Date: September 8, 2022 ADDENDUM 1

PROJECT NAME: Renovate B4431 LRS

LOCATION: Bldg. 4431- Keesler AFB, Mississippi

PROJECT NUMBER: MAHG18-1009

WO: 81827

DIRECTIVES

SPECIFICATIONS:

1- OMIT Section 284600 Fire Detection and Alarm in its entirety.

2- ADD Section 283100 User-Addressable Interior Fire Alarm System with Integrated MNS.

END OF ADDENDUM 1

MachadoǀPatano, PLLC Wednesday, September 7, 2022 MǀP Design Group, PLLC

0110.21.001/ KAFB Renovate B4431

283100 - 1 ADDRESSABLE INTERIOR FIRE

ALARM SYSTEM WITH

INTEGRATED MNS

SECTION 283100 - ADDRESSABLE INTERIOR FIRE ALARM SYSTEM WITH INTEGRATED MNS

PART 1 GENERAL

REFERENCES

2.01 THE PUBLICATIONS LISTED BELOW FORM A PART OF THIS SPECIFICATION TO THE

EXTENT REFERENCED. THE PUBLICATIONS ARE REFERRED TO WITHIN THE TEXT BY

THE BASIC DESIGNATION ONLY.

2.02 SODIV TG-1008 TECHNICAL GUIDE FOR FIRE PROTECTION DESIGN

2.03 KEESLER AFB FIRE ALARM SYSTEM STANDARD FM GLOBAL (FM)

2.04 FM P7825 (2014) APPROVAL GUIDE

A. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

1. IEEE C62.41 (Latest Edition) Recommended Practice for Surge Voltages in Low- Voltage

AC Power Circuits

a. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

b. NFPA 101 (2021) Life Safety Code

c. NFPA 241 (2019) Safeguarding Construction, Alteration, and Demolition Operations

d. NFPA 72 (2022) National Fire Alarm Code

e. NFPA 90A (2018) Installation of Air Conditioning and Ventilating Systems

f. NFPA 1221 (2019) Standard for the Installation, Maintenance, and Use of Emergency

Services Communications Systems

g. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

h. NEMA ICS 6 (2016) Industrial Control and Systems: Enclosures

i. NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches

(600 Volts Maximum)

1) U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA) 47

CFR 90 Private Land Mobile Radio Services

2) UNDERWRITERS LABORATORIES (UL)

j. UL 1971 (2004) Signaling Devices for the Hearing Impaired

k. UL 268 (2021) Smoke Detectors for Fire Protective Signaling Systems

l. UL 464 (2004) Audible Signal Appliances

m. UL 497B (2004) Protectors for Data Communications and Fire Alarm Circuits

n. UL 1449 (2021) Transient Voltage Surge Suppressors

o. UL Elec Const Dir (Latest Edition) Electrical Construction Equipment Directory

p. UL Fire Prot Dir (Latest Edition) Fire Protection Equipment Directory UNIFIED

FACILITIES CRITERIA (UFC)

q. UFC 3-600-01 (Latest Edition) Design Fire Protection for Facilities

r. UFC 4-724-01 (Latest Edition) Air Force Visiting Quarters Facilities Design Guide

s. UFC 4-021-01 (Latest Edition) Design of O&M Mass Notification Systems

B. RELATED REQUIREMENTS

1. Section BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein.

C. DESCRIPTION OF WORK

D. Scope

1. This work includes designing and providing a new analog/addressable fire alarm, detection and communication system as described herein and on the contract drawings for Project KAFB Renovate. In addition to the fire alarm system, additional infrastructure components to accommodate a mass notification system shall be provided as described within the specification. The system shall include wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, power disconnect switches, alarm and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, automatic and manually operated equipment to issue voice messages, and other accessories and miscellaneous items required for a complete

283100 - 2 ADDRESSABLE INTERIOR FIRE

operating system even though each item is not specifically mentioned or described.

Provide system complete and ready for operation. Equipment, materials, installation, workmanship, inspection, and testing shall be in strict accordance with the required and advisory provisions of NFPA 72 and NFPA 70 except as modified herein. The system layout on the drawings show the area of coverage, which is the entire premises. The fire alarm is a delegated deisgn. Final design, quantity, layout, and coordination is the responsibility of the Contractor. The Contractor shall be responsible for placing the system program’s unique address on the individual devices in an inconspicuous location with a permanent marking system. Included with the location of the FACP shall be a file folder holder adjacent to the FACP.

E. SUBMITTALS

1. Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G"

2. designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01330 SUBMITTAL

PROCEDURES:

3. Provide six complete sets of submittals. Partial submittals will not be acceptable and will be returned without review. The contracting officer will review and approve submittals.

a. SD-02 Shop Drawings

1) Provide point-to-point wiring diagrams (French curves are not acceptable) showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems which are supervised or controlled by the system. Diagrams shall show connections from field devices to the FACP and remote fire alarm control units, initiating circuits, switches, relays and terminals.

2) Provide plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, point to point conduit routing, wire counts, circuit identification in each conduit, and circuit layouts for all floors.

3) Provide a complete description of the system operation input/output matrix format on the drawings.

4) Provide a complete list of device addresses and corresponding messages.

5) Include annotated catalog data, in table format on the drawings, showing manufacturer's name, model, voltage, and catalog numbers for equipment and components. Each proposed component shall be specifically identified within each catalog data sheet.

6) Provide complete riser diagrams indicating the wiring sequence of devices and their connections to the control equipment. Include a color code schedule for the wiring. Include floor plans showing the locations of devices and equipment.

(a) Battery power calculations, Voltage drop calculations

(1) Submit shop drawings not smaller than 600 by 915 mm (24 by 36 inches). As a minimum, the shop drawing submittal shall include the items listed above.

(b) SD-03 Product Data

(1) Fire alarm control panel (FACP); G Printers, covers, console rack, etc.;

G Terminal cabinets/assemblies; G Manual stations; G

(2) Voice command station including microphones, switches, and enclosures; G Batteries; G

(3) Battery chargers; G Smoke sensors; G Thermal sensors; G

(4) Wiring and cable; G Notification appliances; G

(5) Addressable interface devices; G Amplifiers; G

(6) Tone generators; G

(7) Digitalized voice generators; G Waterflow detectors; G Tamper switches; G

283100 - 3 ADDRESSABLE INTERIOR FIRE

(8) Smoke sensor testing procedures; G Radio transmitter and interface panels; G Digital alarm radio transmitter (DART); G

(9) Submit data on proposed equipment, including, but not limited to the items listed above. Include UL or FM listing cards for equipment provided.

(10) SD-06 Test Reports

(11) Furnish preliminary test results to the Contracting Officer. Include the control panel and initiating and indicating devices, a unique identifier for each device with an indication of test results, and signature of the factory-trained technician of the control panel manufacturer and equipment installer. With reports on preliminary tests, include printer information.

(12) SD-07 Certificates

(13) Qualifications of installer (Copy of NICET Certificate) SD-10 Operation and Maintenance Data

(14) INTERIOR FIRE ALARM SYSTEM, Data Package; G

F. ADDITIONAL SUBMITTAL REQUIREMENTS

G. Battery Power Calculations

1. Verify that battery capacity exceeds supervisory and alarm power requirements.

a. Provide complete battery calculations for both the alarm and supervisory power requirements. Ampere-hour requirements for each system component shall be submitted with the calculations.

b. Provide data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances, 25 percent spare capacity for initiating devices.

Annotate data for each circuit on the drawings.

c. Provide data to indicate that the amplifiers have sufficient capacity to simultaneously drive fire alarm speakers at their 1/2 watt tap plus 50 percent spare capacity.

Annotate data for each circuit on the drawings.

d. Provide a detailed description of the final acceptance testing procedures (including equipment necessary for testing smoke detectors using real smoke).

H. Qualifications of Installer & Designer

1. Design shall be by a National Institute for Certification in Engineering Technologies

(NICET) Level III or IV Technician. Installer shall have a fully staffed, Factory Authorized and licensed office, which has been in existence for at least 3 years. Installation shall be accomplished by a NICET Level II technician with at least 3 years experience in the installation of “voice evacuation and MNS” systems. The Contracting Officer may reject any proposed installer who cannot show evidence of such qualifications. The services of a technician authorized by the control equipment manufacturer shall be provided to supervise installation, adjustments, and final certification tests of the system. The Contractor shall furnish evidence that the fire alarm equipment supplier has an experienced and effective service organization which carries a stock of repair parts for the system to be furnished. The Contractor shall guarantee labor, materials, and equipment provided under this contract against defects for a period of one year after the date of final acceptance of this work by the Contracting Officer and the receipt of as- built drawings and schematics of all equipment. Prior to installation, submit data for approval by the contracting officer, showing that the Contractor has successfully installed addressable, analog intelligent interior fire alarm systems of the same type as specified herein, or that the Contractor has a firm contractual agreement with a subcontractor having such required experience. Include the names and locations of at least three installations where the Contractor or the subcontractor referred to above, has installed such systems. Indicate the type and design of each system and certify that each system has performed satisfactorily in the manner intended for a period of not less than 18 months. Submit names and phone numbers of points of contact at each site.

I. Record Drawing Software

283100 - 4 ADDRESSABLE INTERIOR FIRE

1. Furnish three sets of compact diskettes (CDs) containing AutoCAD 2000 or higher version drawings in DWG format of as-built drawings and schematics.

J. QUALITY ASSURANCE

1. Equipment and devices shall be compatible and operable with existing station fire alarm system and shall not impair reliability or operational functions of existing supervising station fire alarm system.

2. Existing supervising station fire alarm system operates at a non-narrow band frequency of

139.6750 MHz.

K. Regulatory Requirements

1. Devices and equipment for fire alarm service shall be listed by UL Fire Prot Dir or approved by FM P7825.

L. Requirements for Fire Protection Service

1. Equipment and material shall have been tested by UL and listed in UL Fire Prot Dir or approved by FM and listed in FM P7825. Where the terms "listed" or "approved" appear in this specification, they shall mean listed in UL Fire Prot Dir or FM P7825. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement.

M. Testing Services or Laboratories N. Fire alarm and fire detection equipment shall be constructed in accordance with UL Fire Prot

Dir, UL Elec Const Dir, or FM P7825.

O. Standard Products

1. Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory, such as UL or FM, and listed or approved for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials.

P. Modification of References

1. In NFPA publications referred to herein, consider advisory provisions to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; interpret reference to "authority having jurisdiction" to mean the Keesler Air Force Base Fire Marshal.

2. The recommended practices stated in the manufacturer's literature or documentation shall be considered as mandatory requirements.

Q. DELIVERY, STORAGE, AND HANDLING

1. Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

R. SPARE PARTS AND TOOLS

S. Interchangeable Parts

1. Spare parts furnished shall be directly interchangeable with the corresponding components of the installed system. Spare parts shall be suitably packaged and identified by nameplate, tagging, or stamping. Spare parts shall be delivered to the Contracting Officer at the time of the final acceptance testing.

T. Spare Parts

1. Furnish the following spare parts and accessories:

a. 4 audiovisual appliances of each type installed

b. 4 fuses for each fused circuit

c. 2 manual stations

d. 9 spare reams of paper for the system printer, plus sufficient paper for fire alarm acceptance tests

e. 2 smoke sensors and base of each type installed

f. 2 heat sensors and base of each type installed

283100 - 5 ADDRESSABLE INTERIOR FIRE

g. 3 spare printer ribbons

h. 3 test devices for each type of sensors installed

U. Parts List

1. Furnish a list, in duplicate, of all other parts and accessories which the manufacturer of the system recommends to be stocked for maintenance.

V. 1.9 KEYS

1. Keys and locks for equipment shall be identical. Provide not less than six keys, keyed to

PK 625.

PART 2 PRODUCTS

EXISTING FIRE ALARM EQUIPMENT

4.01 EXISTING FIRE ALARM EQUIPMENT SHALL BE MAINTAINED FULLY OPERATIONAL UNTIL

THE NEW EQUIPMENT HAS BEEN TESTED AND ACCEPTED BY THE CONTRACTING

OFFICER. AS NEW EQUIPMENT IS INSTALLED, IT SHALL BE LABELED "NOT IN SERVICE"

UNTIL THE NEW EQUIPMENT IS ACCEPTED. ONCE THE NEW SYSTEM IS COMPLETED,

TESTED, AND ACCEPTED BY THE GOVERNMENT, IT SHALL BE PLACED IN SERVICE AND

CONNECTED TO THE STATION FIRE ALARM SYSTEM. NEW EQUIPMENT SHALL HAVE

TAGS REMOVED AND THE EXISTING EQUIPMENT SHALL BE TAGGED "NOT IN SERVICE"

UNTIL REMOVED FROM THE BUILDING.

A. Equipment Removal

1. After acceptance of the new system by the Contracting Officer, existing equipment shall be removed, unused exposed conduit shall be removed, and damaged surfaces shall be restored. The material shall be removed from the site and disposed of by the Contractor.

B. Repair Service/Replacement Parts

1. Repair services and replacement parts for the system shall be furnished under this contract and be available for a period of 10 years after the date of final acceptance of this work by the Contracting Officer. On-site service during the guarantee period shall be provided within 24 hours after notification. All repairs shall be completed within 48 hours after notification.

C. Manufacturer Qualifications

1. Components shall be of current design and shall be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72, except as otherwise or additionally specified herein. Acceptable manufacturers of the fire alarm, detection and communications systems are Monaco addressable, Siemens MXL, FCI, and EST.

D. INTERIOR FIRE ALARM SYSTEM DESIGN

E. Definitions

1. Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions shall be defined as follows:

a. Addressable System: A system in which multiple signals are transmitted via the same conduction path to a remote fire alarm control unit and fire alarm control panel, decoded and separated so that each signal will initiate the specified response.

b. Hard Wired System: A system in which alarm and supervisory initiating devices are directly connected, through individual dedicated conductors, to a central control panel without the use of analog/addressable circuits or devices.

c. Interface Device: An addressable device which interconnects hard wired systems or devices to an analog/addressable system.

d. Fire Alarm Control Unit: A control panel, remote from the fire alarm control panel, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm control panel.

283100 - 6 ADDRESSABLE INTERIOR FIRE

e. Fire Alarm Control Panel (FACP): A master control panel having the features of a fire alarm control unit and to which fire alarm control units are interconnected. The panel has central processing, memory, input and output terminals, LED display panel and printers.

f. Terminal Cabinet: A steel cabinet with locking, hinge-mounted door in which terminal strips are securely mounted.

g. Remote Microphone Station: A steel cabinet with hinge-mounted door containing a remote microphone and associated equipment with controls providing redundant capabilities to the microphone provided at the FACP.

F. System Operation

1. The system shall be a complete, supervised, non-coded, addressable fire alarm system conforming to NFPA 72. The system shall have an interconnected riser loop or network having Style 7, Class A supervision that shall not be located in the same room or shaft.

The return portion of the loop shall be remote from the supply portion of the loop. Where the building has two stairs for egress from floors above grade, a single impairment cannot adversely affect more than one floor. Where three or more stairs are provided for egress from floors above grade, a single impairment cannot adversely affect more than 1/2 of any floor. Any single impairment of the system shall not affect the system on more than one-half of any floor. The system shall operate in the alarm mode upon actuation of any alarm initiating device. The system shall remain in the alarm mode until initiating device(s) are reset and the fire alarm control panel is manually reset and restored to normal. "T"-tapping of any fire alarm circuit is not allowed. The system shall provide the following functions and operating features:

a. The FACP and fire alarm control units, if used, shall provide power, annunciation, supervision, and control for the system.

b. Provide Class A, Style Ea initiating device circuits.

c. Provide Class A, Style 7a signaling line circuits for each floor.

d. Provide Class A, Style 7a signaling line circuits for the network.

1) Provide Class A, Style Z notification appliance circuits. Separate NAC circuits shall be provided for the audible and visible appliances. The visual alarm notification appliances shall have the flash rates synchronized. Separate notification circuits shall be provided for the mass notification system visible appliances.

(a) Provide electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control panel.

(1) Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. Provide a trouble alarm silence feature which shall silence the audible trouble signal, without affecting the visual indicator. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke sensor in the process of being verified for the actual presence of smoke shall not initiate a trouble condition.

(2) Provide a notification appliance silencing switch which, when activated, will silence the audible signal appliance, but will not affect the visual alarm indicator, the liquid crystal display, or the automatic notification of the Keesler AFB Fire Department. This switch shall be overridden upon activation of a subsequent alarm.

(3) Provide alarm verification capability for smoke sensors. Alarm verification shall initially be set for 30 seconds.

(4) Provide program capability via switches in a locked portion of the FACP to bypass the automatic notification appliance circuits, fire

283100 - 7 ADDRESSABLE INTERIOR FIRE

reporting system, and air handler shutdown features. Operation of this programming shall indicate this action on the FACP display and printer output.

(5) Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the Keesler AFB Fire Department.

(6) Alarm functions shall override trouble or supervisory functions.

Supervisory functions shall override trouble functions.

(7) The system shall be capable of being programmed from the panel’s keyboard. Programmed information shall be stored in non-volatile memory.

(8) The system shall be capable of operating, supervising, and/or monitoring both addressable and non-addressable alarm and supervisory devices.

(9) There shall be no limit, other than maximum system capacity, as to the number of addressable devices which may be in alarm simultaneously.

(10) Where the fire alarm system is responsible for initiating an action in another emergency control device or system, such as an HVAC system, the addressable fire alarm relay shall be within 915 mm (3 feet) of the emergency control device.

(11) An alarm signal shall automatically initiate the following functions:

(12) Transmission of an alarm signal to a designated zone on the building's digital alarm radio transmitter (DART).

(13) Visual indication of the device operated on the fire alarm control panel

(FACP).

(14) Continuous actuation of all alarm notification appliances.

(15) Recording of the event via the system printer.

(16) Operation of a duct smoke sensor shall shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph.

(17) A supervisory signal shall automatically initiate the following functions:

(18) Visual indication of the device operated on the FACP and sound the audible alarm at the respective panel.

(19) Transmission of a supervisory signal to a designated zone on the building's digital alarm radio transmitter (DART).

(20) Recording of the event via the system printer.

(21) A trouble condition shall automatically initiate the following functions:

(22) Visual indication of the system trouble on the FACP and sound the audible alarm at the respective panel.

(23) Transmission of a trouble signal to a designated zone on the building's digital alarm radio transmitter (DART).

(24) Recording of the event via the system printer.

(25) The maximum permissible elapsed time between the actuation of an initiating device and its indication at the FACP shall be 15 seconds.

(26) The maximum elapsed time between the occurrence of the trouble condition and its indication at the FACP shall not exceed 200 seconds.

(27) Each horn/strobe location shall have installed 2 horn/strobes. One shall have clear lens and shall act as notification device in the event of a fire alarm. One shall have an amber lens and shall act as notification device in the vent of a mass notification alarm.

G. System Monitoring

1. Valves: Each valve affecting the proper operation of a fire protection system, including automatic sprinkler control valves, sprinkler service entrance valve, and valves at backflow preventers, whether supplied under this contract or existing, shall be electrically monitored

283100 - 8 ADDRESSABLE INTERIOR FIRE

to ensure its proper position. Each tamper switch shall be provided with a separate address.

H. Surge Protection I. Line Voltage Surge Suppression

1. Provide line voltage surge arresters to suppress all voltage transients that might damage fire alarm panel/transmitter components. Unit shall wire in series with the power supply of the protected equipment with screw terminations. Unit shall be UL 1449 listed with a 330-volt suppression level and have a maximum response time of 5 nanoseconds. Unit shall also meet IEEE C62.41 category B tests for surge capacity. Device shall feature multi stage construction that includes inductors and silicon avalanche zener diodes. Device shall feature a long life indicator lamp (light emitting diode or neon lamp) that extinguishes upon failure of protection components. Any unit fusing shall be externally accessible win this feature is available. One such acceptable product is a model HSP-121BT-1RU as manufactured by Edco of Florida (Ocala, FL) or equal. Provide detailed manufacturer’s submittal data demonstrating compliance with all the above listed requirements.

J. Low Voltage Surge Suppression K. Provide low voltage surge arrestors to suppress al voltage transients on initiating, signaling, notification, transmitter tripping, and auxiliary control circuits. Provide protection for all circuits that leave the building shell. Unit(s) shall be UL 497B listed with a 30-volt clamping level and have a maximum response time of 5 nanoseconds. Device shall feature multi stage construction and both differential/common mode protection. Install units in strict accordance with the manufacturer’s recommendations. One such acceptable product is a model P264 (audible/visual device circuits) and model PC-642030XLC (initiating circuits) as manufactured by Edco Inc. of Florida (Ocala, FL) or equal. Provide detailed manufacturer’s submittal data demonstrating compliance with all the above listed requirements.

L. Addressable Interface Devices

1. The addressable interface (AI) device shall provide an addressable input interface to the

FACP for monitoring normally open or normally closed contact devices such as waterflow switches, valve supervisory switches, independent smoke detection systems, relays for output function actuation, etc.

M. Smoke Sensors N. Advanced Multi-criteria Smoke Sensors

1. Provide addressable multi-criteria smoke sensors as follows:

a. Provide analog/addressable ASA smoke sensors utilizing at a minimum,the photoelectric light scattering principle, along with adnaved algorithm technology for operation in accordance with UL 268. Smoke sensors shall be listed for use with the fire alarm control panel.

b. Provide self-restoring type sensors which do not require any readjustment after actuation at the FACP to restore them to normal operation. Sensors shall be UL listed as smoke- automatic fire sensors.

c. Components shall be rust and corrosion resistant. Vibration shall have no effect on the sensor's operation. Protect the detection chamber with a fine mesh metallic screen which prevents the entrance of insects or airborne materials. The screen shall not inhibit the movement of smoke particles into the chamber.

d. Provide twist lock bases for the sensors. The sensors shall maintain contact with their bases without the use of springs. Provide companion mounting base with screw terminals for each conductor. Terminate field wiring on the screw terminals. The sensor shall have a visual indicator to show actuation.

e. The sensor address shall identify the particular unit, its location within the system, and its sensitivity setting. Sensors shall be of the low voltage type rated for use on a 24 VDC system.

f. An operator at the control panel, having a proper access level, shall have the capability to manually access the following information for each initiating device.

283100 - 9 ADDRESSABLE INTERIOR FIRE

g. Primary status

h. Device type

i. Present average value

j. Present sensitivity selected

k. Sensor range (normal, dirty, etc.)

l. An operator at the control panel, having the proper access level, shall have the capability to manually control the following information for each heat sensor:

m. Alarm detection sensitivity values

n. Enable or disable the point/device

o. Control sensor's relay driver output

O. Duct Smoke Sensors

1. Duct smoke sensors shall be analog/addressable ASA type as described in paragraph entitled "Smoke Sensors," and shall be provided in ductwork in accordance with NFPA 90A and in accordance with manufacturers recommendations.

P. 2.2.6.2.1 Remote Test Switch

1. Duct detectors located greater that 1829 mm (6 feet) above the floor shall be provided with a remote indicator and remote test switch.

Q. 2.2.6.3 Smoke Sensor Testing

1. Smoke sensors shall be tested in accordance with manufacturer's recommended calibrated test method. Submit smoke sensor testing equipment and procedures for approval.

R. Thermal Sensors Not used.

S. Electric Power T. 2.2.8.1 Primary Power

1. Provide primary power for the FACP from a heavy-duty, fused disconnect switch fed from an electrical circuit to the building. Power shall be 120 VAC service, transformed through a two-winding, isolation type transformer and rectified to low voltage DC for operation of circuits and devices. The disconnect switch shall be provided with a red and white engraved plastic sign stating “FIRE ALARM SYSTEM”, and shall be permanently affixed to the face of the switch, and provided with a lockable handle or cover. Provide appropriate equipment to protect against power surges.

U. Emergency Power Supply

1. Provide for system operation in the event of primary power source failure. Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power shall be automatic and shall not cause transmission of a false alarm.

V. Batteries

1. Provide sealed, maintenance-free, gel cell batteries as the source for emergency power to the FACP. Batteries shall contain suspended electrolyte. The battery system shall be maintained in a fully

2. charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.

W. Capacity

1. Provide the batteries with sufficient capacity to operate the system under supervisory and trouble conditions, including audible trouble signal devices for 60 hours and audible and visual signal devices under alarm conditions for an additional 15 minutes.

X. Battery Chargers

1. Provide a solid state, fully automatic, variable charging rate battery charger. The charger shall be capable of providing 150 percent of the connected system load and shall maintain the batteries at full charge. In the event the batteries are fully discharged, the charger shall recharge the batteries back to 95 percent of full charge within 48 hours. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.

283100 - 10 ADDRESSABLE INTERIOR FIRE

Y. System Field Wiring Z. Wiring Within Cabinets, Enclosures, Boxes, Junction Boxes, and Fittings

1. Provide wiring installed in a neat and workmanlike manner and installed parallel with or at right angles to the sides and back of any box, enclosure, or cabinet. Conductors which are terminated, spliced, or otherwise interrupted in any enclosure, cabinet, mounting, or junction box shall be connected to terminal blocks and labeled at each end in accordance with Section 2.2.10.4 of this Specification. Mark each terminal in accordance with the wiring diagrams of the system. Make connections with approved pressure type terminal blocks, which are securely mounted. The use of wire nuts or similar devices shall be prohibited. Conductors provided for the mass notification systems shall be routed between the FACP and the mass notification appliance backboxes, with a minimum 24 inch long coil and shall be provided in each for use.

AA. Terminal Cabinets

1. Provide a terminal cabinet at the base of any circuit riser, on each floor at each riser, and where indicated on the drawings. Terminal size shall be appropriate for the size of the wiring to be connected. Conductor terminations shall be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection shall be permanently mounted in the terminal cabinet. Minimum size is 200 mm by 200 mm (8 inches by 8 inches).

AB. Alarm Wiring

1. Signaling line circuits and initiating device circuit field wiring shall be copper, No. 18 AWG size, twisted, FPL conductors at a minimum. Notification appliance circuit conductors, other than speakers (including those for mass notification), shall be solid copper No. 14 AWG size conductors at a minimum.

2. Speaker circuits shall be copper No. 16 AWG size conductors at a minimum. Speaker circuits shall utilize twisted, shielded FPL conductors at a minimum. Wire size shall be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC shall not operate at less than 21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage. Power wiring, operating at 120 VAC minimum, shall be No. 12 AWG solid copper having similar insulation. Provide all wiring in rigid metal conduit or intermediate metal conduit. Electrical metallic tubing conduit is acceptable in dry locations not enclosed in concrete or where not subject to mechanical damage. Conceal conduit in finished areas of new construction and wherever practicable in existing construction. The use of flexible conduit not exceeding a 1830 mm (6 foot) length shall be

3. permitted in initiating device circuits. Run conduit or tubing concealed unless specifically shown otherwise on the drawings. Shielded wiring shall be utilized where recommended by the manufacturer. For shielded wiring, the shield shall be grounded at only one point, which shall be in or adjacent to the FACP. Color coding is required for circuits and shall be maintained throughout the circuit.

AC. Conductor Terminations

1. Labeling of conductors at terminal blocks in terminal cabinets, FACP, and remote fire alarm control units shall be provided at each conductor connection. Each conductor or cable shall have a shrink- wrap label to provide a unique and specific designation. Each terminal cabinet, FACP, and fire alarm control unit shall contain a laminated drawing which indicates each conductor, its label, circuit, and terminal. The laminated drawing shall be neat, using 12 point lettering minimum size, and mounted within each cabinet, panel, or unit so that it does not interfere with the wiring or terminals. Maintain existing color code scheme where connecting to existing equipment.

AD. Fire Alarm/MNS Control Panel (FACP)

1. Provide a complete control panel fully enclosed in a lockable steel enclosure as specified herein. Operations required for testing or for normal care and maintenance of the systems shall be performed from the front of the enclosure. If more than a single unit is required at a location to form a complete control panel, the unit enclosures shall match exactly. Each

283100 - 11 ADDRESSABLE INTERIOR FIRE

control unit shall provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit shall be suitable for operation on a 120 volt, 60 hertz, normal building power supply. Provide each panel with supervisory functions for power failure, internal component placement, and operation. Visual indication of alarm, supervisory, or trouble initiation on the fire alarm control panel shall be by liquid crystal display or similar means with a minimum of 80 characters of which at least 32 are field changeable.

AE. Cabinet

1. Install control panel components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of panels as well as field wiring. The enclosure shall be identified by an engraved laminated phenolic resin nameplate. Lettering on the nameplate shall say "Fire Alarm Control Panel" and shall not be less than one inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches. The cabinet shall be provided in a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and surface mounting provisions.

AF. Control Modules

1. Provide power and control modules to perform all functions of the FACP. Provide audible signals to indicate any alarm, supervisory, or trouble condition. The alarm signals shall be different from the trouble signal. Connect circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for identification. Locate diodes and relays, if any, on screw terminals in the FACP. Circuits operating at 24 VDC shall not operate at less than 21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage.

AG. Silencing Switches

1. Alarm Silencing Switch: Provide an alarm silencing switch at the FACP which shall silence the audible signal but not affect the visual alarm indicator. This switch shall be overridden upon activation of a subsequent alarm.

2. Supervisory/Trouble Silencing Switch: Provide supervisory and trouble silencing switch which shall silence the audible trouble and supervisory signal, but not extinguish the visual

3. indicator. This switch shall be overridden upon activation of a subsequent alarm, supervision, or trouble condition.

AH. Non-Interfering

1. Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Circuits shall be manually resettable by switch from the FACP after the initiating device or devices have been restored to normal.

AI. Fire Alarm Voice Message

1. The voice evacuation system shall provide for one-way voice communications, routing and pre- amplification of digital alarm tones and voice (digital and analog) messages. The following electronic tones shall be available from the amplifier: Slow Whoop, High/Los, Horn, Chime, Beep, Stutter, Wail and Bell. A fire alarm shall activate notification appliance circuits. Textual audible appliances shall produce a slow whoop tone for three cycles followed by a voice message which is repeated until the control panel is reset or silenced.

Automatic messages shall be broadcast through speakers on appropriate floors, but not in stairs. The visual strobes and audible message shall automatically be broadcast on all floors. A live voice message shall override the automatic audible output through use of a microphone input at either the FACP or remote microphone enclosure. The system shall have redundant microphones and allow for general paging within the space. One microphone shall be provided at the FACP with the second microphone provided in a cabinet at the First Floor entrance of each building. Operation shall be either manually from a control switch or automatically from the fire alarm control panel. When using the microphone, live messages shall be broadcast through speakers in stairs and throughout a selected floor or floors. The system shall be capable of operating all speakers at the same time. The digitized voice message shall consist of a non-volatile (EPROM)

283100 - 12 ADDRESSABLE INTERIOR FIRE

microprocessor based input to the amplifiers. The microprocessor shall actively interrogate circuitry, field wiring, and digital coding necessary for the immediate and accurate rebroadcasting of the stored voice data into the appropriate amplifier input. Loss of operating power, supervisory power, or any other malfunction which could render the digitized voice module inoperative shall automatically cause the slow whoop tone to take over all functions assigned to the failed unit. Messages shall utilize a female voice and shall be as follows:

2. "May I have your attention please. May I have your attention please. A fire emergency has been reported in the building. Please leave the building by the nearest exit or exit stairway." (Provide a 2 second pause.) “Do not use the elevators” (Provide a 2 second pause) "May I have your attention please..(repeat the message)."

AJ. Fire Alarm Signal

1. A fire alarm shall activate notification appliances throughout the building. Audible devices shall be fire alarm speakers. Visual devices shall be ADA, clear-lensed strobes operating in accordance with NFPA 72.

AK. Memory

1. Provide each control unit with non-volatile memory and logic for all functions. The use of long life batteries, capacitors, or other age-dependent devices shall not be considered as equal to non-volatile processors, PROMS, or EPROMS.

AL. Field Programmability

1. Provide control units and control panels that are fully field programmable for control, initiation, notification, supervisory, and trouble functions of both input and output. The system program configuration shall be menu driven. System changes shall be password protected and shall be accomplished using personal computer based equipment.

AM. Input/Output Modifications

1. The FACP shall contain features which allow the bypassing of input devices from the system or the modification of system outputs. These control features shall consist of a panel mounted keypad. Any bypass or modification to the system shall indicate a trouble condition on the FACP and a printed output of the trouble condition.

AN. Resetting

1. Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm, supervisory or trouble condition on the system still exists.

AO. Instructions

1. Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a stainless steel or aluminum frame. Install the instructions on the interior of the FACP. The card shall show those steps to be taken by an operator when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, supervisory, and trouble. The instructions shall be approved by the Contracting Officer before being posted.

AP. Walk Test

1. The FACP shall have a walk test feature. When using this feature, operation of initiating devices shall result in limited system outputs, so that the notification appliances operate for only a few seconds and the event is indicated on the system printer, but no other outputs occur.

AQ. History Logging

1. In addition to the required printer output, the control panel shall have the ability to store a minimum of 400 events in a log. These events shall be stored in a battery-protected memory and shall remain in the memory until the memory is downloaded or cleared manually. Resetting of the control panel shall not clear the memory.

AR. RS-232-C Output

1. Each local control panel shall be capable of operating remote service type cathode ray tubes (CRTs), printers, and/or modems. The output shall be paralleled ASCII from an EIA

283100 - 13 ADDRESSABLE INTERIOR FIRE

RS-232-C connection with a baud rate of 1200 or 2400 to allow use of any commonly available CRT, printer, or modem.

AS. Remote Fire Alarm Control Units Not used.

AT. Amplifiers, Preamplifier, Tone Generators

1. Any amplifiers, preamplifier, tone generators, digitized voice generators, and other hardware necessary for a complete, operational, textual audible circuit conforming to NFPA 72 shall be housed in a fire alarm control unit, terminal cabinet, or in the fire alarm control panel. The system shall automatically operate and control all building fire alarm speakers except those installed in the stairs.

2. The speakers in the stairs shall operate only when the microphone is used to deliver live messages. Each amplifier shall have two channels; one to broadcast a message and the other for paging.

AU. Construction

1. Amplifiers shall utilize computer grade solid state components and shall be provided with output protection devices sufficient to protect the amplifier against any transient up to 10 times the highest rated voltage in the system.

AV. Inputs

1. Each system shall be equipped with separate inputs from the tone generator, digitized voice driver and panel mounted microphone. Microphone inputs shall be of the low impedance, balanced line type. Both microphone and tone generator input shall be operational on any amplifier.

AW. Tone Generator

1. The tone generator shall be of the modular, plug-in type with securely attached labels to identify the component as a tone generator and to identify the specific tone it produces.

The tone generator shall produce a slow whoop tone, which shall slowly ascend from low (500 hertz) to high (1200 hertz), and shall be constantly repeated until interrupted by either the digitized voice message, the microphone input, or the alarm silence mode as specified. Each slow whoop cycle shall last approximately 4 seconds. The tone generator shall be single channel with an automatic backup generator per channel such that failure of the primary tone generator causes the backup generator to automatically take over the functions of the failed unit and also causes transfer of the common trouble relay.

AX. Protection Circuits

1. Each amplifier shall be constantly supervised for any condition which could render the amplifier inoperable at its maximum output. Failure of any component shall cause automatic transfer to a designated backup amplifier, illumination of a visual "amplifier trouble" indicator on the control panel, appropriate logging of the condition on the system printer, and other actions for trouble condition as specified.

AY. System Printer

1. Provide a UL listed system printer to record alarm, supervisory, and trouble conditions without loss of any signal or signals. Printout shall be by circuit, device, and function as provided in the FACP. Printer shall operate on a 120 VAC, 60 Hz power supply.

2. (1) The UL listed printer shall have at least 80 characters per line and have a 96 ASCII character set. The printer shall have a microprocessor-controlled, bi-directional, logic seeking head capable of printing 120 characters per second utilizing a 9 by 7 dot matrix print head. Printer shall not contain internal software which is essential for proper operation.

3. When the FACP receives a signal, the alarm, supervisory, and trouble condition shall be printed. The printout shall include the type of signal, the circuit or device reporting, the date, and the time of the occurrence. The printer shall differentiate alarm signals from other printed indications. When the system is reset, this condition shall also be printed including the same information concerning device, location, date, and time. Provide a means to automatically print a list of existing alarm, supervisory, and trouble conditions in the system. If a printer is off-line when an alarm is received, the system shall have a buffer

283100 - 14 ADDRESSABLE INTERIOR FIRE

to retain the data and it shall be printed when the printer is restored to service. The printer shall have an indicator to alert the operator that the paper has run out.

AZ. Manual Stations

1. Provide metal or plastic, semi-flush mounted, double action, addressable manual stations, which are not subject to operation by jarring or vibration. Stations shall be equipped with screw terminals for each conductor. Stations which require the replacement of any portion of the device after activation are not permitted. Stations shall be finished in fire-engine red with molded raised lettering operating instructions of contrasting color. The use of a key shall be required to reset the station.

BA. Notification Appliances BB. Fire Alarm Speakers

1. Provide fire alarm speakers conforming to UL 464 having a minimum of four tap settings and separate terminations for each in and out connection. Tap settings shall include taps of 1/4, 1/2, 1 and 2 watt. Speakers shall utilize the 1/2 watt tap in the system. Speakers shall have an output rating of 84 dBA at 3050 mm (10 feet) as determined by the reverberant room test; data on peak output as determined in an anechoic chamber is not suitable. Speakers shall be capable of installation on standard 100 mm (4 inch) square electrical boxes. Where speakers and strobes are provided in the same location, they may be combined into a single wall mounted unit.

2. Provide speaker mounting plates constructed of cold rolled steel having a minimum thickness of 16 gage and equipped with mounting holes and other openings as needed for a complete installation. Fabrication marks and holes shall be ground and finished to provide a smooth and neat appearance for each plate. Each plate shall be primed and painted.

BC. Visual Alarm Signals

1. Provide strobe light visual alarm signals which operate on a supervised 24 volt DC circuit.

The strobe lens shall comply with UL 1971 and conform to the Americans With Disabilities Act. The light pattern shall be disbursed so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe. The strobe flash output shall be a minimum of 75 candela based on the UL 1971 test. The strobe shall have a xenon flash tube or LED. Visible appliances may be part of an audio- visual assembly. Where more than two appliances are located in the same room or corridor, provide synchronized operation. The strobe and associated enclosure used to indicate a visual alarm for a waterflow condition on the exterior of the building shall be NEMA 4 or 4X rated for weatherproof installation. Both Amber lensed devices and clear lensed devices shall be installed at each location.

BD. 2.2.16.2.1 Waterflow Alarm Notification Signage

1. Provide a permanently mounted weatherproof metal or rigid plastic sign secured with corrosion resistant…