Attachment 1 Updated Salient Characteristics.pdf

PDF 162 KB Posted

Attached to
NAF Above Ground Fuel Tank
Solicitation number
FA301025QSC01_Conger
Issued by

About this file

This is a Salient Characteristics document for an aboveground fuel tank to be delivered to Keesler AFB, MS Outdoor Recreation, dated December 5, 2024. The document specifies technical requirements for a 2,000-gallon capacity double-walled steel fuel tank constructed with 3/16" thick primary and secondary cylindrical tanks.

The tank must be horizontally skid mounted for portability and include specific safety and monitoring features such as emergency vents, stack vents, overspill containers, and various gauges. Key components include a Fe Petro 2 HP Pump Assembly for non-ethanol gasoline use, multiple valves and caps, monitoring equipment including a Krueger Level Gauge and Interstitial Leak Gauge, and must be UL 142 Labeled & Listed. The tank requires a 2" flanged connector, and the manufacturer should install as many accessories as possible at the factory before delivery to Keesler AFB, MS Outdoor Recreation.

View the file

Other files

File Type Posted
Questions and Answers.pdf PDF
Attachment 2 NAF Clauses.pdf PDF
Combo.pdf PDF
Attachment 1 Salient Characteristics.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

Aboveground Fuel Tank

Keesler AFB, MS Outdoor Recreation

Dated: 5 December 2024

1. Requirements/Specifications:

• 2,000 gallon capacity

• Double walled steel construction with a thickness of at least 3/16” primary tank and 3/16” secondary cylindrical tank

• Horizontally Skid mounted for portability

• At least 2 6'' 8 Oz Emergency Vent Male w/O-ring

• At least one 2'' Stack Vent (12' above grade) w/ 2'' Mushroom Cap

• At least 7.5 Gal 4 in Aluminum Overspill Container 179 Series hinged Style Fill Cap

• 1 Valve Pressure Fill Overfill Prevention 2" Aluminum Body w/ 3" Male Quick

Disconnect x 4" Female threads

• 1 Cap Dust 3" for use with Adaptors-Aluminum

• 1 Overfill Valve Test Mechanism

• 1 Diffuser Threaded 2"

• 1 Monitoring Well w/ 2'' Cap

• 1 Krueger Level Gauge

• 1 Interstitial Leak Gauge

• 1 Tank Decal Kit

• 1 UL 142 Labeled & Listed

• At minimum a Fe Petro 2 HP Pump Assembly For Non-Ethanol Gasoline Use (2,000 -

4,000 Gallon)

• A 2" flanged connector

• As many accessories installed as possible at the factory

2. Delivery Location The Aboveground Storage Tank will be delivered to Keesler AFB, MS Outdoor Recreation.

File details come from the government source that posted it. Updated .