Attachment_2_Drawings_FTEV_13-1049B.pdf

PDF 799 KB Posted

Attached to
Replace Generators Federal contract opportunity
Solicitation number
FA4417-16-R-0006
Issued by
Department of the Air Force Special Operations Command

About this file

Attachment 2 Drawings FTEV 13-1049B

View the file

Other files for this federal contract opportunity

Other files attached to Replace Generators, newest first.
File Type Posted
Solicitation_Extension_Amendment.pdf PDF
Questions_and_Answers_7_Apr_16.docx DOCX document
Responses_to_Contractor_Questions_from_Pre-Bid_Site_Visit_(FTEV_13-1049B).pdf PDF
Site_Visit_MFR_and_Roster.pdf PDF
Solicitation _FA4417-16-R-0006.pdf PDF
Attachment_6_Financial_Reference_Sheet.docx DOCX document
Attachment_4_Wage_Determination.pdf PDF
Attachment_1_Specifications_FTEV_13-1049B.pdf PDF
Attachment_5_Past_Present_Performance_Questionnaire.docx DOCX document
Attachment_3_GFP_Listing.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

unk

L e t o u r n e a u

C i r c l e

L e t o u r n e a u

C i r c l e

F o x x

A v e n u e

Tully Street

S i m p s o n e n u e

Tully Street

R e d

H o r s e

R o a d

Tupelo Circle

Bakke Street

M a y

S t r e e t

Bakke Street

R e d

H r s

R a d

Grimm Lane

Hume Drive

Bland Street

Galvan Street

Hume Drive

Lewis Drive

Hodges Street

Walters Drive

H u m

D r i v e

A c h i v e

H a r r i s i v e

Hume Drive

McIntosh Court

US98

O N e i l

A v e n u e

In d e p e n d e n c e

R o a d

US98

C o d y

A v e n u e

Purcell Drive

C a m p a i g r e e t

Whitbeck Street

Gelshlager Street

Clark Road

Hume Drive

Schmauss Lane

W e a v e n u e

US98

M cM illa n S tre et

C o r l w a d

W a l k p

W y

I n d e p e n d e n c a d

Bedel Street

B e n n e t t

A v e n u e

Frazier Street

C r u z

A v e n u e

Red Horse Road

C r u z

A v e n u e

T u l l r e e t

T u l l y

S t r e e t

Bedel Street

W e s t f a

C r c l e

H a m b

P a c e

R r a d

Tully Street

L u ka sik A ve n u e

C o e n u e

K e r w o o d

R o a d

US98

Lielmanis Avenue

H o w l t e y

US98

M a i n t e n a n a

T u l r e e t

US98

H a r t s r e e t

M c

C l e r e e t

T e r e n u e

I n d e p e n d e n a d

M i t c h e l l

R o a d

Bartley Street

D o w n s

R o a d

90918

92470

90043

90308

92006

92007

90600

92431

92081

90101

90761

91048

99045

91307

90325

90637

90106

90032

92469

90359

91159

92427

92550

91400

90030

92085

91265

90053

92046

90225

99061

99029

99118

90815

91301

90880

92093

91148

91303

99042

92429

91364

90366

91056

99500

90304

91254

90051

90531

99030

91045

90636

90062

92449

92519

90115

90370

90064

92403

90713

90326

92028

92019

92021

91047

90525

90806

90138

92060

90352

91029

90371

90137

92472

90748

90822

90128

90618

90035

90619

90532

90369

92065

90935

92438

90033

90702

91255

91520

90521

92091

90510

99142

90302

90345

90232

92404

90382

90215

92080

90617

92059

91137

92513

90003

92057

92042

92043

92037

92551

92017

92016

92107

91142

90300

90374

92546

92084

90048

99116

92099

99059

90621

92105

90339

91300

90008

92102

91163

90347

92098

90358

90825

99022

99145

99126

99044

90390

99056

99055

99083

99007

99105

91016

90552

99060

90131

99001

99998

90950

92090

92050

90334

91050

91350

91363

91130

90337

92538

92061 92082

90049

90760

90375

90229

90707

92052

92035

90615

92406

90105

90616

90928

99160

99999

99068

90635

91039

91009

90015

92432

92039

90121

91031

90801

90610

92275

92420

90759

92430

91151

91023

91140

92011

91037

90802

99043

91055

91252

92013

92000

90703

92528

92455

90005

90084

92024

92069

90328

90731

90372

92032

92030

90717

90145

91054

92436

91155

90346

90606

92452

92451

90378

92022

91012

90001

90223

90642

90054

90377

92040

92027

92026

91146

90230

90817

90056

92055

92010

92072

92076

92071

92068

92058

90058

91053

90333

90320

90827

92004

92100

99115

90207

92522

92087

91104

91103

90580

91105

92437

90809

91330

92553

90701

92548

90327

92435

90626

92549

92001

92008

92051

90724

91122

92434

90511

92009

92461

90085

90609

99023

99716

99717

99718

99719

99127

99051

99999

99999

99999

99025

99024

92005

90315

90210

99067

92034

91032

92023

99058

92505

90522

90509

90747

92089

91154

90330

92426

92419

92463

92501

99535

99150

92516

92541

90607

99104

99090

99048

99020

99106

99107

90340

90075

90577

92048

90711

92094

91133

90523

91112

92424

90388

99057

91510

99041

90068

90069

90629

90392

92064

90037

90141

99004

90362

92537

90613

90134

92014

92529

90052

91162

90951

92464

92025

92446

92515

91161

90381

90387

99112

92103

99053

99038

91057

90729

99094

99146

92502

92450

92033

91034

91132

91030

91152

92556

90076

91145

90911

90042

90102

92441

92471

90023

90357

90111

90070

92054

90355

90601

92527

91099

92407

92015

92400

92425

92079

91109

90914

91156

90811

90743

91007

91360

91325

90081

90833

92038

92533

99137

92095

90368

91052

91164

90742

92083

92555

92514

90823

90627

90810

92047

90361

99010

90714

90763

90109

92503

90329

91106

91135

91310

92460

92428

91266

99117

91500

92044

90213

92012

92036

92539

90039

90073

90074

91035

90505

92466

91120

91601

90926

91025

91603

91365

99158

99054

99043

92562

99999

99999

99019

90535

91351

99126

92062

91020

90036

90518

91370

92088

92063

92544

90402

90140

92521

99031

92473

91361

92518

92433

91027

91024

91515

92523

90318

92545

90373

90343

91147

92445

92530

90117

92092

90705

90517

92511

90331

92444

90079

91000

92401

91033

99098

90838

91538

91119

91114

90203

92045

90632

90720

92067

92097

92543

92506

92535

92524

92070

92056

92053

92041

92104

92106

92074

91268

92459

92508

91036

90624

92517

90625

91260

90553

90638

90066

90061

90057

91028

91021

92525

92440

99141

90816

92468

91144

90034

90755

90310

90220

92086

90551

90317

90050

90367

90323

92402

92467

90055

92018

91257

90029

92020

92002

92003

92073

90519

99065

92101

92463

90712

91013

92442

99902

92096

90135

91049

90829

92465

92408

90231

90603

91250

90322

92507

92066

90718

92049

90501

90640

90353

91041

92542

91153

92552

90002

92108

92276

92531

90758

90700

92439

90113

92564

91302

90812

90708

91126

90010

92077

90060

91136

91042

90332

91258

99910

91113

90630

90206

90421

90028

90020

92075

92078

92031

92500

91259

91262

90067

90059

92485

92509

92536

90349

90065

90612

99049

90228

90319

90221

91625

92418

99005

91141

90336

99009

90502

90412

90038

92540

90202

92557

91537

90503

90021

99077

99154

90628

92547

90506

91101

90507

90380

90379

91149

91124

29075

29075

29075

29075

90396

90396

29073

29073

90534

90581

90734

90005

91038

91043

29077

29077

W a l k p y

90512

90513

90513

90512

90360

90363

90351

92479

92478

92477

91264

91263

91261

91041

90813

90757

90749

90626

99121

90524

99103

90364

90356

90083

30041

D o w a d

90611

90500

90508

90311

90086

M

Y

T

R

E

E

T

91058

91059

99958

90917

90905

90306

91168

91107

91157

90534

90536

90800

Kissam Street

90727

30007

99326

BUILDING 90710

BUILDING 90730

BUILDING 90208

BUILDING 90063

BUILDING 90365

BUILDING 91546

LOCATION MAP

N.T.S.

LOCATION MAP & INDEX OF DRAWINGS

ELECTRICAL PLANS - BUILDING 90063

T-1

E-1

E-2

E-3

E-4

SHEET # TITLE

INDEX OF DRAWINGS

MAIN GATE

HAUL ROUTE

E-5

E-6

E-7

E-8

REPLACE GENERATOR 5 YEAR PLAN

MULTIPLE BUILDINGS

(BUILDINGS 90063, 90208, 90365, 90710, 90730 & 91546)

HURLBURT FIELD, FLORIDA

FTEV 13-1049B

DETAILS - BUILDING 90063

ELECTRICAL PLANS - BUILDING 90208

DETAILS - BUILDING 90208

ELECTRICAL PLANS - BUILDING 90365

ELECTRICAL PLANS - BUILDING 90710

ELECTRICAL PLANS - BUILDING 90730

ELECTRICAL PLANS - BUILDING 91546E-9

DETAILS - BUILDING 90710

GENERAL NOTES:

1. ENSURE THAT NO WASTEWATER ASSOCIATED WITH THE POURING OF ANY CONCRETE IS

DISCHARGED TO SURFACE WATERS OF THE STATE (E.G.: WETLANDS, STORMWATER SYSTEMS, ETC.)

2. TO ENSURE THE REQUIREMENTS OF THE CLEAN AIR ACT AND AFI 32-7040 ARE MET, ALL GENERATOR

INFORMATION, INCLUDING ANY RUN-TIMES ASSOCIATED WITH THE INSTALLATION, MUST BE ENTERED

INTO THE AIR PROGRAM INFORMATION MANAGEMENT SYSTEM (APIMS). THIS INFORMATION AND DATA

MUST BE REPORTED TO MR. BARRY L. WOODS, 1 SOCES/CEIE, (850) 884-4652.

3. CONSTRUCTION AT EACH INDIVIDUAL BUILDING SHALL BE ACCOMPLISHED INDIVIDUALLY. THE

COMPLETE REMOVAL, CONSTRUCTION, REINSTALLATION, TESTING, AND GOVERNMENT ACCEPTANCE

OF EACH BUILDING SHALL BE COMPLETED BEFORE THE CONTRACTOR WILL BE ALLOWED TO START

CONSTRUCTION AT THE NEXT BUILDING.

4. POWER OUTAGES REQUIRED FOR CONSTRUCTION ACTIVITIES TO THE ELECTRICAL SERVICES TO

FACILITIES SHALL NOT EXCEED 12 HOURS AT A TIME.

5. THE CONTRACTOR SHALL PROVIDE FACTORY CERTIFIED GENERATOR START-UP PERSONNEL TO

PERFORM FACTORY START-UP IN ORDER TO BEGIN FACTORY WARRANTY.

6. WORK IS AUTHORIZED ON WEEKEND WITH PRIOR APPROVAL.

7. ENSURE CLEARANCES AROUND GENERATOR ARE AT LEAST 48” AT CONSTRUCTION COMPLETION.

8. FOR GENERATORS 250KW AND ABOVE THE CONTRACTOR SHALL PROVIDE 4” BOX BEAMS UNDER THE

GENERATOR TO PROVIDE CLEARANCE.

9. CONTROL WIRING IS CAT 5 CABLE.

POWER PRODUCTION SHOP

27 JAN 2015

OF 10

FTEV 13-1049B

JRH/EWW

JRH

MULTIPLE

T-1

L O

C A

T I O

N

M

P

I N

D E

X

O

F

D

R A

W I N

G

ELECTRICAL PLAN - BUILDING 90063 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BUILDING 90063 - NEW WORK

SCALE: 1/8" = 1'-0"

REMOVE EXISTING 350 KW GENERATOR SET.

EXISTING PAD MOUNTED TRANSFORMER

EXISTING 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION

REMOVE EXISTING SECONDARY CONDUIT & WIRING FROM

TRANSFORMER SECONDARY LUGS TO EXISTING AUTOMATIC

TRANSFER SWITCH. SEE "SINGLE LINE DIAGRAM -

DEMOLITION," SHEET E-2. EXISTING SECONDARY ROUTED

FROM AUTOMATIC TRANSFER SWITCH, THRU PAD MOUNTED

TRANSFORMER TO BUILDING SERVICE PANEL SHALL REMAIN.

NEW 600 A., 3 P. MAIN BREAKER IN NEMA 3R

ENCLOSURE. MOUNT ON NEW SUPPORT

STRUCTURE. SEE "DETAIL - MAIN BREAKER

SUPPORT STRUCTURE," SHEET E-2.

NEW UNDERGROUND SECONDARY - EXTEND INTO SIDE

OF EXISTING TRANSFORMER SECONDARY SECTION.

SEE "SINGLE LINE DIAGRAM - NEW WORK," SHEET E-2.

NEW SECONDARY CONDUIT &

WIRING. SEE "SINGLE LINE

DIAGRAM - NEW WORK," SHEET E-2.

E

U

S

E U

S

E U

S

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 150 KW.

NEW GENERATOR SET RATED AT 250 KW WILL BE LOADED AT 60%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 19.6 GPH.

48 HOUR FUEL CONSUMPTION AT FULL LOAD IS 941 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 60% IS APPROXIMATELY 12.8 GPH.

48 HOUR FUEL CONSUMPTION AT 60% IS APPROXIMATELY 614 GALLONS.

NEW SUB-BASE FUEL TANK SHALL HAVE 600 GALLON CAPACITY.

600 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 47 HOURS OF BACKUP POWER.

DEMOLISH EXISTING CONCRETE PAD.

REMOVE EXISTING SECONDARY WIRING. REMOVE

EXISTING CONDUIT BELOW EXISTING CONCRETE

PAD. REUSE EXISTING CONDUIT ENTRANCE INTO

EXISTING AUTOMATIC TRANSFER SWITCH.

INSTALL NEW 250 KW GENERATOR SET

ON NEW CONCRETE PAD.

U

S

OUTLINE OF GENERATOR HOUSING

SPECIFICATIONS

GRID (TYPICAL)

SECURE GENERATOR SET TO

CONCRETE PAD W/ ANCHOR

BOLTS PER MANUFACTURER'S

# 2/0 BARE COPPER GROUND

# 2/0 GROUND - 30" MIN. BELOW GRADE.

#4 BARS AT 12" O.C. EACH WAY (TYP.)

EMERGENCY GENERATOR PAD DETAILS

ALL GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDEDNOTE:

2#4 CONT. (TYP.)

ASECTION

N.T.S.

E1 E1

12"

4"

8" MINIMUM

6" TYPICAL

PLAN VIEW

N.T.S.

16"

3/4" X 20'-0" COPPERCLAD

GROUND ROD (TYP. - 4.)

3500 PSI CONCRETE PAD

A

BOND # 2/0 TO GENERATOR FRAME

E1 E1

FINISHED GRADE

GENERAL NOTES:GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER

SWITCHES THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER

PRODUCTION SHOP. THE CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO

A LOCATION ON HURLBURT FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND

DISPOSE OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

BASIS OF DESIGN:

CUMMINS 250 KW DQDAA W/ 600 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 188" LONG X 82" WIDE X 111" HIGH.

REMOVE EXISTING 120 V WIRING. REMOVE EXISTING CONDUIT

TO A POINT BELOW GRADE. REUSE EXISTING CONDUIT &

EXTEND INTO NEW GENERATOR SET. SEE NEW WORK PLAN.

INTERCEPT EXISTING CONDUIT & EXTEND INTO NEW

GENERATOR SET. PULL IN NEW 120 VOLT WIRING FROM

EXISTING DISCONNECT SWITCH MOUNTED ON DRY TYPE

TRANSFORMER TO DUPLEX RECEPTACLE IN GENERATOR

HOUSING.

REMOVE EXISTING CONTROL WIRING. REMOVE EXISTING CONDUIT TO A

POINT BELOW GRADE. REUSE EXISTING CONDUIT & EXTEND INTO NEW

GENERATOR SET. SEE NEW WORK PLAN.

INTERCEPT EXISTING CONDUIT & EXTEND INTO NEW

GENERATOR SET. PULL IN NEW CONTROL WIRING FROM

EXISTING AUTOMATIC TRANSFER SWITCH TO NEW

GENERATOR SET.

EXISTING ELECTRICAL SERVICE GROUNDING NOTE:

REMOVE EXISTING SERVICE GROUND CONNECTIONS IN EXISTING MAIN PANEL. REMOVE EXISTING

GROUND CONDUCTOR BONDING NEUTRAL BUS TO GROUND BUS IN EXISTING MAIN PANEL.

EXISTING SCADA CONDUIT &

WIRING TO REMAIN.

27 JAN 2015

90063

E-1

E L E

C T

R I C

A L

P

L A

B

U I L D

I N

G

MAIN BKR.

600 A., 3 P.

EUS

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

EXISTING PAD MOUNTED

TRANSFORMER

US

G

EUS

EUS

EXISTING 600 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

REMOVE EXISTING 350 KW

EMERGENCY GENERATOR SET.

REMOVE EXISTING

CONDUIT & WIRING.

EUS

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

EXISTING PAD MOUNTED

TRANSFORMER

G

EUS

EXISTING 600 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

NEW 250 KW/312.5 KVA, 480Y/277 V., 3Ø

EMERGENCY GENERATOR SET.

1 5/8" X 1 5/8" 12 GAUGE HOT-

DETAIL - MAIN BREAKER SUPPORT STRUCTURE

PVC, SCH. 40 CONDUIT

FINISH GRADE

CONCRETE FOOTING

N.T.S.

18" SQUARE

12"

1" CHAMFER

ENCLOSED CIRCUIT BREAKER

DIPPED GALV. STEEL CHANNEL

2"

48"±

BREAKER

REQD. FOR

WIDTH AS

ENCLOSURE

WEATHERPROOF

"LB" FITTINGS

REMOVE EXISTING CONTROL WIRING

& A PORTION OF CONDUIT.

REMOVE EXISTING SECONDARY

WIRING & A PORTION OF CONDUIT.

US

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

NEW GENERATOR ELEVATION

N.T.S.

WORK NOTES:

1 PROVIDE NEW SECONDARY CONDUIT & WIRING CONNECTION TO GENERATOR CIRCUIT

BREAKER ENCLOSURE. SEE "SINGLE LINE DIAGRAM - NEW WORK," THIS SHEET.

PROVIDE NEW 120 VOLT CONDUIT & WIRING CONNECTION TO DUPLEX RECEPTACLE IN

GENERATOR HOUSING.

PROVIDE NEW CONDUIT & CONTROL WIRING CONNECTION TO NEW GENERATOR SET

FROM EXISTING AUTOMATIC TRANSFER SWITCH.

4 REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING

GENERATOR SET. MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE.

2 PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 2/0 GND. -

3 1/2" RIGID GALV. STEEL CONDUIT

2 PARALLEL CIRCUITS OF 4 - 350 MCM - 3 1/2" PVC,

SCH. 40 CONDUIT. CONVERT PVC, SCH. 40 CONDUIT

TO PVC, SCH. 80 BEFORE IT RISES ABOVE GRADE TO

NEW MAIN BREAKER.

# 2/0 CU. - 3/4" PVC, SCH. 80 TO 3/4"

X 20'-0" COPPERCLAD GROUND ROD

# 2/0 CU. - 3/4" PVC, SCH. 80 TO

METALLIC COLD WATER PIPE

2 PARALLEL CIRCUITS OF 4 - 350 MCM & 1 # 2/0 GND. -

3 1/2" PVC, SCH. 40 CONDUIT

EXISTING UNDERGROUND

SECONDARY TO REMAIN.

INSTALL GENERATOR CONTROL

WIRING IN 1" PVC, SCH. 40 CONDUIT

27 JAN 2015

90063

E-2

D E

T A

I

U I L D

I N

G

EXISTING PANEL "MDP"

ELECTRICAL PLAN - BUILDING 90208 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BUILDING 90208 - NEW WORK

SCALE: 1/8" = 1'-0"

EXISTING PANEL "MP"

EXISTING PANEL "MA"

E3 E3

A

ELEVATION

SCALE: 1/4" = 1'-0"

E3 E3

A

NORMAL

LOAD

EMERGENCY

EXISTING POLARIS INSULATED

CONNECTOR BLOCKS

EXISTING ATS WIRING DIAGRAM

N.T.S.

EXISTING C.T.'S

EXISTING PULL BOX

REMOVE EXISTING 150 KW GENERATOR SET.

EXISTING PAD MOUNTED TRANSFORMER

EXISTING PANEL "MDP"

EXISTING PANEL "MP"

EXISTING PANEL "MA"

EXISTING PULL BOX

EXISTING PAD MOUNTED TRANSFORMER

REINSTALL EXISTING 300 A., 3 P.

ENCLOSED CIRCUIT BREAKER

NEW 600 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION.

TEMPORARILY REMOVE EXISTING 300 A., 3 P.

ENCLOSED CIRCUIT BREAKER.

REMOVE EXISTING 600 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

INSTALL NEW 100 KW GENERATOR SET.

REMOVE EXISTING 600 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

TEMPORARILY REMOVE EXISTING 300 A.,

3 P. ENCLOSED CIRCUIT BREAKER.

EXISTING PULL BOX

EXISTING PANEL "MP"

TEMPORARILY DISCONNECT ALL

EXISTING CONDUIT & WIRING

CONNECTIONS FROM EXISTING

AUTOMATIC TRANSFER SWITCH &

RECONNECT TO NEW SWITCH.

E

U

S

E

U

S

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 45 KW.

NEW GENERATOR SET RATED AT 100 KW WILL BE LOADED AT 45%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 8.87 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 638 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 50% IS 5.0 GPH.

72 HOUR FUEL CONSUMPTION AT 50% IS 360 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 100 KW GENERATOR SET W/ WEATHER PROTECTIVE ENCLOSURE

IS 309 GALLONS.

309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 61.8 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 100 KW DSGAA W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

RECONNECT EXISTING GROUND

CONDUCTOR TO GENERATOR FRAME.

EXISTING CONCRETE BLOCK SCREEN WALL

27 JAN 2015

90208

E-3

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

EXISTING PAD MOUNTED

TRANSFORMER

G

EUSEUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

NEW 100 KW/125 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

REMOVE EXISTING 600 A., 3 P.

AUTOMATIC TRANSFER SWITCH.

EXISTING

MAIN

PANEL

EXISTING

PANEL

"MP"

"MDP"

EXISTING

PANEL

"MA"

EXISTING PULL BOX

EXISTING 300 A., 3 P.,

ENCLOSED CIRCUIT BREAKER

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

EXISTING PAD MOUNTED

TRANSFORMER

G

EUSEUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

REMOVE EXISTING 150 KW

EMERGENCY GENERATOR SET.

NEW 600 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

EXISTING

MAIN

PANEL

EXISTING

PANEL

"MP"

"MDP"

EXISTING

PANEL

"MA"

EXISTING PULL BOX

EXISTING 300 A., 3 P.,

ENCLOSED CIRCUIT BREAKER

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

WORK NOTES:

1 EXISTING PARALLEL EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER

FEEDER NOTE," THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE

"SCADA WIRING NOTE," THIS SHEET.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED

WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

CONDUIT ENTRY OPENING

NEW GENERATOR ELEVATION

N.T.S.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE

EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

REMOVE EXISTING FLEXIBLE CONDUIT FROM EXISTING RECEPTACLE TO A POINT JUST ABOVE EXISTING

CONCRETE PAD. INSTALL WEATHERPROOF JUNCTION BOX ABOVE CONCRETE PAD AND BELOW NEW FUEL TANK

AS REQUIRED TO LINE UP WITH FUEL TANK CONDUIT ENTRY OPENING. EXTEND 2 # 12 & 1 # 12 GND. - 1/2" LIQUID

TIGHT FLEXIBLE METAL CONDUIT FROM JUNCTION BOX TO RELOCATED RECEPTACLE.

SCADA WIRING NOTE:

RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE

COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE CONTROLLER.

27 JAN 2015

90208

E-4

D E

T A

I

U I L D

I N

G

ELECTRICAL PLAN - BUILDING 90365 - DEMOLITION

SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BUILDING 90365 - NEW WORK

BUILDING

90365

BUILDING

90365

EXISTING 225 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION

REMOVE EXISTING 35 KW GENERATOR SET. INSTALL NEW 20 KW, 208Y/120 V. GENERATOR SET.

EXISTING 225 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION

E

U

S

E

U

S

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 10 KW.

NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 50%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 50% IS 0.97 GPH.

72 HOUR FUEL CONSUMPTION AT 50% IS 70 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 91 GALLONS.

91 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 88 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, REMOVE THE

EXISTING FLEXIBLE CONDUITS BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. EXISTING 120 VOLT CIRCUIT IS

RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY POWER FEEDER. IN

THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE

EXISTING ENT CONDUIT CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE

EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER

SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING

CONTROL CIRCUIT IS RUN IN ELECTRICAL NON-METALLIC TUBING INSTALLED IN SAME CONDUIT W/ EMERGENCY

POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW

CONTROLLER, REMOVE THE EXISTING ENT CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING

CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CONTROLLER.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING CONDUITS

FALL WITHIN THE CONDUIT ENTRY OPENING BELOW THE

GENERATOR CIRCUIT BREAKER.

NEW GENERATOR ELEVATION

N.T.S.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE

"SCADA WIRING NOTE," THIS SHEET.

5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

REMOVE EXISTING 35 KW

EMERGENCY GENERATOR SET.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING 225 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

NEW 20 KW/25 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

EUS

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

EXISTING 225 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EXISTING UNDERGROUND SECONDARY

TO REMAIN.

EUS

EXISTING MAIN

DISCONNECT SWITCH

EXISTING CONTROL WIRING & CONDUIT TO REMAIN.

EUS

27 JAN 2015

90365

E-5

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

ELECTRICAL PLAN - BUILDING 90710 - DEMOLITION

ELECTRICAL PLAN - BUILDING 90710 - NEW WORK

SCALE: 1/8" = 1'-0"

REMOVE EXISTING 35 KW GENERATOR SET.

ATS

ATS

E6 E6

A

ELEVATION

SCALE: 1/4" = 1'-0"

E6 E6

A

REMOVE EXISTING 225 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

INSTALL NEW 20 KW GENERATOR SET.

ELEVATION

SCALE: 1/4" = 1'-0"

E6 E6

B

E6 E6

B

REMOVE EXISTING 225 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

INSTALL NEW 225 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION.

EXISTING MAIN BREAKER

EXISTING PANEL "E"

EXISTING MAIN BREAKER

EXISTING PANEL "E"

EXISTING SCADA

EQUIPMENT CABINET

REMOVE EXISTING

CONDUIT & WIRING

EXISTING CONDUIT TO

REMAIN & BE REUSED.

EXISTING SCADA

EQUIPMENT CABINET

PULL NEW WIRING INTO

EXISTING CONDUITS.

INSTALL NEW 150 A., 4 POLE

AUTOMATIC TRANSFER SWITCH

W/ BYPASS/ISOLATION.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

PULL NEW SCADA WIRING FROM SCADA

EQUIPMENT CABINET TO NEW GENERATOR

SET THRU EXISTING CONDUIT PENETRATING

EXISTING EXTERIOR WALL.

EXISTING SCADA CIRCUIT CONDUIT

PENETRATION THRU EXTERIOR WALL

EXISTING POWER FEEDER CONDUIT

PENETRATION THRU EXTERIOR WALL

RECONNECT EXISTING GROUND CONDUCTOR

TO NEW GENERATOR BREAKER.

EXISTING CONCRETE BLOCK SCREEN WALL

27 JAN 2015

90710

E-6

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

MAIN BKR.

EXISTING

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

REMOVE EXISTING

CONDUIT & WIRING.

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

NEW 225 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

NEW 20 KW/25 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

EXISTING

PANEL

"E"

EXISTING DISCONNECT SWITCH

EXISTING GUTTER

MAIN BKR.

EXISTING

G

REMOVE EXISTING 35 KW

EMERGENCY GENERATOR SET.

EXISTING

PANEL

"E"

EXISTING DISCONNECT SWITCH

EXISTING GUTTER

REMOVE EXISTING 225 A., 3 P.

AUTOMATIC TRANSFER SWITCH.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 12 KW.

NEW GENERATOR SET RATED AT 20 KW WILL BE LOADED AT 60%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 1.81 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 130 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 60% IS APPROXIMATELY 1.21 GPH.

72 HOUR FUEL CONSUMPTION AT 60% IS 87 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 20 KW GENERATOR SET W/ WEATHER PROTECTIVE

ENCLOSURE IS 91 GALLONS.

91 GALLONS AT 60% FUEL CONSUMPTION WILL PROVIDE APPROXIMATELY 75 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 20 KW C20 D6 W/ 91 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 65.7" LONG X 34" WIDE X 74" HIGH.

EMERGENCY POWER FEEDER NOTE:

INSTALL NEW EMERGENCY POWER FEEDER WIRING FROM NEW AUTOMATIC TRANSFER SWITCH TO GENERATOR

SET. REUSE EXISTING CONDUIT.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT

CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH

BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.

CONTROL WIRING NOTE:

INSTALL NEW CONTROL WIRING FROM NEW AUTOMATIC TRANSFER SWITCH TO GENERATOR SET. REUSE

EXISTING CONDUIT.

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY

OPENING BELOW THE GENERATOR CIRCUIT BREAKER.

NEW GENERATOR ELEVATION

N.T.S.

WORK NOTES:

1 EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER FEEDER NOTE,"

THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING SCADA ENCLOSURE. SEE

"SCADA WIRING NOTE," THIS SHEET.

5 EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

6 REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED

WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH.

INTERCEPT EXISTING CONDUIT & EXTEND NEW 2 1/2"

CONDUIT TO NEW ATS. PULL IN NEW 4 # 3/0 & 1 # 6

GND. FROM EXISTING MAIN BREAKER TO NEW ATS.

INTERCEPT EXISTING CONDUIT & EXTEND NEW 2 1/2"

CONDUIT TO NEW ATS. PULL IN NEW 4 # 3/0 & 1 # 6

GND. FROM EXISTING GUTTER TO NEW ATS.

TERMINATE EXISTING CONDUIT INTO BACK OF ATS.

PULL IN NEW 4 # 3/0 & 1 # 6 GND. FROM EMERGENCY

GENERATOR SET TO NEW ATS. PULL IN NEW

CONTROL WIRING.

27 JAN 2015

90710

E-7

D E

T A

I

U I L D

I N

G

ELECTRICAL PLAN - BUILDING 90730 - DEMOLITION

ELECTRICAL PLAN - BUILDING 90730 - NEW WORK

SCALE: 1/8" = 1'-0"

E

U

S

E

U

S

REMOVE EXISTING 150 KW

EMERGENCY GENERATOR SET.

REMOVE EXISTING 800 A., 3 POLE

AUTOMATIC TRANSFER SWITCH.

INSTALL NEW 150 KW GENERATOR SET.

INSTALL NEW 800 A., 4 POLE AUTOMATIC

TRANSFER SWITCH W/ BYPASS/ISOLATION.

E U

S

EXISTING 800 A., 3 P. ENCLOSED

MAIN CIRCUIT BREAKER

E U

S

EXISTING PANEL "MDP"

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE CONTRACTOR SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS AND DISPOSE

OF PROPERLY.

5. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 70 KW.

NEW GENERATOR SET RATED AT 150 KW WILL BE LOADED AT 47%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 11.73 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 845 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 50% IS 6.94 GPH.

72 HOUR FUEL CONSUMPTION AT 50% IS 500 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 150 KW GENERATOR SET W/ WEATHER

PROTECTIVE ENCLOSURE IS 309 GALLONS.

309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE 45 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 150 KW DSGAC W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.

WORK NOTES:

1 REWORK EXISTING PARALLEL EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY

POWER FEEDER NOTE," THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

REWORK EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING ATS ENCLOSURE.

SEE "SCADA WIRING NOTE," THIS SHEET.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

REINSTALL EXISTING CURRENT TRANSFORMERS, SCADA WIRING, AND ALL ACCESSORIES ASSOCIATED

WITH THE SCADA SYSTEM IN THE NEW AUTOMATIC TRANSFER SWITCH. RECONNECT EXISTING

CONDUITS ENTERING INTO SIDE OF EXISTING ATS. RECONNECT EXISTING POWER FEEDERS, CONTROL

WIRING, ETC., AS REQUIRED TO MAKE THE NEW ATS FUNCTIONAL.

FUEL TANK

CONDUIT ENTRY OPENING

OUTLINE OF GENERATOR

CIRCUIT BREAKER

CONDUIT ENTRY OPENING

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

NEW GENERATOR ELEVATION

N.T.S.

EXISTING CONCRETE BLOCK SCREEN WALL

EMERGENCY POWER FEEDER NOTE:

REMOVE THE EXISTING PARALLEL FLEXIBLE CONDUIT CONNECTIONS TO THE EXISTING GENERATOR SET.

INSTALL NEW LIQUID-TIGHT FLEXIBLE CONDUITS W/ LENGTHS AS REQUIRED TO REACH THE NEW CONDUIT

ENTRY POINT. PULL EXISTING WIRING BACK INTO NEW CONDUITS & RECONNECT EXISTING EMERGENCY POWER

FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT THAT THE EXISTING FEEDER IS NOT LONG

ENOUGH TO REACH THE NEW CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS

WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE

NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. IN THE EVENT THAT THE

EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT

CONNECTION BELOW THE CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH

BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

REMOVE THE EXISTING FLEXIBLE CONDUIT CONNECTION TO THE EXISTING GENERATOR SET. INSTALL NEW

LIQUID-TIGHT FLEXBILE CONDUIT W/ LENGTH AS REQUIRED TO REACH THE NEW CONDUIT ENTRY POINT. PULL

EXISTING SCADA WIRING BACK INTO NEW CONDUIT & RECONNECT EXISTING SCADA WIRING TO NEW

GENERATOR CONTROLLER.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING

CONTROL WIRING IS INSTALLED IN THE SAME CONDUIT W/ THE EMERGENCY POWER FEEDER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE

COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE CONTROLLER.

RECONNECT EXISTING GROUND

CONDUCTOR TO NEW GENERATOR FRAME.

MAIN BKR.

EXISTING

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

NEW 800 A., 4 P. AUTOMATIC TRANSFER

SWITCH W/ BYPASS/ISOLATION.

NEW 150 KW/187.5 KVA, 208Y/120 V., 3Ø

EMERGENCY GENERATOR SET.

MAIN BKR.

EXISTING

G

REMOVE EXISTING 150 KW

EMERGENCY GENERATOR SET.

EXISTING

PANEL

"MDP"

REMOVE EXISTING 800 A., 3 P.

AUTOMATIC TRANSFER SWITCH.

EUS

EUS

EUS

EXISTING

PANEL

"MDP"

EUS

EUS

EXISTING UNDERGROUND

SECONDARY TO REMAIN.

EUS

EXISTING UNDERGROUND

SECONDARY TO REMAIN.

27 JAN 2015

90730

E-8

E L E

C T

R I C

A L

P

L A

U I L D

I N

G

ELECTRICAL PLAN - BUILDING 91546 - DEMOLITION

SCALE: 1/8" = 1'-0" SCALE: 1/8" = 1'-0"

ELECTRICAL PLAN - BUILDING 91546 - NEW WORK

ATS

REMOVE EXISTING 150 KW GENERATOR SET.

EXISTING 400 A., 4 POLE

AUTOMATIC TRANSFER SWITCH

EXISTING MAIN DISCONNECT

SWITCH

EXISTING MAINTENANCE -

BYPASS SAFETY SWITCH

EXISTING PAD MOUNTED

TRANSFORMER

E

U

S

ATS

EXISTING 400 A., 4 POLE

AUTOMATIC TRANSFER SWITCH

EXISTING MAIN DISCONNECT

SWITCH

EXISTING BYPASS SWITCH

EXISTING PAD MOUNTED

TRANSFORMER

E

U

S

INSTALL NEW 150 KW GENERATOR SET.

GENERAL NOTES:

1. NEW EMERGENCY GENERATOR SETS AND NEW AUTOMATIC TRANSFER SWITCHES SHALL BE GOVERNMENT

FURNISHED AND CONTRACTOR INSTALLED. ALL OTHER EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY

THE CONTRACTOR.

2. ALL EXISTING EMERGENCY GENERATOR SETS AND AUTOMATIC TRANSFER SWITCHES WHICH ARE SHOWN TO

BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR. ALL GENERATOR SETS AND TRANSFER SWITCHES

THAT ARE BEING REMOVED SHALL BE TURNED OVER TO THE HURLBURT FIELD POWER PRODUCTION SHOP. THE

CONTRACTOR SHALL DELIVER ALL GENERATOR SETS AND TRANSFER SWITCHES TO A LOCATION ON HURLBURT

FIELD AS DESIGNATED BY THE POWER PRODUCTION SHOP.

3. THE CONTRACTOR SHALL TRANSPORT ALL GOVERNMENT FURNISHED GENERATOR SETS AND TRANSFER

SWITCHES FROM THE POWER PRODUCTION SHOP TO EACH BUILDING FOR INSTALLATION.

4. THE GOVERNMENT SHALL REMOVE THE DIESEL FUEL FROM THE EXISTING SUB-BASE FUEL TANKS.

5. THE GOVERNMENT SHALL FILL THE NEW SUB-BASE FUEL TANKS WITH DIESEL FUEL.

6. NEW GENERATOR SETS SHALL BE FURNISHED WITH VIBRATION ISOLATORS. THE CONTRACTOR SHALL MOUNT

VIBRATION ISOLATORS TO CONCRETE PADS W/ WEDGE ANCHORS IN ACCORDANCE WITH MANUFACTURER

RECOMMENDATIONS.

7. THE GOVERNMENT WILL FILL THE DIESEL FUEL TANKS WITH FUEL AFTER THE CONTRACTOR HAS INSTALLED

THE NEW GENERATOR SETS, AND PRIOR TO TESTING OF THE GENERATOR SETS.

FUEL TANK SIZING CALCULATION:

METERED LOAD ON EXISTING GENERATOR SET IS 74 KW.

NEW GENERATOR SET RATED AT 150 KW WILL BE LOADED AT 49%.

GENERATOR SET FUEL CONSUMPTION AT FULL LOAD IS 11.73 GPH.

72 HOUR FUEL CONSUMPTION AT FULL LOAD IS 845 GALLONS.

GENERATOR SET FUEL CONSUMPTION AT 50% IS 6.94 GPH.

72 HOUR FUEL CONSUMPTION AT 50% IS 500 GALLONS.

THE LARGEST FUEL TANK AVAILABLE FOR THE 150 KW GENERATOR SET W/ WEATHER

PROTECTIVE ENCLOSURE IS 309 GALLONS.

309 GALLONS AT 50% FUEL CONSUMPTION WILL PROVIDE 45 HOURS OF BACKUP POWER.

BASIS OF DESIGN:

CUMMINS 150 KW DSGAC W/ 309 GALLON SUB-BASE DIESEL FUEL TANK & WEATHER PROTECTIVE ENCLOSURE.

PHYSICAL DIMENSIONS: 105" LONG X 44" WIDE X 88" HIGH.

WORK NOTES:

1 RECONNECT EXISTING EMERGENCY POWER FEEDER TO TRANSFER SWITCH. SEE "EMERGENCY POWER

FEEDER NOTE," THIS SHEET.

EXISTING 120 VOLT CIRCUIT. SEE "120 VOLT CIRCUIT NOTE," THIS SHEET.

REINSTALL EXISTING DUPLEX RECEPTACLE & DEVICE BOX REMOVED FROM EXISTING GENERATOR SET.

MOUNT ON SIDE OF GENERATOR BREAKER ENCLOSURE & RECONNECT TO EXISTING 120 VOLT CIRCUIT.

RECONNECT EXISTING SCADA WIRING & CONDUIT FROM GENERATOR SET TO EXISTING ATS ENCLOSURE.

SEE "SCADA WIRING NOTE," THIS SHEET.

EXISTING CONTROL WIRING & CONDUIT. SEE "CONTROL WIRING NOTE," THIS SHEET.

RECONNECT EXISTING GROUND CONDUCTOR TO GROUND BUS GENERATOR BREAKER COMPARTMENT.

EMERGENCY POWER FEEDER NOTE:

RECONNECT EXISTING EMERGENCY POWER FEEDER TO NEW GENERATOR CIRCUIT BREAKER. IN THE EVENT

THAT THE EXISTING FEEDER IS NOT LONG ENOUGH TO REACH THE NEW CIRCUIT BREAKER, SPLICE NEW

CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION SPLICES, INSTALL HEAT SHRINK

INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE CIRCUIT BREAKER.

120 VOLT CIRCUIT NOTE:

RECONNECT EXISTING 120 VOLT POWER CIRCUIT TO THE DUPLEX RECEPTACLE. 120 VOLT CIRCUIT IS RUN IN

THE SAME CONDUIT WITH THE EMERGENCY POWER FEEDER. IN THE EVENT THAT THE EXISTING CIRCUIT IS NOT

LONG ENOUGH TO REACH THE RECEPTACLE, REMOVE THE EXISTING CONDUIT CONNECTION BELOW THE

CIRCUIT BREAKER, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE COMPRESSION

SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW CONDUCTORS TO THE

DUPLEX RECEPTACLE.

SCADA WIRING NOTE:

RECONNECT EXISTING SCADA WIRING TO NEW GENERATOR CONTROLLER.

CONTROL WIRING NOTE:

RECONNECT EXISTING CONTROL WIRING CONDUCTORS TO THE NEW GENERATOR CONTROLLER. EXISTING

CONTROL WIRING IS INSTALLED IN THE SAME CONDUIT W/ THE EMERGENCY POWER FEEDER. IN THE EVENT

THAT THE EXISTING CIRCUIT IS NOT LONG ENOUGH TO REACH THE NEW CONTROLLER, REMOVE THE EXISTING

FLEXIBLE CONDUIT, SPLICE NEW CONDUCTORS TO THE EXISTING CONDUCTORS WITH BUTT TYPE

COMPRESSION SPLICES, INSTALL HEAT SHRINK INSULATION OVER SPLICES, AND EXTEND THE NEW

CONDUCTORS TO THE CONTROLLER.

NO SCALE

SINGLE LINE DIAGRAM - DEMOLITION

G

REMOVE EXISTING 150 KW

EMERGENCY GENERATOR SET.

EXISTING

PANEL

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH

EUS

EUS

1 2

PLAN VIEW - NEW SUB-BASE FUEL TANK

N.T.S.

FUEL TANK

CONDUIT ENTRY OPENING

LOCATE NEW GENERATOR SET SO THAT EXISTING

CONDUITS FALL WITHIN THE CONDUIT ENTRY OPENING

BELOW THE GENERATOR CIRCUIT BREAKER.

CONDUIT ENTRY OPENING

NEW GENERATOR ELEVATION

N.T.S.

EXISTING MAIN

DISCONNECT SWITCH

EUS EUSEUS

EXISTING UNDERGROUND

SECONDARY TO REMAIN (TYP.)

NO SCALE

SINGLE LINE DIAGRAM - NEW WORK

G

EXISTING

PANEL

EXISTING 400 A., 4 P.

AUTOMATIC TRANSFER SWITCH.

EUS

EUS

EXISTING MAIN

DISCONNECT SWITCH

EUS EUSEUS

EXISTING UNDERGROUND

SECONDARY TO REMAIN (TYP.)

EXISTING BYPASS SWITCH

NEW 150 KW/187.5 KVA, 480Y/277 V., 3Ø

EMERGENCY GENERATOR SET.

EXISTING BYPASS SWITCH

OUTLINE OF GENERATOR

CIRCUIT BREAKER

27 JAN 2015

91546

E-9

E L E

C T

R I C

A L

P

L A

U I L D

I N

G