This document is a Salient Characteristics specification for a Compressor/Air Dryer/Receiver Tank System installation at Building 4301, dated August 3, 2026. The government requires installation of an integrated compressed air system consisting of a rotary screw air compressor (minimum 50 HP, capable of delivering 225 CFM at 125 PSIG), an industrial refrigerated air dryer (minimum 225 SCFM), and an air receiver tank (minimum 200 gallons with 200 PSIG MAWP). All equipment must operate on 460V AC, 3-Phase, 60 Hz power and fit within an 11' x 12' rectangular footprint in Room 109, Bay West Wall. The system shall include approximately 40 feet of 1.5-inch pipe for inter-component connections and facility airline integration, plus 25 feet of 0.5-inch pipe for contaminant drainage, with the compressor requiring a full sound enclosure if rated 70 dBA or above.
The installation scope includes removal of existing equipment, provision of a 5-year major component warranty with machine manuals, power-on and function training, and integrated pre- and post-filtration with auto-drains on the dryer. The air receiver tank must include an automatic or zero-loss condensate drain and an ASME-rated pressure relief valve with pressure gauge. The government will handle equipment offloading upon delivery and disposal of existing components not designated for reuse. A facility hard-line plumbing connection point for the 1.5-inch line exists at approximately 13 feet high on the west wall.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
Bldg. 4301 Compressor/Air Dryer/Receiver Tank System
Dated: 3 August 3, 2026
• Compressor, Air Dryer, Air Receiver Tank, and all system associated filters/ contaminant separators install to include:
o Approximately 40ft of 1.5-inch pipe plumbed for inter system set up and connection to the facility’s existing airline.
o 1.5” pipe will be used to connect all three components to each other and also to connect to existing 1.5” fittings that begin the building infrastructure air lines.
o Approximately 25 ft of 0.5-inch pipe plumbed for inter system contaminants drainage o 0.5” pipe will be individually connected to equipment and be plumbed to contaminants drainage o 5-year Major Component Warranty to include machine manuals o Power On/ function training required o Removal of existing compressor, air dryer, associated piping and related components not designated for reuse, government will handle disposal o Government will offload equipment upon delivery o Entire compressed air system footprint is required to fit in rectangle area that measures 11’ x 12’.
• Air Compressor o Rotary Screw Compressor type o Minimum 50 HP o Capable of Delivering 225CFM at 125PSIG o 460V AC / 3-Phase / 60 Hz input voltage o Full Sound Enclosure for compressors rated 70dBA and above
• Air Dryer o Industrial Refrigerated Dryer type.
o Minimum 225 SCFM o 460V AC / 3-Phase / 60 Hz input voltage o Integrated pre-filter (particle) and post-filter (oil removal) with auto-drains filtration
• Air Receiver Tank o Minimum 200 Gal o Minimum 200 PSIG MAWP o Automatic or zero-loss condensate drain o ASME-rated pressure relief valve o Pressure gauge.
Existing Compressor
3’ x 5’
Existing Air Dryer
32” x 32”
Existing Air Receiver Tank- 28” Diam
Existing Throwdown Breakers
11’
12’
Hard line plumbing connection for 1.5” line.
Approx 13’ high to connection.
Rm 109 Bay West Wall