Attachment_2_Drawings_FTEV_13-1049B.pdf
PDF 799 KB Posted
- Attached to
- Replace Generators Federal contract opportunity
- Solicitation number
- FA4417-16-R-0006
About this file
Attachment 2 Drawings FTEV 13-1049B
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation_Extension_Amendment.pdf | ||
| Questions_and_Answers_7_Apr_16.docx | DOCX document | |
| Responses_to_Contractor_Questions_from_Pre-Bid_Site_Visit_(FTEV_13-1049B).pdf | ||
| Site_Visit_MFR_and_Roster.pdf | ||
| Solicitation _FA4417-16-R-0006.pdf | ||
| Attachment_6_Financial_Reference_Sheet.docx | DOCX document | |
| Attachment_4_Wage_Determination.pdf | ||
| Attachment_1_Specifications_FTEV_13-1049B.pdf | ||
| Attachment_5_Past_Present_Performance_Questionnaire.docx | DOCX document | |
| Attachment_3_GFP_Listing.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
unk
L e t o u r n e a u
C i r c l e
L e t o u r n e a u
C i r c l e
F o x x
A v e n u e
Tully Street
S i m p s o n e n u e
Tully Street
R e d
H o r s e
R o a d
Tupelo Circle
Bakke Street
M a y
S t r e e t
Bakke Street
R e d
H r s
R a d
Grimm Lane
Hume Drive
Bland Street
Galvan Street
Hume Drive
Lewis Drive
Hodges Street
Walters Drive
H u m
D r i v e
A c h i v e
H a r r i s i v e
Hume Drive
McIntosh Court
US98
O N e i l
A v e n u e
In d e p e n d e n c e
R o a d
US98
C o d y
A v e n u e
Purcell Drive
C a m p a i g r e e t
Whitbeck Street
Gelshlager Street
Clark Road
Hume Drive
Schmauss Lane
W e a v e n u e
US98
M cM illa n S tre et
C o r l w a d
W a l k p
W y
I n d e p e n d e n c a d
Bedel Street
B e n n e t t
A v e n u e
Frazier Street
C r u z
A v e n u e
Red Horse Road
C r u z
A v e n u e
T u l l r e e t
T u l l y
S t r e e t
Bedel Street
W e s t f a
C r c l e
H a m b
P a c e
R r a d
Tully Street
L u ka sik A ve n u e
C o e n u e
K e r w o o d
R o a d
US98
Lielmanis Avenue
H o w l t e y
US98
M a i n t e n a n a
T u l r e e t
US98
H a r t s r e e t
M c
C l e r e e t
T e r e n u e
I n d e p e n d e n a d
M i t c h e l l
R o a d
Bartley Street
D o w n s
R o a d
90918
92470
90043
90308
92006
92007
90600
92431
92081
90101
90761
91048
99045
91307
90325
90637
90106
90032
92469
90359
91159
92427
92550
91400
90030
92085
91265
90053
92046
90225
99061
99029
99118
90815
91301
90880
92093
91148
91303
99042
92429
91364
90366
91056
99500
90304
91254
90051
90531
99030
91045
90636
90062
92449
92519
90115
90370
90064
92403
90713
90326
92028
92019
92021
91047
90525
90806
90138
92060
90352
91029
90371
90137
92472
90748
90822
90128
90618
90035
90619
90532
90369
92065
90935
92438
90033
90702
91255
91520
90521
92091
90510
99142
90302
90345
90232
92404
90382
90215
92080
90617
92059
91137
92513
90003
92057
92042
92043
92037
92551
92017
92016
92107
91142
90300
90374
92546
92084
90048
99116
92099
99059
90621
92105
90339
91300
90008
92102
91163
90347
92098
90358
90825
99022
99145
99126
99044
90390
99056
99055
99083
99007
99105
91016
90552
99060
90131
99001
99998
90950
92090
92050
90334
91050
91350
91363
91130
90337
92538
92061 92082
90049
90760
90375
90229
90707
92052
92035
90615
92406
90105
90616
90928
99160
99999
99068
90635
91039
91009
90015
92432
92039
90121
91031
90801
90610
92275
92420
90759
92430
91151
91023
91140
92011
91037
90802
99043
91055
91252
92013
92000
90703
92528
92455
90005
90084
92024
92069
90328
90731
90372
92032
92030
90717
90145
91054
92436
91155
90346
90606
92452
92451
90378
92022
91012
90001
90223
90642
90054
90377
92040
92027
92026
91146
90230
90817
90056
92055
92010
92072
92076
92071
92068
92058
90058
91053
90333
90320
90827
92004
92100
99115
90207
92522
92087
91104
91103
90580
91105
92437
90809
91330
92553
90701
92548
90327
92435
90626
92549
92001
92008
92051
90724
91122
92434
90511
92009
92461
90085
90609
99023
99716
99717
99718
99719
99127
99051
99999
99999
99999
99025
99024
92005
90315
90210
99067
92034
91032
92023
99058
92505
90522
90509
90747
92089
91154
90330
92426
92419
92463
92501
99535
99150
92516
92541
90607
99104
99090
99048
99020
99106
99107
90340
90075
90577
92048
90711
92094
91133
90523
91112
92424
90388
99057
91510
99041
90068
90069
90629
90392
92064
90037
90141
99004
90362
92537
90613
90134
92014
92529
90052
91162
90951
92464
92025
92446
92515
91161
90381
90387
99112
92103
99053
99038
91057
90729
99094
99146
92502
92450
92033
91034
91132
91030
91152
92556
90076
91145
90911
90042
90102
92441
92471
90023
90357
90111
90070
92054
90355
90601
92527
91099
92407
92015
92400
92425
92079
91109
90914
91156
90811
90743
91007
91360
91325
90081
90833
92038
92533
99137
92095
90368
91052
91164
90742
92083
92555
92514
90823
90627
90810
92047
90361
99010
90714
90763
90109
92503
90329
91106
91135
91310
92460
92428
91266
99117
91500
92044
90213
92012
92036
92539
90039
90073
90074
91035
90505
92466
91120
91601
90926
91025
91603
91365
99158
99054
99043
92562
99999
99999
99019
90535
91351
99126
92062
91020
90036
90518
91370
92088
92063
92544
90402
90140
92521
99031
92473
91361
92518
92433
91027
91024
91515
92523
90318
92545
90373
90343
91147
92445
92530
90117
92092
90705
90517
92511
90331
92444
90079
91000
92401
91033
99098
90838
91538
91119
91114
90203
92045
90632
90720
92067
92097
92543
92506
92535
92524
92070
92056
92053
92041
92104
92106
92074
91268
92459
92508
91036
90624
92517
90625
91260
90553
90638
90066
90061
90057
91028
91021
92525
92440
99141
90816
92468
91144
90034
90755
90310
90220
92086
90551
90317
90050
90367
90323
92402
92467
90055
92018
91257
90029
92020
92002
92003
92073
90519
99065
92101
92463
90712
91013
92442
99902
92096
90135
91049
90829
92465
92408
90231
90603
91250
90322
92507
92066
90718
92049
90501
90640
90353
91041
92542
91153
92552
90002
92108
92276
92531
90758
90700
92439
90113
92564
91302
90812
90708
91126
90010
92077
90060
91136
91042
90332
91258
99910
91113
90630
90206
90421
90028
90020
92075
92078
92031
92500
91259
91262
90067
90059
92485
92509
92536
90349
90065
90612
99049
90228
90319
90221
91625
92418
99005
91141
90336
99009
90502
90412
90038
92540
90202
92557
91537
90503
90021
99077
99154
90628
92547
90506
91101
90507
90380
90379
91149
91124
29075
29075
29075
29075
90396
90396
29073
29073
90534
90581
90734
90005
91038
91043
29077
29077
W a l k p y
90512
90513
90513
90512
90360
90363
90351
92479
92478
92477
91264
91263
91261
91041
90813
90757
90749
90626
99121
90524
99103
90364
90356
90083
30041
D o w a d
90611
90500
90508
90311
90086
M
Y
T
R
E
E
T
91058
91059
99958
90917
90905
90306
91168
91107
91157
90534
90536
90800
Kissam Street
90727
30007
99326
BUILDING 90710
BUILDING 90730
BUILDING 90208
BUILDING 90063
BUILDING 90365
BUILDING 91546
LOCATION MAP
N.T.S.
LOCATION MAP & INDEX OF DRAWINGS
ELECTRICAL PLANS - BUILDING 90063
T-1
E-1
E-2
E-3
E-4
SHEET # TITLE
INDEX OF DRAWINGS
MAIN GATE
HAUL ROUTE
E-5
E-6
E-7
E-8
REPLACE GENERATOR 5 YEAR PLAN
MULTIPLE BUILDINGS
(BUILDINGS 90063, 90208, 90365, 90710, 90730 & 91546)
HURLBURT FIELD, FLORIDA
FTEV 13-1049B
DETAILS - BUILDING 90063
ELECTRICAL PLANS - BUILDING 90208
DETAILS - BUILDING 90208
ELECTRICAL PLANS - BUILDING 90365
ELECTRICAL PLANS - BUILDING 90710
ELECTRICAL PLANS - BUILDING 90730
ELECTRICAL PLANS - BUILDING 91546E-9
DETAILS - BUILDING 90710
GENERAL NOTES:
1. ENSURE THAT NO WASTEWATER ASSOCIATED WITH THE POURING OF ANY CONCRETE IS
DISCHARGED TO SURFACE WATERS OF THE STATE (E.G.: WETLANDS, STORMWATER SYSTEMS, ETC.)
2. TO ENSURE THE REQUIREMENTS OF THE CLEAN AIR ACT AND AFI 32-7040 ARE MET, ALL GENERATOR
INFORMATION, INCLUDING ANY RUN-TIMES ASSOCIATED WITH THE INSTALLATION, MUST BE ENTERED
INTO THE AIR PROGRAM INFORMATION MANAGEMENT SYSTEM (APIMS). THIS INFORMATION AND DATA
MUST BE REPORTED TO MR. BARRY L. WOODS, 1 SOCES/CEIE, (850) 884-4652.
3. CONSTRUCTION AT EACH INDIVIDUAL BUILDING SHALL BE ACCOMPLISHED INDIVIDUALLY. THE
COMPLETE REMOVAL, CONSTRUCTION, REINSTALLATION, TESTING, AND GOVERNMENT ACCEPTANCE
OF EACH BUILDING SHALL BE COMPLETED BEFORE THE CONTRACTOR WILL BE ALLOWED TO START
CONSTRUCTION AT THE NEXT BUILDING.
4. POWER OUTAGES REQUIRED FOR CONSTRUCTION ACTIVITIES TO THE ELECTRICAL SERVICES TO
FACILITIES SHALL NOT EXCEED 12 HOURS AT A TIME.
5. THE CONTRACTOR SHALL PROVIDE FACTORY CERTIFIED GENERATOR START-UP PERSONNEL TO
PERFORM FACTORY START-UP IN ORDER TO BEGIN FACTORY WARRANTY.
6. WORK IS AUTHORIZED ON WEEKEND WITH PRIOR APPROVAL.
7. ENSURE CLEARANCES AROUND GENERATOR ARE AT LEAST 48” AT CONSTRUCTION COMPLETION.
8. FOR GENERATORS 250KW AND ABOVE THE CONTRACTOR SHALL PROVIDE 4” BOX BEAMS UNDER THE
GENERATOR TO PROVIDE CLEARANCE.
9. CONTROL WIRING IS CAT 5 CABLE.
POWER PRODUCTION SHOP
27 JAN 2015
OF 10
FTEV 13-1049B
JRH/EWW
JRH
MULTIPLE
T-1
L O
C A
T I O
N
M
P
I N
D E
X
O
F
D
R A
W I N
G
ELECTRICAL PLAN - BUILDING 90063 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - BUILDING 90063 - NEW WORK
SCALE: 1/8" = 1'-0"
REMOVE EXISTING 350 KW GENERATOR SET.
EXISTING PAD MOUNTED TRANSFORMER
EXISTING 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION
REMOVE EXISTING SECONDARY CONDUIT & WIRING FROM
TRANSFORMER SECONDARY LUGS TO EXISTING AUTOMATIC
TRANSFER SWITCH. SEE "SINGLE LINE DIAGRAM -
DEMOLITION," SHEET E-2. EXISTING SECONDARY ROUTED
FROM AUTOMATIC TRANSFER SWITCH, THRU PAD MOUNTED
TRANSFORMER TO BUILDING SERVICE PANEL SHALL REMAIN.
NEW 600 A., 3 P. MAIN BREAKER IN NEMA 3R
ENCLOSURE. MOUNT ON NEW SUPPORT
STRUCTURE. SEE "DETAIL - MAIN BREAKER
SUPPORT STRUCTURE," SHEET E-2.
NEW UNDERGROUND SECONDARY - EXTEND INTO SIDE
OF EXISTING TRANSFORMER SECONDARY SECTION.
SEE "SINGLE LINE DIAGRAM - NEW WORK," SHEET E-2.
NEW SECONDARY CONDUIT &
WIRING. SEE "SINGLE LINE
DIAGRAM - NEW WORK," SHEET E-2.
E
U
S
E U
S
E U
S
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 150 KW.
NEW GENERATOR SET RATED AT 250 KW WILL BE LOADED AT 60%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 19.6 GPH.
48 HOUR FUEL CONSUMPTION AT FULL LOAD IS 941 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 60% IS APPROXIMATELY 12.8 GPH.
48 HOUR FUEL CONSUMPTION AT 60% IS APPROXIMATELY 614 GALLONS.
NEW SUB-BASE FUEL TANK SHALL HAVE 600 GALLON CAPACITY.
600 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 47 HOURS OF BACKUP POWER.
DEMOLISH EXISTING CONCRETE PAD.
REMOVE EXISTING SECONDARY WIRING. REMOVE
EXISTING CONDUIT BELOW EXISTING CONCRETE
PAD. REUSE EXISTING CONDUIT ENTRANCE INTO
EXISTING AUTOMATIC TRANSFER SWITCH.
INSTALL NEW 250 KW GENERATOR SET
ON NEW CONCRETE PAD.
U
S
OUTLINE OF GENERATOR HOUSING
SPECIFICATIONS
GRID (TYPICAL)
SECURE GENERATOR SET TO
CONCRETE PAD W/ ANCHOR
BOLTS PER MANUFACTURER'S
# 2/0 BARE COPPER GROUND
# 2/0 GROUND - 30" MIN. BELOW GRADE.
#4 BARS AT 12" O.C. EACH WAY (TYP.)
EMERGENCY GENERATOR PAD DETAILS
ALL GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDEDNOTE:
2#4 CONT. (TYP.)
ASECTION
N.T.S.
E1 E1
12"
4"
8" MINIMUM
6" TYPICAL
PLAN VIEW
N.T.S.
16"
3/4" X 20'-0" COPPERCLAD
GROUND ROD (TYP. - 4.)
3500 PSI CONCRETE PAD
A
BOND # 2/0 TO GENERATOR FRAME
E1 E1
FINISHED GRADE
GENERAL NOTES:GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER
SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER
PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO
A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND
DISPOSE OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
BASIS OF DESIGN:
CUMMINS 250 KW DQDAA W/ 600 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 188" LONG X 82" WIDE X 111" HIGH.
REMOVE EXISTING 120 V WIRING. REMOVE EXISTING CONDUIT
TO A POINT BELOW GRADE. REUSE EXISTING CONDUIT &
EXTEND INTO NEW GENERATOR SET. SEE NEW WORK PLAN.
INTERCEPT EXISTING CONDUIT & EXTEND INTO NEW
GENERATOR SET. PULL IN NEW 120 VOLT WIRING FROM
EXISTING DISCONNECT SWITCH MOUNTED ON DRY TYPE
TRANSFORMER TO DUPLEX RECEPTACLE IN GENERATOR
HOUSING.
REMOVE EXISTING CONTROL WIRING. REMOVE EXISTING CONDUIT TO A
POINT BELOW GRADE. REUSE EXISTING CONDUIT & EXTEND INTO NEW
GENERATOR SET. SEE NEW WORK PLAN.
INTERCEPT EXISTING CONDUIT & EXTEND INTO NEW
GENERATOR SET. PULL IN NEW CONTROL WIRING FROM
EXISTING AUTOMATIC TRANSFER SWITCH TO NEW
GENERATOR SET.
EXISTING ELECTRICAL SERVICE GROUNDING NOTE:
REMOVE EXISTING SERVICE GROUND CONNECTIONS IN EXISTING MAIN PANEL. REMOVE EXISTING
GROUND CONDUCTOR BONDING NEUTRAL BUS TO GROUND BUS IN EXISTING MAIN PANEL.
EXISTING SCADA CONDUIT &
WIRING TO REMAIN.
27 JAN 2015
90063
E-1
E L E
C T
R I C
A L
P
L A
B
U I L D
I N
G
MAIN BKR.
600 A., 3 P.
EUS
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
EXISTING PAD MOUNTED
TRANSFORMER
US
G
EUS
EUS
EXISTING 600 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
REMOVE EXISTING 350 KW
EMERGENCY GENERATOR SET.
REMOVE EXISTING
CONDUIT & WIRING.
EUS
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
EXISTING PAD MOUNTED
TRANSFORMER
G
EUS
EXISTING 600 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
NEW 250 KW/312.5 KVA, 480Y/277 V., 3Ø
EMERGENCY GENERATOR SET.
1 5/8" X 1 5/8" 12 GAUGE HOT-
DETAIL - MAIN BREAKER SUPPORT STRUCTURE
PVC, SCH. 40 CONDUIT
FINISH GRADE
CONCRETE FOOTING
N.T.S.
18" SQUARE
12"
1" CHAMFER
ENCLOSED CIRCUIT BREAKER
DIPPED GALV. STEEL CHANNEL
2"
48"±
BREAKER
REQD. FOR
WIDTH AS
ENCLOSURE
WEATHERPROOF
"LB" FITTINGS
REMOVE EXISTING CONTROL WIRING
& A PORTION OF CONDUIT.
REMOVE EXISTING SECONDARY
WIRING & A PORTION OF CONDUIT.
US
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
NEW GENERATOR ELEVATION
N.T.S.
WORK NOTES:
1 PROVIDE NEW SECONDARY CONDUIT & WIRING CONNECTION TO GENERATOR CIRCUIT
BREAKER ENCLOSURE. SEE "SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET.
PROVIDE NEW 120 VOLT CONDUIT & WIRING CONNECTION TO DUPLEX RECEPTACLE IN
GENERATOR HOUSING.
PROVIDE NEW CONDUIT & CONTROL WIRING CONNECTION TO NEW GENERATOR SET
FROM EXISTING AUTOMATIC TRANSFER SWITCH.
4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING
GENERATOR SET. MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE.
2 PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 2/0 GND. -
3 1/2" RIGID GALV. STEEL CONDUIT
2 PARALLEL CIRCUITS OF 4 - 350 MCM - 3 1/2" PVC,
SCH. 40 CONDUIT. CONVERT PVC, SCH. 40 CONDUIT
TO PVC, SCH. 80 BEFORE IT RISES ABOVE GRADE TO
NEW MAIN BREAKER.
# 2/0 CU. - 3/4" PVC, SCH. 80 TO 3/4"
X 20'-0" COPPERCLAD GROUND ROD
# 2/0 CU. - 3/4" PVC, SCH. 80 TO
METALLIC COLD WATER PIPE
2 PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 2/0 GND. -
3 1/2" PVC, SCH. 40 CONDUIT
EXISTING UNDERGROUND
SECONDARY TO REMAIN.
INSTALL GENERATOR CONTROL
WIRING IN 1" PVC, SCH. 40 CONDUIT
27 JAN 2015
90063
E-2
D E
T A
I
U I L D
I N
G
EXISTING PANEL "MDP"
ELECTRICAL PLAN - BUILDING 90208 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - BUILDING 90208 - NEW WORK
SCALE: 1/8" = 1'-0"
EXISTING PANEL "MP"
EXISTING PANEL "MA"
E3 E3
A
ELEVATION
SCALE: 1/4" = 1'-0"
E3 E3
A
NORMAL
LOAD
EMERGENCY
EXISTING POLARIS INSULATED
CONNECTOR BLOCKS
EXISTING ATS WIRING DIAGRAM
N.T.S.
EXISTING C.T.'S
EXISTING PULL BOX
REMOVE EXISTING 150 KW GENERATOR SET.
EXISTING PAD MOUNTED TRANSFORMER
EXISTING PANEL "MDP"
EXISTING PANEL "MP"
EXISTING PANEL "MA"
EXISTING PULL BOX
EXISTING PAD MOUNTED TRANSFORMER
REINSTALL EXISTING 300 A., 3 P.
ENCLOSED CIRCUIT BREAKER
NEW 600 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION.
TEMPORARILY REMOVE EXISTING 300 A., 3 P.
ENCLOSED CIRCUIT BREAKER.
REMOVE EXISTING 600 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
INSTALL NEW 100 KW GENERATOR SET.
REMOVE EXISTING 600 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
TEMPORARILY REMOVE EXISTING 300 A.,
3 P. ENCLOSED CIRCUIT BREAKER.
EXISTING PULL BOX
EXISTING PANEL "MP"
TEMPORARILY DISCONNECT ALL
EXISTING CONDUIT & WIRING
CONNECTIONS FROM EXISTING
AUTOMATIC TRANSFER SWITCH &
RECONNECT TO NEW SWITCH.
E
U
S
E
U
S
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 45 KW.
NEW GENERATOR SET RATED AT 100 KW WILL BE LOADED AT 45%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 8.87 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 638 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 50% IS 5.0 GPH.
72 HOUR FUEL CONSUMPTION AT 50% IS 360 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 100 KW GENERATOR SET W/ WEATHER PROTECTIVE ENCLOSURE
IS 309 GALLONS.
309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 61.8 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 100 KW DSGAA W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
RECONNECT EXISTING GROUND
CONDUCTOR TO GENERATOR FRAME.
EXISTING CONCRETE BLOCK SCREEN WALL
27 JAN 2015
90208
E-3
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
EXISTING PAD MOUNTED
TRANSFORMER
G
EUSEUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
NEW 100 KW/125 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
REMOVE EXISTING 600 A., 3 P.
AUTOMATIC TRANSFER SWITCH.
EXISTING
MAIN
PANEL
EXISTING
PANEL
"MP"
"MDP"
EXISTING
PANEL
"MA"
EXISTING PULL BOX
EXISTING 300 A., 3 P.,
ENCLOSED CIRCUIT BREAKER
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
EXISTING PAD MOUNTED
TRANSFORMER
G
EUSEUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
REMOVE EXISTING 150 KW
EMERGENCY GENERATOR SET.
NEW 600 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
EXISTING
MAIN
PANEL
EXISTING
PANEL
"MP"
"MDP"
EXISTING
PANEL
"MA"
EXISTING PULL BOX
EXISTING 300 A., 3 P.,
ENCLOSED CIRCUIT BREAKER
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
WORK NOTES:
1 EXISTING PARALLEL EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER
FEEDER NOTE," THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE
"SCADA WIRING NOTE," THIS SHEET.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED
WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
CONDUIT ENTRY OPENING
NEW GENERATOR ELEVATION
N.T.S.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE
EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
REMOVE EXISTING FLEXIBLE CONDUIT FROM EXISTING RECEPTACLE TO A POINT JUST ABOVE EXISTING
CONCRETE PAD. INSTALL WEATHERPROOF JUNCTION BOX ABOVE CONCRETE PAD AND BELOW NEW FUEL TANK
AS REQUIRED TO LINE UP WITH FUEL TANK CONDUIT ENTRY OPENING. EXTEND 2 # 12 & 1 # 12 GND. - 1/2" LIQUID
TIGHT FLEXIBLE METAL CONDUIT FROM JUNCTION BOX TO RELOCATED RECEPTACLE.
SCADA WIRING NOTE:
RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE
COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE CONTROLLER.
27 JAN 2015
90208
E-4
D E
T A
I
U I L D
I N
G
ELECTRICAL PLAN - BUILDING 90365 - DEMOLITION
SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - BUILDING 90365 - NEW WORK
BUILDING
90365
BUILDING
90365
EXISTING 225 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION
REMOVE EXISTING 35 KW GENERATOR SET. INSTALL NEW 20 KW, 208Y/120 V. GENERATOR SET.
EXISTING 225 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION
E
U
S
E
U
S
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 10 KW.
NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 50%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 50% IS 0.97 GPH.
72 HOUR FUEL CONSUMPTION AT 50% IS 70 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 91 GALLONS.
91 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 88 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE
EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. EXISTING 120 VOLT CIRCUIT IS
RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY POWER FEEDER. IN
THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE
EXISTING ENT CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE
EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER
SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING
CONTROL CIRCUIT IS RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY
POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW
CONTROLLER, REMOVE THE EXISTING ENT CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING
CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CONTROLLER.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING CONDUITS
FALL WITHIN THE CONDUIT ENTRY OPENING BELOW THE
GENERATOR CIRCUIT BREAKER.
NEW GENERATOR ELEVATION
N.T.S.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE
"SCADA WIRING NOTE," THIS SHEET.
5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
REMOVE EXISTING 35 KW
EMERGENCY GENERATOR SET.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING 225 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
NEW 20 KW/25 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
EUS
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
EXISTING 225 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EXISTING UNDERGROUND SECONDARY
TO REMAIN.
EUS
EXISTING MAIN
DISCONNECT SWITCH
EXISTING CONTROL WIRING & CONDUIT TO REMAIN.
EUS
27 JAN 2015
90365
E-5
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
ELECTRICAL PLAN - BUILDING 90710 - DEMOLITION
ELECTRICAL PLAN - BUILDING 90710 - NEW WORK
SCALE: 1/8" = 1'-0"
REMOVE EXISTING 35 KW GENERATOR SET.
ATS
ATS
E6 E6
A
ELEVATION
SCALE: 1/4" = 1'-0"
E6 E6
A
REMOVE EXISTING 225 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
INSTALL NEW 20 KW GENERATOR SET.
ELEVATION
SCALE: 1/4" = 1'-0"
E6 E6
B
E6 E6
B
REMOVE EXISTING 225 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
INSTALL NEW 225 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION.
EXISTING MAIN BREAKER
EXISTING PANEL "E"
EXISTING MAIN BREAKER
EXISTING PANEL "E"
EXISTING SCADA
EQUIPMENT CABINET
REMOVE EXISTING
CONDUIT & WIRING
EXISTING CONDUIT TO
REMAIN & BE REUSED.
EXISTING SCADA
EQUIPMENT CABINET
PULL NEW WIRING INTO
EXISTING CONDUITS.
INSTALL NEW 150 A., 4 POLE
AUTOMATIC TRANSFER SWITCH
W/ BYPASS/ISOLATION.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
PULL NEW SCADA WIRING FROM SCADA
EQUIPMENT CABINET TO NEW GENERATOR
SET THRU EXISTING CONDUIT PENETRATING
EXISTING EXTERIOR WALL.
EXISTING SCADA CIRCUIT CONDUIT
PENETRATION THRU EXTERIOR WALL
EXISTING POWER FEEDER CONDUIT
PENETRATION THRU EXTERIOR WALL
RECONNECT EXISTING GROUND CONDUCTOR
TO NEW GENERATOR BREAKER.
EXISTING CONCRETE BLOCK SCREEN WALL
27 JAN 2015
90710
E-6
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
MAIN BKR.
EXISTING
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
REMOVE EXISTING
CONDUIT & WIRING.
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
NEW 225 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
NEW 20 KW/25 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
EXISTING
PANEL
"E"
EXISTING DISCONNECT SWITCH
EXISTING GUTTER
MAIN BKR.
EXISTING
G
REMOVE EXISTING 35 KW
EMERGENCY GENERATOR SET.
EXISTING
PANEL
"E"
EXISTING DISCONNECT SWITCH
EXISTING GUTTER
REMOVE EXISTING 225 A., 3 P.
AUTOMATIC TRANSFER SWITCH.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 12 KW.
NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 60%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 60% IS APPROXIMATELY 1.21 GPH.
72 HOUR FUEL CONSUMPTION AT 60% IS 87 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE
ENCLOSURE IS 91 GALLONS.
91 GALLONS AT 60% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 75 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.
EMERGENCY POWER FEEDER NOTE:
INSTALL NEW EMERGENCY POWER FEEDER WIRING FROM NEW AUTOMATIC TRANSFER SWITCH TO GENERATOR
SET. REUSE EXISTING CONDUIT.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT
CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH
BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.
CONTROL WIRING NOTE:
INSTALL NEW CONTROL WIRING FROM NEW AUTOMATIC TRANSFER SWITCH TO GENERATOR SET. REUSE
EXISTING CONDUIT.
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY
OPENING BELOW THE GENERATOR CIRCUIT BREAKER.
NEW GENERATOR ELEVATION
N.T.S.
WORK NOTES:
1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"
THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE
"SCADA WIRING NOTE," THIS SHEET.
5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
6 REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED
WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH.
INTERCEPT EXISTING CONDUIT & EXTEND NEW 2 1/2"
CONDUIT TO NEW ATS. PULL IN NEW 4 # 3/0 & 1 # 6
GND. FROM EXISTING MAIN BREAKER TO NEW ATS.
INTERCEPT EXISTING CONDUIT & EXTEND NEW 2 1/2"
CONDUIT TO NEW ATS. PULL IN NEW 4 # 3/0 & 1 # 6
GND. FROM EXISTING GUTTER TO NEW ATS.
TERMINATE EXISTING CONDUIT INTO BACK OF ATS.
PULL IN NEW 4 # 3/0 & 1 # 6 GND. FROM EMERGENCY
GENERATOR SET TO NEW ATS. PULL IN NEW
CONTROL WIRING.
27 JAN 2015
90710
E-7
D E
T A
I
U I L D
I N
G
ELECTRICAL PLAN - BUILDING 90730 - DEMOLITION
ELECTRICAL PLAN - BUILDING 90730 - NEW WORK
SCALE: 1/8" = 1'-0"
E
U
S
E
U
S
REMOVE EXISTING 150 KW
EMERGENCY GENERATOR SET.
REMOVE EXISTING 800 A., 3 POLE
AUTOMATIC TRANSFER SWITCH.
INSTALL NEW 150 KW GENERATOR SET.
INSTALL NEW 800 A., 4 POLE AUTOMATIC
TRANSFER SWITCH W/ BYPASS/ISOLATION.
E U
S
EXISTING 800 A., 3 P. ENCLOSED
MAIN CIRCUIT BREAKER
E U
S
EXISTING PANEL "MDP"
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE
OF PROPERLY.
5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 70 KW.
NEW GENERATOR SET RATED AT 150 KW WILL BE LOADED AT 47%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 11.73 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 845 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 50% IS 6.94 GPH.
72 HOUR FUEL CONSUMPTION AT 50% IS 500 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 150 KW GENERATOR SET W/ WEATHER
PROTECTIVE ENCLOSURE IS 309 GALLONS.
309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE 45 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 150 KW DSGAC W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.
WORK NOTES:
1 REWORK EXISTING PARALLEL EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY
POWER FEEDER NOTE," THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
REWORK EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING ATS ENCLOSURE.
SEE "SCADA WIRING NOTE," THIS SHEET.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED
WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH. RECONNECT EXISTING
CONDUITS ENTERING INTO SIDE OF EXISTING ATS. RECONNECT EXISTING POWER FEEDERS, CONTROL
WIRING, ETC., AS REQUIRED TO MAKE THE NEW ATS FUNCTIONAL.
FUEL TANK
CONDUIT ENTRY OPENING
OUTLINE OF GENERATOR
CIRCUIT BREAKER
CONDUIT ENTRY OPENING
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
NEW GENERATOR ELEVATION
N.T.S.
EXISTING CONCRETE BLOCK SCREEN WALL
EMERGENCY POWER FEEDER NOTE:
REMOVE THE EXISTING PARALLEL FLEXIBLE CONDUIT CONNECTIONS TO THE EXISTING GENERATOR SET.
INSTALL NEW LIQUID-TIGHT FLEXIBLE CONDUITS W/ LENGTHS AS REQUIRED TO REACH THE NEW CONDUIT
ENTRY POINT. PULL EXISTING WIRING BACK INTO NEW CONDUITS & RECONNECT EXISTING EMERGENCY POWER
FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT THE EXISTING FEEDER IS NOT LONG
ENOUGH TO REACH THE NEW CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS
WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE
NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE
EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT
CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH
BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
REMOVE THE EXISTING FLEXIBLE CONDUIT CONNECTION TO THE EXISTING GENERATOR SET. INSTALL NEW
LIQUID-TIGHT FLEXBILE CONDUIT W/ LENGTH AS REQUIRED TO REACH THE NEW CONDUIT ENTRY POINT. PULL
EXISTING SCADA WIRING BACK INTO NEW CONDUIT & RECONNECT EXISTING SCADA WIRING TO NEW
GENERATOR CONTROLLER.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING
CONTROL WIRING IS INSTALLED IN THE SAME CONDUIT W/ THE EMERGENCY POWER FEEDER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE
COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE CONTROLLER.
RECONNECT EXISTING GROUND
CONDUCTOR TO NEW GENERATOR FRAME.
MAIN BKR.
EXISTING
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
NEW 800 A., 4 P. AUTOMATIC TRANSFER
SWITCH W/ BYPASS/ISOLATION.
NEW 150 KW/187.5 KVA, 208Y/120 V., 3Ø
EMERGENCY GENERATOR SET.
MAIN BKR.
EXISTING
G
REMOVE EXISTING 150 KW
EMERGENCY GENERATOR SET.
EXISTING
PANEL
"MDP"
REMOVE EXISTING 800 A., 3 P.
AUTOMATIC TRANSFER SWITCH.
EUS
EUS
EUS
EXISTING
PANEL
"MDP"
EUS
EUS
EXISTING UNDERGROUND
SECONDARY TO REMAIN.
EUS
EXISTING UNDERGROUND
SECONDARY TO REMAIN.
27 JAN 2015
90730
E-8
E L E
C T
R I C
A L
P
L A
U I L D
I N
G
ELECTRICAL PLAN - BUILDING 91546 - DEMOLITION
SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0"
ELECTRICAL PLAN - BUILDING 91546 - NEW WORK
ATS
REMOVE EXISTING 150 KW GENERATOR SET.
EXISTING 400 A., 4 POLE
AUTOMATIC TRANSFER SWITCH
EXISTING MAIN DISCONNECT
SWITCH
EXISTING MAINTENANCE -
BYPASS SAFETY SWITCH
EXISTING PAD MOUNTED
TRANSFORMER
E
U
S
ATS
EXISTING 400 A., 4 POLE
AUTOMATIC TRANSFER SWITCH
EXISTING MAIN DISCONNECT
SWITCH
EXISTING BYPASS SWITCH
EXISTING PAD MOUNTED
TRANSFORMER
E
U
S
INSTALL NEW 150 KW GENERATOR SET.
GENERAL NOTES:
1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT
FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY
THE CONTRACTOR.
2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO
BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES
THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE
CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT
FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.
3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER
SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.
4. THE GOVERNMENT SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS.
5. THE GOVERNMENT SHALL FILL THE NEW SUB-BASE FUEL TANKS WITH DIESEL FUEL.
6. NEW GENERATOR SETS SHALL BE FURNISHED WITH VIBRATION ISOLATORS. THE CONTRACTOR SHALL MOUNT
VIBRATION ISOLATORS TO CONCRETE PADS W/ WEDGE ANCHORS IN ACCORDANCE WITH MANUFACTURER
RECOMMENDATIONS.
7. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED
THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.
FUEL TANK SIZING CALCULATION:
METERED LOAD ON EXISTING GENERATOR SET IS 74 KW.
NEW GENERATOR SET RATED AT 150 KW WILL BE LOADED AT 49%.
GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 11.73 GPH.
72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 845 GALLONS.
GENERATOR SET FUEL CONSUMPTION AT 50% IS 6.94 GPH.
72 HOUR FUEL CONSUMPTION AT 50% IS 500 GALLONS.
THE LARGEST FUEL TANK AVAILABLE FOR THE 150 KW GENERATOR SET W/ WEATHER
PROTECTIVE ENCLOSURE IS 309 GALLONS.
309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE 45 HOURS OF BACKUP POWER.
BASIS OF DESIGN:
CUMMINS 150 KW DSGAC W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.
PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.
WORK NOTES:
1 RECONNECT EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER
FEEDER NOTE," THIS SHEET.
EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.
REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.
MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.
RECONNECT EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING ATS ENCLOSURE.
SEE "SCADA WIRING NOTE," THIS SHEET.
EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.
RECONNECT EXISTING GROUND CONDUCTOR TO GROUND BUS GENERATOR BREAKER COMPARTMENT.
EMERGENCY POWER FEEDER NOTE:
RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT
THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, SPLICE NEW
CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK
INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.
120 VOLT CIRCUIT NOTE:
RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. 120 VOLT CIRCUIT IS RUN IN
THE SAME CONDUIT WITH THE EMERGENCY POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT
LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT CONNECTION BELOW THE
CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION
SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE
DUPLEX RECEPTACLE.
SCADA WIRING NOTE:
RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.
CONTROL WIRING NOTE:
RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING
CONTROL WIRING IS INSTALLED IN THE SAME CONDUIT W/ THE EMERGENCY POWER FEEDER. IN THE EVENT
THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING
FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE
COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW
CONDUCTORS TO THE CONTROLLER.
NO SCALE
SINGLE LINE DIAGRAM - DEMOLITION
G
REMOVE EXISTING 150 KW
EMERGENCY GENERATOR SET.
EXISTING
PANEL
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH
EUS
EUS
1 2
PLAN VIEW - NEW SUB-BASE FUEL TANK
N.T.S.
FUEL TANK
CONDUIT ENTRY OPENING
LOCATE NEW GENERATOR SET SO THAT EXISTING
CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING
BELOW THE GENERATOR CIRCUIT BREAKER.
CONDUIT ENTRY OPENING
NEW GENERATOR ELEVATION
N.T.S.
EXISTING MAIN
DISCONNECT SWITCH
EUS EUSEUS
EXISTING UNDERGROUND
SECONDARY TO REMAIN (TYP.)
NO SCALE
SINGLE LINE DIAGRAM - NEW WORK
G
EXISTING
PANEL
EXISTING 400 A., 4 P.
AUTOMATIC TRANSFER SWITCH.
EUS
EUS
EXISTING MAIN
DISCONNECT SWITCH
EUS EUSEUS
EXISTING UNDERGROUND
SECONDARY TO REMAIN (TYP.)
EXISTING BYPASS SWITCH
NEW 150 KW/187.5 KVA, 480Y/277 V., 3Ø
EMERGENCY GENERATOR SET.
EXISTING BYPASS SWITCH
OUTLINE OF GENERATOR
CIRCUIT BREAKER
27 JAN 2015
91546
E-9