M|P Project # 0110.21.001 SET NO. _______

BOOKLET INCLUDING SOW,

SUBMITTALS FORM, ROM & EQUIP.

CUTSHEETS

MAHG181009

RENOVATE B4431

VECTRUS

KAFB

627 Parade Ln | Bldg. 4431 | KAFB, Biloxi | Mississippi 39534

REV 0 – Issued for Construction May 20, 2022

Air System Sizing Summary for PAC-1 Project Name: 0110.21.002 KAFB 4431 04/11/2022 Prepared by: Machado Patano 02:59PM

Hourly Analysis Program 5.10 Page 1 of 8

Air System Information Air System Name .......................................... PAC-1 Equipment Class ................................... SPLT AHU Air System Type ............................................... VAV

Number of zones Floor Area .......................................................... 4164.0 ft² Location ................................. Hattiesburg, Mississippi

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ................................................... 14.4 Tons Total coil load ................................................. 172.2 MBH Sensible coil load ............................................ 139.8 MBH Coil CFM at Jul 1600 ....................................... 7054 CFM Max block CFM at Jul 1600 ............................. 7554 CFM Sum of peak zone CFM ................................... 7779 CFM Sensible heat ratio .......................................... 0.812 CFM/Ton ........................................................ 491.6 ft²/Ton ............................................................. 290.2 BTU/(hr·ft²) ....................................................... 41.4 Water flow @ 10.0 °F rise .................................. N/A

Load occurs at ................................................. Jul 1600

OA DB / WB .................................................. 95.4 / 77.8 °F

Entering DB / WB .......................................... 73.1 / 62.3 °F Leaving DB / WB ........................................... 54.7 / 53.7 °F Coil ADP ................................................................. 52.6 °F Bypass Factor ...................................................... 0.100 Resulting RH ............................................................. 54 % Design supply temp. ............................................... 55.0 °F Zone T-stat Check ................................................ 8 of 8 OK Max zone temperature deviation ............................... 0.0 °F

Preheat Coil Sizing Data No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM at Jul 1600 ............................ 7554 CFM Standard CFM ................................................. 7514 CFM Actual max CFM/ft² ........................................... 1.81 CFM/ft²

Fan motor BHP ....................................................... 0.00 BHP Fan motor kW ......................................................... 0.00 kW Fan static ................................................................ 0.00 in wg

Outdoor Ventilation Air Data Design airflow CFM ........................................... 543 CFM CFM/ft² ............................................................. 0.13 CFM/ft²

CFM/person ........................................................... 8.72 CFM/person

Zone Sizing Summary for PAC-1

Prepared by: Machado Patano 02:59PM

Hourly Analysis Program 5.10 Page 2 of 8

Air System Information Air System Name .......................................... PAC-1 Equipment Class ................................... SPLT AHU Air System Type ............................................... VAV

Number of zones Floor Area .......................................................... 4164.0 ft² Location ................................. Hattiesburg, Mississippi

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load Space CFM Sizing ........... Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/ft²

Reheat Coil Load

(MBH)

Reheat Coil

Water gpm

@ 20.0 °F

Zone Htg Unit

Coil Load

(MBH)

Zone Htg Unit Water gpm

@ 20.0 °F

Mixing Box Fan Airflow

(CFM)

Zone 1 663 430 2.15 18.5 - 0.0 - 0 Zone 2 396 253 2.24 10.9 - 0.0 - 0 Zone 3 1023 221 1.59 9.5 - 0.0 - 0 Zone 4 511 433 1.40 18.6 - 0.0 - 0 Zone 5 832 298 1.78 12.8 - 0.0 - 0 Zone 6 1236 852 1.93 36.6 - 0.0 - 0 Zone 7 859 575 1.79 24.7 - 0.0 - 0 Zone 8 2105 1307 1.94 56.1 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone Cooling Time of Heating Floor Sensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (ft²) Zone 1 11.4 Oct 1400 11.6 308.0 Zone 2 6.8 Oct 1400 6.8 177.0 Zone 3 17.6 Jul 1400 1.7 645.0 Zone 4 8.8 Jul 1600 11.6 366.0 Zone 5 14.3 Jul 1500 8.0 467.0 Zone 6 21.2 Jul 1500 22.9 639.0 Zone 7 14.8 Aug 1500 15.5 479.0 Zone 8 36.2 Jul 1600 35.1 1083.0

Space Loads and Airflows

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

Zone 1 A101 VEHICLE DISPATCH 1 11.4 Oct 1400 663 11.6 308.0 2.15 Zone 2 A102 FLEET MANAGER 1 6.8 Oct 1400 396 6.8 177.0 2.24 Zone 3 A103.1 COPIER 1 5.9 Jul 1400 343 0.5 190.0 1.81 A103/A104 1 11.7 Jul 1400 679 1.2 455.0 1.49 Zone 4 A105 OFFICE 1 3.2 Jun 1700 188 4.2 122.0 1.54 A106 OFFICE 1 2.5 Jul 1600 148 3.3 122.0 1.21 A107 OFFICE 1 3.0 Jul 1600 176 4.1 122.0 1.44 Zone 5 A108 CONFERENCE RM 1 14.3 Jul 1500 832 8.0 467.0 1.78 Zone 6

Zone Sizing Summary for PAC-1

Prepared by: Machado Patano 02:59PM

Hourly Analysis Program 5.10 Page 3 of 8

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

A109/A110 1 21.2 Jul 1500 1236 22.9 639.0 1.93 Zone 7 A103.2 CORRIDOR 1 1.5 Oct 1400 89 2.3 51.0 1.74 A111 COMM 1 4.3 Jul 1400 250 0.2 68.0 3.68 A111.1 JANITOR 1 0.3 Jul 1400 16 0.1 35.0 0.46 A112 WOMEN 1 0.7 Jul 1400 41 0.1 54.0 0.76 A113 MENS 1 1.3 Sep 1700 77 2.0 54.0 1.42 A114 ELECTRICAL 1 2.0 Jul 1500 116 2.1 52.0 2.23 A115 MECHANICAL 1 5.0 Aug 1600 289 8.7 165.0 1.75 Zone 8 B101 TENANT SPACE 1 33.0 Jul 1600 1922 29.0 973.0 1.98 B102 MENS 1 2.2 Aug 1900 130 4.1 56.0 2.33 B103 WOMENS 1 1.3 Sep 1700 77 2.0 54.0 1.42

Air System Design Load Summary for PAC-1

Prepared by: Machado Patano 02:59PM

Hourly Analysis Program 5.10 Page 4 of 8

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG

COOLING OA DB / WB 95.4 °F / 77.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 315 ft² 11390 - 315 ft² - - Wall Transmission 2955 ft² 17486 - 2955 ft² 39654 - Roof Transmission 4164 ft² 11277 - 4164 ft² 7931 - Window Transmission 315 ft² 8039 - 315 ft² 17562 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 168 ft² 4059 - 168 ft² 6293 - Floor Transmission 4164 ft² 0 - 4164 ft² 9370 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 4997 W 17049 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 9118 W 31110 - 0 0 - People 62 15263 12772 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 11567 1277 40% 32324 0 >> Total Zone Loads - 127242 14049 - 113134 0 Zone Conditioning - 124291 14049 - 111615 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 6854 CFM 0 - 4259 CFM 0 - Ventilation Load 507 CFM 12992 18328 321 CFM 15481 0 Supply Fan Load 7054 CFM 0 - 4459 CFM 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 2% 2545 - 2% 2263 - >> Total System Loads - 139829 32377 - 129359 0 Central Cooling Coil - 139829 32379 - -48226 0 Preheat Coil - 0 - - 0 - Terminal Reheat Coils - 0 - - 177585 - >> Total Conditioning - 139829 32379 - 129359 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads

Zone Design Load Summary for PAC-1

Hourly Analysis Program 5.10 Page 5 of 8

Zone 1 DESIGN COOLING DESIGN HEATING COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG

COOLING OA DB / WB 88.4 °F / 73.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 40 ft² 3208 - 40 ft² - - Wall Transmission 332 ft² 1807 - 332 ft² 4455 - Roof Transmission 308 ft² 667 - 308 ft² 587 - Window Transmission 40 ft² 657 - 40 ft² 2230 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 0 ft² 0 - 0 ft² 0 - Floor Transmission 308 ft² 0 - 308 ft² 979 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 370 W 1261 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 664 W 2266 - 0 0 - People 2 490 410 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 1036 41 40% 3300 0 >> Total Zone Loads - 11392 451 - 11551 0

Zone 2 DESIGN COOLING DESIGN HEATING COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG

COOLING OA DB / WB 88.4 °F / 73.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 25 ft² 2005 - 25 ft² - - Wall Transmission 191 ft² 1040 - 191 ft² 2563 - Roof Transmission 177 ft² 384 - 177 ft² 337 - Window Transmission 25 ft² 411 - 25 ft² 1394 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 0 ft² 0 - 0 ft² 0 - Floor Transmission 177 ft² 0 - 177 ft² 566 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 212 W 725 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 406 W 1385 - 0 0 - People 1 245 205 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 619 21 40% 1944 0 >> Total Zone Loads - 6813 226 - 6804 0

Hourly Analysis Program 5.10 Page 6 of 8

Zone 3 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

COOLING OA DB / WB 95.4 °F / 77.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - - Wall Transmission 0 ft² 0 - 0 ft² 0 - Roof Transmission 645 ft² 2045 - 645 ft² 1229 - Window Transmission 0 ft² 0 - 0 ft² 0 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 0 ft² 0 - 0 ft² 0 - Floor Transmission 645 ft² 0 - 645 ft² 0 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 774 W 2641 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 2668 W 9103 - 0 0 - People 9 2193 1835 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 1598 183 40% 491 0 >> Total Zone Loads - 17580 2018 - 1720 0

Zone 4 DESIGN COOLING DESIGN HEATING

COOLING OA DB / WB 95.4 °F / 77.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 15 ft² 313 - 15 ft² - - Wall Transmission 360 ft² 1875 - 360 ft² 4831 - Roof Transmission 366 ft² 991 - 366 ft² 697 - Window Transmission 15 ft² 383 - 15 ft² 836 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 21 ft² 547 - 21 ft² 853 - Floor Transmission 366 ft² 0 - 366 ft² 1082 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 439 W 1499 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 480 W 1638 - 0 0 - People 3 735 615 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 798 62 40% 3320 0 >> Total Zone Loads - 8779 677 - 11618 0

Hourly Analysis Program 5.10 Page 7 of 8

Zone 5 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 96.0 °F / 78.0 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 30 ft² 605 - 30 ft² - - Wall Transmission 180 ft² 869 - 180 ft² 2415 - Roof Transmission 467 ft² 1409 - 467 ft² 890 - Window Transmission 30 ft² 772 - 30 ft² 1673 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 0 ft² 0 - 0 ft² 0 - Floor Transmission 467 ft² 0 - 467 ft² 746 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 560 W 1912 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 500 W 1706 - 0 0 - People 23 5721 4787 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 1299 479 40% 2289 0 >> Total Zone Loads - 14293 5265 - 8013 0

Zone 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 96.0 °F / 78.0 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 103 ft² 3010 - 103 ft² - - Wall Transmission 507 ft² 3083 - 507 ft² 6797 - Roof Transmission 639 ft² 1928 - 639 ft² 1217 - Window Transmission 103 ft² 2638 - 103 ft² 5715 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 21 ft² 545 - 21 ft² 853 - Floor Transmission 639 ft² 0 - 639 ft² 1763 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 767 W 2616 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 890 W 3037 - 0 0 - People 10 2450 2050 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 1931 205 40% 6538 0 >> Total Zone Loads - 21238 2255 - 22883 0

Hourly Analysis Program 5.10 Page 8 of 8

Zone 7 DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 96.0 °F / 78.0 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - - Wall Transmission 444 ft² 2888 - 444 ft² 5958 - Roof Transmission 479 ft² 1378 - 479 ft² 912 - Window Transmission 0 ft² 0 - 0 ft² 0 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 84 ft² 1580 - 84 ft² 2881 - Floor Transmission 479 ft² 0 - 479 ft² 1285 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 575 W 1961 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 1500 W 5118 - 0 0 - People 2 490 410 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 1342 41 40% 4415 0 >> Total Zone Loads - 14757 451 - 15451 0

Zone 8 DESIGN COOLING DESIGN HEATING

COOLING OA DB / WB 95.4 °F / 77.8 °F HEATING OA DB / WB 24.0 °F / 20.1 °F

OCCUPIED T-STAT 71.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 103 ft² 6064 - 103 ft² - - Wall Transmission 942 ft² 5560 - 942 ft² 12634 - Roof Transmission 1083 ft² 2933 - 1083 ft² 2063 - Window Transmission 103 ft² 2616 - 103 ft² 5715 - Skylight Transmission 0 ft² 0 - 0 ft² 0 - Door Loads 42 ft² 1482 - 42 ft² 1706 - Floor Transmission 1083 ft² 0 - 1083 ft² 2949 - Partitions 0 ft² 0 - 0 ft² 0 - Ceiling 0 ft² 0 - 0 ft² 0 - Overhead Lighting 1300 W 4434 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 2010 W 6858 - 0 0 - People 12 2940 2460 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 3289 246 40% 10026 0 >> Total Zone Loads - 36175 2706 - 35093 0

Job Number: NB6KB3 Page Prepared Date: 4/7/2022 Job Name: KAFB Bldg 4431

1 of 11 www.DaikinApplied.com

Table of Contents

Specification for CU-1

Technical Data Sheet for CU-1

Drawings(1) for CU-1

Drawings(2) for CU-1

Specification for CU-1

Job Name: KAFB Bldg 4431 2 of 11 www.DaikinApplied.com

Specificati on for CU-1

PART 1: GENERAL

1.01 Section Includes:

A. Condensing unit rated and certified in accordance with AHRI Standard 365.

1.02 SUBMITTALS

A. Shop Drawings: Indicate assembly, unit dimensions, weight loading, required clearances, construction details, field connection details, electrical characteristics and connection requirements.

B. Product Data:

1. Provide literature that indicates dimensions, weights, capacities, ratings, and electrical characteristics and connection requirements.

1.03 OPERATION AND MAINTANENCE DATA

A. Maintenance Data: Provide instructions for installation, maintenance and service

1.04 QUALIFICATIONS

A. Manufacturer: Company specializing in manufacturing the Products specified in this section with minimum five years documented experience, who issues complete catalog data on total product.

B. Startup must be done by trained personnel experienced with split systems.

C. Do not operate units for any purpose, temporary or permanent, until remote controls are in place, and manufacturers’ installation instructions have been followed.

1.05 DELIVERY, STORAGE, HANDLING

A. Deliver, store, protect and handle products to site.

B. Handle carefully to avoid damage to components, enclosures, and finish C. Store in a clean, dry place to protect from weather and construction traffic.

PART 2: PRODUCTS

2.01 MANUFACTURERS

A. Basis of Design: Daikin Applied

2.02 GENERAL DESCRIPTION

A. Furnish as shown on plans, Condensing Unit(s) . Unit performance and electrical characteristics shall be per the job schedule.

B. Configuration: Fabricate as detailed on prints and drawings.

C. The complete unit shall be ETL listed.

D. Unit shall be completely factory assembled and shipped in one piece.

E. Unit to be shipped with a nitrogen holding charge only.

F. The unit shall undergo an operational test prior to shipment. The factory test shall include a refrigeration circuit check test, a unit safety control system operations checkout, and a final unit inspection.

G. All units shall have decals and tags to indicate caution areas and aid unit service. Unit nameplates shall be fixed to the main control panel door. Electrical wiring diagrams shall be attached to the control panels. Installation, operating and maintenance bulletins and start-up forms shall be supplied with each unit.

H. Performance: All scheduled capacities and face areas are the minimum accepted value. All scheduled amps, KW, and HP are maximum accepted values that allow scheduled capacity to be met.

2.03 CABINET

A. Exterior surfaces shall be constructed of painted galvanized steel, for aesthetics and long-term durability. Paint finish will include a base primer with a high-quality polyester resin topcoat. Finished, unabraded panel surfaces shall

Job Name: KAFB Bldg 4431 3 of 11 www.DaikinApplied.com be exposed to an ASTM B117 salt spray environment and exhibit no visible red rust at a minimum of 3,000 hours exposure. Finished, abraded surfaces shall be tested per ASTM D1654, having a mean scribe creepage not exceeding 1/16” at 1,000 hours minimum exposure to an ASTM B117 salt spray environment. Measurements of results shall be quantified using ASTM D1654 in conjunction with ASTM D610 and ASTM D714 to evaluate blister and rust ratings.

B. The unit base frame shall be constructed of 15 gauge pre-painted galvanized steel.

C. Lifting brackets shall be provided on the unit base with lifting holes to accept cable or chain hooks.

2.04 ELECTRICAL

A. Unit wiring shall comply with NEC requirements and with all applicable UL standards. All electrical components shall be UL recognized where applicable. All wiring and electrical components provided with unit shall be number and color coded and labeled according to the electrical diagram provided for easy identification.

B. The unit shall be provided with a factory wired weatherproof control panel. Unit shall have a power terminal block for main power connection. A terminal board shall be provided for low voltage control wiring. Branch circuit short circuit protection, 115 volt control circuit transformer and fuse, system switches, and a high temperature sensor. Each compressor and condenser fan motor shall be furnished with contactors and inherent thermal overload protection. Knockouts shall be provided in the side of the main control panels for field wiring entrance.

C. All 115-600 volt internal and external wiring between control boxes and components shall be protected from damage by raceways or liquid tight conduit.

D. The receptacle shall be powered by a field supplied 115V source.

E. Single terminal block shall be provided for connecting electrical power at the unit.

F. Unit SCCR rating to be 10 kAIC.

G. Unit shall be provided with a 24 volt transformer and terminal strip for field supplied controls.

2.05 DISCHARGE AND RETURN PLENUM OPTIONS

A. A supply air discharge plenum shall be provided. The plenum section shall have a discharge opening.

2.06 CONDENSING SECTION

A. Air Cooled Condenser

1. The condensing section shall be open on the sides and bottom to provide access and to allow airflow through the coils. Condenser coils shall be multi-row and fabricated from cast aluminum micro-channel coils. Each condenser coil shall be factory leak tested with high-pressure air under water. Coils are to be recessed so that the cabinet provides built in hail protection.

2. Condenser fans shall be direct drive, propeller type designed for low tip speed, vertical air discharge, and include service guards. Fan blades shall be constructed of steel and riveted to a steel center hub. Condenser fan motors shall be heavy-duty, inherently protected, three-phase, non-reversing type with permanently lubricated ball bearing and integral rain shield.

3. Units shall have at least one head pressure sensing condenser fan controlled to maintain positive head pressure. An ambient thermostat shall prevent the refrigeration system from operating below 45º F ambient.

SpeedTrol™ condenser fan speed control shall be added to the last fan off on each refrigeration circuit to provide cooling operation to ambient temperatures down to 0° F. Fan speed control shall be field adjustable.

B. Scroll Compressors

1. Each unit shall have multiple, heavy-duty Copeland scroll compressors.

2. Each compressor shall be complete with gauge ports, crankcase heater, sight-glass, anti-slug protection, motor overload protection and a 5 minute time anti-cycling time delay.

3. Compressors shall be isolated with resilient rubber isolators to decrease noise transmission.

C. Refrigeration Circuit

1. Each unit shall have two independent refrigeration circuits. Each circuit shall be complete with low pressure control, liquid line charging valve with a 3/8" charging port, a manual reset high pressure safety switch. Each

Job Name: KAFB Bldg 4431 4 of 11 www.DaikinApplied.com

Circuit shall be dehydrated, leak tested, and shipped with a Nitrogen holding charge. Unit shall have discharge and suction line shutoff valves.

2. Each compressor shall be complete with gauge, ports, crankcase heater, sight - glass, anti-slug protection, motor overload protection and a 5 minute time anti-cycling time delay.

D. Hot gas bypass capped T shall be factory installed on the discharge line of refrigerant circuits.

2.07 CONTROLS

A. Refrigeration capacity control shall be accomplished by staging of the unit's multiple compressors. Unit shall be equipped with a 120V terminal strip for field supplied and installed controls

2.08 WARRANTY

A. The manufacturer shall provide 12 month parts only warranty. Defective parts will be repaired or replaced during the warranty period at no charge. The warranty period shall commence at start up, or 6 months after shipment, which ever occurs first.

B. The manufacturer will provide extended 48 month parts only warranty on the compressor.

PART 3: EXECUTION

3.01 INSTALLATION

A. Install in accordance with manufacturer's instruction

Technical Data Sheet for CU-1

Job Name: KAFB Bldg 4431 5 of 11 www.DaikinApplied.com

Job Information Technical Data Sheet

Job Name KAFB Bldg 4431 Date 4/7/2022 Submitted By John Munoz Software Version 08.50 Unit Tag CU-1

Unit Overview

Model Number Voltage V/Hz/Phase

Total Refrigeration

Effect Btu/hr

Total Unit Power kW

EER

AHRI

Conditions

IEER

AHRI

Conditions

ASHRAE 90.1

RCS015D 208/60/3 185500 15.2 12.3 13.0 2013 Compliant

Unit Model Number: RCS015D

Type: Applied Approval: ETL - USA

Refrigerant Type: No. of Refrigerant Circuits Refrigerant Weight

R410A 2 16.8 lb

Condensing Section

Temperature Altitude Refrigeration Effect Power Suction Ambient

45.0 °F 95.4 °F 0 ft 185500 Btu/hr 15.2 kW

Compressor

Quantity Type Capacity Control Compressor Isolation

2 Scroll 2 steps Resilient Full Load Current:

Compressor 1 27.6 A Compressor 2 27.6 A

Condenser

Coil Fans Fan Motors Type Number of Rows Fins per Inch Condenser

Fan Type Quantity Full Load Current

Aluminum tube micro channel 1 18 Standard 2 4.20 A

Sound Casing Radiated Sound Power (db)

63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

0 91 88 86 86 81 79 78

Job Name: KAFB Bldg 4431 6 of 11 www.DaikinApplied.com

Physical Dimensions and Weight

Length Height Width Operating Weight

58.0 in 55.5 in 99.0 in 1821 lb Connections

Connection Connection Sizes Suction Line Circuit (2) 1.12 in.

Liquid Line Circuit (2) 0.62 in.

Hot Gas Bypass Circuit (2) 0.88 in.

Electrical

Voltage MROPD Field Power Connection MCA SCCR Field Outlet

Connection 208/60/3 V/Hz/Phase

90 A Single power block 71.9 A 10 kAIC 115V, 20 amp service

Note:

Use only copper supply wires with ampacity based on 75° C conductor rating. Connections to terminals must be made with copper lugs and copper wire.

Options

Isolation Valves Per Circuit: Refrigeration Service Valves Hot Gas Bypass: HGBP Tee (See Accessory Tab)

Condenser Coil Options: Condenser with built in hail protection, Electrofin Coating Electrical

Field Connection Single power block Wiring Options Sealtite conduit GFI Receptacle Field powered

Unit Control

Temperature Controls: No temp control, 115 V transformer Low Ambient Control: Speedtrol, Low ambient control to 0 degrees F

Warranty

Parts: Standard one year parts

Compressor: Extended four year compressor, five year total

AHRI Certification

All equipment is rated and certified in accordance with AHRI 365.

Accessories Optional

Part Number Description

193330721 Hot gas bypass kit, one circuit

193330711 Liquid line kit, replace core filter drier

Job N am e:

Job N um ber:

Draw ings(1) for CU

-1

KAFB Bldg 4431 N

B6KB3

Page

Prepared Date:

w w

DaikinApplied com

4/7/2022

Drawings(1) for CU-1

Product Drawing Unit Tag: CU-1 Sales Office: Mid-South Equipment Sales and Service, LLC

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 08.50

Product: Project Name: KAFB Bldg 4431 Sales Engineer:

Model: RCS015D Apr. 07, 2022 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm] e:

Job N ings(1) for CU

-1

KAFB Bldg 4431 w

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

e:

Job N ings(2) for CU

-1

KAFB Bldg 4431 w

Drawings(2) for CU-1

Product Drawing Unit Tag: CU-1 Sales Office: Mid-South Equipment Sales and Service, LLC

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 08.50

Product: Project Name: KAFB Bldg 4431 Sales Engineer:

Model: RCS015D Apr. 07, 2022 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm] e:

Job N ings(2) for CU

-1

KAFB Bldg 4431 w

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Vision® Air Handling Unit

Page 1 of 5 www.DaikinApplied.com

Job Information Technical Data Sheet

Job Name KAFB Bldg 4431

Date April 11 2022

Submitted By JM

Software Version 12.81

Unit Tag AHU-1

Unit Overview

Model Number

Supply

Air Volume cfm

Static Pressure External Dimensions

External inWc

Total inWc

Height in

Width in

Length in

CAH017GDAC 7779 2.00 3.46 46* 80* 50**

*Not including base rails, coil connectors, drain connectors and control boxes.

**Total lower deck length.

Model Number: CAH017GDAC

Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)

Outer Panel: 24 gauge G90 Galvanized Steel (unpainted)

Liner: 24 gauge Galvanized Steel (unless noted per section)

Insulation: R-13 Injected Foam

Unit Configuration: Stacked / vertical Drive (Handling) Location: Right

Base: 4" formed channel Wall Thickness: 2 in

Altitude: 0 ft Parts Warranty: Standard One Year

Panel Filter Component: 1 Length: 12 in Shipping Section: 1

Type Efficiency Face Velocity Face Area Air Volume Filter Loading

Pre Pleat MERV 13 412 ft/min 18.9 ft² 7779 cfm Side

Air Pressure Drop Number of Filters Height Width Depth Clean Air Mean Air Dirty Air User Spec

0.27 inWc 0.63 inWc 1.00 inWc N/A 6 20 in 24 in 2 in

Door

Location Width Opening

Drive side 8 in Outward http://www.daikinapplied.com/

Page 2 of 5 www.DaikinApplied.com

Direct Expansion Coil Component: 2 Length: 38 in Shipping Section: 1

Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row)

5EJ0804C 199897 Btu/hr 150283 Btu/hr 1 4 8 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure

Drop

Finned Height

Finned Length

Face Area Face Velocity Entering Leaving

Dry Bulb Wet Bulb Dry Bulb Wet Bulb

7779 cfm 73.1 °F 62.3 °F 55.4 °F 53.4 °F 0.70 insWg 36 in 67 in 16.75 ft² 464 ft/min

Fluid Sub-Cooled Refrigerant Liquid Temp.

Suction Vapor Superheat

Temp. at Coil Outlet

Design Saturated Condensing Temp.

Total Refrigerant Weight Suction Temp. Refrigerant

44.0 °F R410a 110.0 °F 8.0 °F 110.0 °F 35.00 lb

Connection [Data Per Coil] Min. Fin Surface Temp.

Min. Tube Wall Surface Temp. Type Liquid [Qty - Size] Suction [Qty - Size] Location Material

OD Sweat 2-0.88 in 2-1.63 in Drive side Copper tube 32.0 °F 32.0 °F

Material Drain Pan Drain Side Fin Tube Header Case

Aluminum .0075 in Copper .020 in Copper Stainless steel Stainless steel Drive side

Total Refrigerant Weight is the total for all circuits of all coils in this coil section and is estimated. Refer to the AHU and Condensing Unit IOMs for recommendations on system start-up.

AHRI 410 Certification

Coil is NOT certified by AHRI Door

Drive side 22 in Outward

Page 3 of 5 www.DaikinApplied.com

Supply Fan Component: 3 Length: 50 in Shipping Section: 2

Fan Performance

Air Volume Static Pressure Fan Energy Index(FEI)

Total Input Power

Fan Shaft Power

Speed Outlet Velocity

External Total Cabinet

Operating Maximum

7779 cfm 2.00 inWc 3.46 inWc 0.13 inWc 1.17 6.0 kW 6.61 BHP 1861 rpm 2858 rpm 1652 ft/min

Fan Data

Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location

Centrifugal DWDI Airfoil / 2 1 19.69 in N/A Up blast CCW To Side of Fan

Motor Data

Power Electrical Supply

Speed Efficiency Enclosure Frame Size Supplier Number of Poles

Lock Rotor Current

Full Load Current

7.5 HP 200/60/3

V/Hz/Phase

1750 rpm Premium ODP 213 T frame Generic 4 162.28 A 23.30 A

Fan Options

Isolator Type: Spring

Drive Package Data*

Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type

1B5V54 BK62H BX47 1 1.14 Standard - L50 (200K)

*Daikin Applied reserves the right to provide a different but equivalent drive package

VFD/Starter/Disconnect Data

Selection Type: VFD Vendor: Daikin Applied

Voltage: 200 V Height x Width x Depth: 12.52 in x 9.15 in x 8.12 in

Mounting: Door Side Enclosure: NEMA 1

VFD Quantity: 1

Door

Drive side 30 in Outward

Unit Sound Power (dB)

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Radiated: 89 84 72 70 63 51 46 51

Unit Discharge: 99 94 90 91 85 79 75 71

Unit Return: 94 88 83 84 78 72 66 59

Page 4 of 5 www.DaikinApplied.com

Shipping Section Details

Section Length in

Weight lb

Corner Weights (lb) Center of Gravity (in)

P1 P2 P3 P4 XX YY ZZ

1 50 880 235 226 205 214 24 39 23

2 50 958 291 206 188 273 24 33 23

Entire Unit

Lower level only n/a

NOTE: Special components aren't included in the corner weights and center of gravity data.

Supply Static Pressure Drop

Component Option Static Pressure Drop

Panel Filter Panel Filter 0.63 insWg

DX Coil DX Coil 0.70 insWg

Supply Fan Cabinet 0.13 insWg

External Static External Static 2.00 insWg

Total Supply Fan Static 3.46 insWg

PFILT

DXC

46 46

FAN

46 46

Elevation View

X Z

Page 5 of 5 www.DaikinApplied.com

Minimum Recommended Drain Pan Trap Dimensions

Shipping Section Component H

1 DX Coil 3.16

Dimensions provided as a courtesy and are recommended minimums only. Daikin is not responsible for supplying or designing drain pan traps and is not responsible for any damage caused by incorrect trap heights. The dimensions listed above should be reviewed and approved by a licensed plumbing professional.

AHRI Certification

Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on AHRI Standards 430/431. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Notes

Standard

1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2007. The approving authority is responsible for compliance of multi - component building systems.

KAFB 4431 REV 0 - SOW etc
_000101 USER-MP Cover-IFC
SOW, SUBMITTALS FORM & rom
MAHG181009
RENOVATE B4431
VECTRUS
KAFB
627 Parade Ln | Bldg. 4431 | KAFB, Biloxi | Mississippi 39534
REV 0 – Issued for Construction
May 20, 2022
MAHG181009 Renovate B4431 SOW IFC
STATEMENT OF WORK
Submittals MAHG181009 Renovate B4431 IFC
Material Submittals Schedule
2022.05.20_Renovate B4431_ROM
ROM
KAFB 4431 REV 0 - Booklet
_000101 USER-MP Cover-50%
BOOKLET
MAHG181009
RENOVATE B4431
VECTRUS
KAFB
627 Parade Ln | Bldg. 4431 | KAFB, Biloxi | Mississippi 39534
REV C – 50% SUBMITTAL
April14, 2022
AHU-1 Building Loads
AHU-1 Condensing Unit
Specification for CU-1
Technical Data Sheet for CU-1
Technical Data Sheet
Job Information
Unit
Options
Warranty
Drawings(1) for CU-1
Drawings(2) for CU-1
KAFB Bldg 4431 AHU-1 - Drawing KAFB Bldg 4431
KAFB Bldg 4431 AHU-1 - Fan Curve KAFB Bldg 4431
KAFB Bldg 4431 AHU-1 - Technical Data Sheet KAFB Bldg 4431