration and are provided for planning, pricing, and comparative purposes only. They are not intended to prescribe a particular manufacturer, model, or exact component configuration.

Offerors may propose an alternate snow and ice retention system, including different rail lengths, clamp spacing, splice quantities, ice-stopper quantities, or related hardware, provided the proposed system meets or exceeds all stated salient characteristics, functional requirements, material requirements, roof-compatibility requirements, and structural performance requirements.

Each offeror shall provide a project-specific layout and bill of materials identifying the proposed system configuration, total linear coverage, component quantities, attachment method, expansion provisions, and load distribution. The proposed configuration shall provide no less than 720 linear feet of continuous snow and ice retention coverage and shall be complete, compatible with the existing roof system, and ready for installation.

The Government will evaluate proposed alternate configurations for compliance with the stated salient characteristics and overall ability to meet the requirement.

Item Estimated Quantity

Continuous snow and ice retention barrier 720 linear feet

Rail sections Equivalent to 720 linear feet; e.g., 120 six-foot sections

Stainless-steel seam clamps 600 each

Stainless-steel set screws 1,200 each

Aluminum ice stoppers 960 each

Self-drilling fasteners 750 each

Internal expansion splices 120 each

3/16-inch Allen installation bits 15 each

1. Requirement
2. Roof Compatibility and Installation Method
3. Functional Requirements
4. Structural and Performance Requirements
5. Material Requirements
5.1 Clamps and Set Screws
5.2 Rails
5.3 Ice Stoppers
6. Dimensional Requirements
6.1 Rail Profile
6.2 Clamps
6.3 Ice Stoppers
7. Required System Components
8. Estimated Quantities and Alternate Solutions

File details come from the government source that posted it. Updated .