Attachment 1 Salient Characteristics.pdf

PDF 117 KB Posted

Attached to
NAF Above Ground Fuel Tank
Solicitation number
FA301025QSC01_Conger
Issued by

About this file

This document is a Salient Characteristics specification sheet for an Aboveground Storage Tank to be delivered to Keesler AFB, MS Outdoor Recreation by November 15, 2024.

The requirements specify a 2,000-gallon capacity double-walled steel tank with 3/16" thickness for both primary and secondary walls, mounted on skids for portability. The tank must include specific safety and operational components including two 6" emergency vents, a 2" stack vent with mushroom cap extending 12' above grade, a 7.5-gallon aluminum overspill container, various valves and gauges (including a Krueger Level Gauge and Interstitial Leak Gauge), and a Fe Petro 2 HP Pump Assembly suitable for gasoline use in 2,000-4,000 gallon tanks. The tank must be UL 2085 labeled and listed, and include all necessary fittings, caps, monitoring equipment, and a tank decal kit.

View the file

Other files

File Type Posted
Attachment 1 Updated Salient Characteristics.pdf PDF
Questions and Answers.pdf PDF
Attachment 2 NAF Clauses.pdf PDF
Combo.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

Aboveground Storage Tank

Keesler AFB, MS Outdoor Recreation

15 November 2024

1. Requirements/Specifications:

• 2,000 gallon capacity

• Double walled steel construction with a thickness of at least 3/16” primary tank and 3/16” secondar

• Skid mounted for portability

• At least 2 6'' 8 Oz Emergency Vent Male w/O-ring

• At least one 2'' Stack Vent (12' above grade) w/ 2'' Mushroom Cap

• At least 7.5 Gal 4 in Aluminum Overspill Container 179 Series hinged Style Fill Cap

• 1 Valve Pressure Fill Overfill Prevention 2" Aluminum Body w/ 3" Male Quick

Disconnect x 4" Female threads

• 1 Cap Dust 3" for use with Adaptors-Aluminum

• 1 Overfill Valve Test Mechanism

• 1 Diffuser Threaded 2"

• 1 Monitoring Well w/ 2'' Cap

• 1 Krueger Level Gauge

• 1 Interstitial Leak Gauge

• 1 Tank Decal Kit

• 1 UL 2085 Labeled & Listed

• At minimum a Fe Petro 2 HP Pump Assembly For Gasoline Use (2,000 - 4,000 Gallon)

• A 2" flanged connector

2. Delivery Location The Aboveground Storage Tank will be delivered to Keesler AFB, MS Outdoor Recreation.