Attachment_6-_Questions_and_Answers.doc
DOC document 37 KB Posted
- Attached to
- NRG-Recommissioning HVAC Systems Federal contract opportunity
- Solicitation number
- FA4417-13-R-0018
About this file
Question and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Ammendment_4.pdf | ||
| 230800-5_-_Missing_page_5_of_section.pdf | ||
| 13-R-0018_Questions_and_Answers_-_7_Aug_13.doc | DOC document | |
| FA4417-13-R-0018_Amend_03.pdf | ||
| B12_Site_Visit_BRIEF-_NRG.docx | DOCX document | |
| document2013-07-30-130848.pdf | ||
| 13-R-0018_0002_-_Correction_to_Amendment_0001.pdf | ||
| 13-R-0018_-_01_-_Site_Visit.pdf | ||
| FTEV12-1082_Retrocommission_HVAC_Multi_Bldgs.pdf | ||
| FTEV_12-1082_drawings.pdf | ||
| FA4417-13-R-0018_-_Retro_Recommission.doc | DOC document | |
| Attachment_5-_Financial_Reference_Sheet.docx | DOCX document | |
| Attachment_4-_Past_Performance_Questionnaire.docx | DOCX document | |
| Attachment_3_-_Wage_Determination.docx | DOCX document |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT 6
SOLICITATION NO. FA4417-13-R-0018
PROJECT: NRG-Retrocommission HVAC multiple Bldgs
PROJECT NO. FTEV 12-1082
QUESTIONS - ANSWERS
14 Aug 2013 I.
QUESTIONS:
1. Reference Specification Section 230593, Part 1.07, paragraph A: "All documents shall be signed by a registered Professional Engineer." Will a certified TBE (Test and Balance Engineer) be sufficient for this requirement?
A-Yes, a certified test and balance engineer is sufficient.
2. Reference Specification Section 230923, Part 3.06, this type of training is typical for new construction; please confirm that this training will be required for the retro-commissioning.
A-Correct, training is only required were a new control system is installed. No controls training is required under this contract.
3. In Section 23 05 93 Testing, Adjusting and Balancing for HVAC
A. 1.07 Quality Assurance
A & B Talks about being NEBB or AABC qualified. I have chosen to take my company in a different direction and focus on the technician being fully qualified not just the company. Would you consider allowing our technicians qualifications as a CATB provider in place of NEBB or AABC? We can provide all certifications documentation you may need.
A- Commissioning firm and/or specialist shall meet the qualifications list in the specifications.
4. Section 23 08 00 Retrocommissioning of HVAC
a. 1.7 Commission of HVAC
A. A & B talks about the commissioning agents qualifications being NEBB or ACG. Would you except my qualifications as a commissioning authority and provider from the College of Engineering University of Wisconsin -Madison in place of NEBB or ACG?
A- Commissioning firm and/or specialist shall meet the qualifications list in the specifications