Features for New Switchboard in BX, B160

480Y/277 V, 3-phase, 4W, 60 Hz

800 Amp main with ground fault protection

Maximum Available fault current—65kA

No metering in the switchboard is required, but it may be supplied if it results in a lower price

Suitable for use as Service Entrance

Silver plated copper bus

Copper ground bus

Surge Protection per UFC 3—520-01.

Electronic trip main breaker with instantaneous, short-time, long-time, and ground fault.

Branch breakers may be adjustable electronic trip or thermal magnetic breakers

All breakers must be fully rated for maximum available fault current. Series rated combinations are not allowed per UFC 3-520-01.

Provide spare capacity per UFC 3-520-02.

Any spaces must be prepared spaces

See attached drawing for number and sizes of existing overcurrent protective devices

Any wiring splices needed to connect to the new switchboard must be made according to Code.

The switchgear may be Square D or approved equal.

See attached drawing for fused switches that are currently installed.