ANG B3500 Chiller As Builts Drawings.pdf
PDF 3 MB Posted
- Attached to
- Repair HVAC/Boiler Bldg 3500 Federal contract opportunity
- Solicitation number
- FA286020R0048
About this file
This solicitation is for repair work at Building 3500 at Joint Base Andrews in Maryland. The Air Force is seeking proposals to replace the HVAC chiller and perform related mechanical work. Offerors must visit the site by the date specified to participate. The selected contractor will be responsible for removal of the existing chiller, installation of a new chiller, and all necessary mechanical, electrical, and control system modifications. The work must be completed within 120 calendar days of the award date. Proposals are due on the date listed in the solicitation document. The Air Force will award a firm-fixed-price contract to the responsible offeror with the lowest price that meets the solicitation's requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation - FA286020R0048 (Revised).pdf | ||
| RFIs (Answered).docx | DOCX document | |
| A70I_33-04-039.PDF | ||
| M2.4.pdf | ||
| P2.2.pdf | ||
| M01.pdf | ||
| M1.5.pdf | ||
| M4.6.pdf | ||
| M6.2.pdf | ||
| RLC-PRC006Q-EN_07102018.pdf | ||
| P0.1.pdf | ||
| M6.1.pdf | ||
| M4.1.pdf | ||
| M2.3.pdf | ||
| M4.6 (1).pdf | ||
| ANGRC HVAC BOILER DIAGRAM.pdf | ||
| M1.12.pdf | ||
| AJXF 20-1547 Repair HVAC Boiler-Bldg 3500 SOW (Revised 2).docx | DOCX document | |
| Solicitation - FA286020R0048.pdf | ||
| AJXF 20-1547 Repair HVAC Boiler-Bldg 3500 SOW (Revised).docx | DOCX document | |
| Base Access Info Requirements.xlsx | XLSX spreadsheet |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR NATIONAL GUARD
READINESS CENTER - CHILLER REPLACEMENT
JOINT BASE ANDREWS BUILDING 3500
MARYLAND
AS-BUILT SUBMISSION
AUGUST 21, 2015
ANG PROJECT NUMBER
AJAX142503
AD
ADJ
AFF
AGGR
ALUM(AL)
APPROX
ARCH
ASPH
ATC
BD
BITUM
BLDG
BLK
BLKG
BM
BMS
BOS
BOTT (BOT)
C
CAB
CB
CEM
CER
CI
CI
CLG
CLKG
CLO
CLR
CMU
CNTR
COL
COMMO
CONC
CONF
CONN
CONSTR
CONT
CORR
CTR
CTSK
DBL
DEFS
DEP
DEPT
DET (DETL)
DF
DFT
DIA
DIM
DISP
DN
DO
DR
DS
DWG
DWR
L
AT
AREA DRAIN
ADJUSTABLE
ABOVE FINISH FLOOR
AGGREGATE
ALUMINUM
APPROXIMATE
ARCHITECTURAL
ASPHALT
ACOUSTICAL
TILE CEILING
BOARD
BITUMINOUS
BUILDING
BLOCK
BLOCKING
BEAM
BALANCED MAGNETIC
SWITCH
BOTTOM OF STEEL
BOTTOM
CENTER LINE
CABINET
CATCH BASIN
CEMENT
CERAMIC
CAST IRON
CONTRACTOR INSTALLED
CEILING
CAULKING
CLOSET
CLEAR
CONCRETE MASONRY UNIT
COUNTER
COLUMN
COMMUNICATION
CONCRETE
CONFERENCE
CONNECTION
CONSTRUCTION
CONTINUOUS
CORRIDOR
CENTER
COUNTERSUNK
DOUBLE
DIRECT APPLIED
EXTERIOR FINISH SYSTEM
DEPRESSION
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DRY FILM THICKNESS
DIAMETER
DIMENSION
DISPENSER
DOWN
DOOR OPENING
DOOR
DOWNSPOUT
DRAWING
DRAWER
E
EA
EJ (EXP JT)
EL
ELEC
ELEV
EMER
ENCL
EP
EQ (EQL)
EQPT
EWC
EXIST
EXP
EXPO
EXT
FA
FACP
FCO
FD
FDN
FE (FEXT)
FEC
FES
FFOW
FH
FHC
FIN (FNSH)
FL
FLASH
FLUOR
FOC
FOF
FOS
FPRF
FR
FS
FTC
FURR
FUT
EAST
EA
EXPANSION JOINT
ELEVATION
ELECTRICAL
ELEVATOR
EMERGENCY
ENCLOSURE
ELECTRICAL PANELBOARD
EQUAL
EQUIPMENT
ELECTRICAL WATER
COOLER
EXISTING
EXPANSION
EXPOSED
EXTERIOR
FIRE ALARM
FIRE ALARM CONTROL
PANEL
FLOOR CLEAN OUT
FLOOR DRAIN
FOUNDATION
EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIRE SURFACE
EXTINGUISHER MOUNTED
FINISH FACE OF WALL
FULL HEIGHT
FIRE HOSE CABINET
FINISH
FLOOR
FLASHING
FLUORESCENT
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIREPROOF
FRONT
FULL SIZE, FLOOR SINK
FOOTING
FURRING
FUTURE
ID
INSUL
INT (INTR)
INTERMED
JAN
JT
KIT
LAB
LAM
LAV
LKR
LP
LT
LVR (L)
MACH
MAINT
MATL
MAX
MC
MECH
MEMB
MET/MTL
MFR (MANUF)
MGR
MH
MIN
MIR
MISC
MK
MO
MTD
MUL
M mm
N
NIC
NO/#
NOM
NTS
OA
OBS (OB)
OC
OD
OD
OFF (OFCE)
OPNG
OPP
OPS
INSIDE DIAMETER
INSULATION
INTERIOR
INTERMEDIATE
JANITOR
JOINT
KITCHEN
LABORATORY
LAMINATE
LAVATORY
LOCKER
LOW POINT
LIGHT
LOUVER
MACHINE
MAINTENANCE
MATERIAL
MAXIMUM
MEDICINE CABINET
MECHANICAL
MEMBRANE
METAL
MANUFACTURER
MANAGER
MANHOLE
MINIMUM OR MINUTES
MIRROR
MISCELLANEOUS
MARK
MASONRY OPENING
MOUNTED
MULLION
METER (METRIC)
MILLIMETER (METRIC)
NORTH
NOT IN CONTRACT
NUMBER
NOMINAL
NOT TO SCALE
OVERALL
OBSCURE
ON CENTER
OUTSIDE DIMENSION
(OUTSIDE DIAMETER)
OVERFLOW DRAIN
OFF (OFCE)
OPENING
OPPOSITE
OPERATIONS
PD
PL
PLAM
PLAS
PLYWD
PM
POP
PR
PRCST
PT
PTD
PTD/R
PTI
PTN
PTR
PVC
QT
R
RAD
RATG
RD
REF
REFR
REINF
RBP
REC
REQ (REQD)
RF
RGTR
RM
RO
RWD
RWL
S
SATC
SC
SCD
SCHED
SCN
SD
SEC
SECT
SH
SHR
SHT
SIM
SND
SNR
SP
SPEC
PIT DRAIN
PLATE
PLASTIC LAMINATE
PLASTER
PLYWOOD
PRESSED METAL FRAMES OR
(PROJECT MANAGER)
POINT OF PRESENCE
PAIR
PRE-CAST
POINT
PAINTED OR (PAPER TOWEL DISPENSER)
PAPER TOWEL DISPENSER
&WASTE RECEPTACLE
PROPERTY TURN IN
PARTITION
PAPER TOWEL RECEPTACLE
POLYVINYL CHLORIDE
QUARRY TILE
RISER
RADIUS
RATING
ROOF DRAIN
REFERENCE
REFRIGERATOR
REINFORCED
REINFORCED BRICK PANEL
RECESSED
REQUIRED
RADIO FREQUENCY
REGISTER
ROOM
ROUGH OPENING
REDWOOD
RAIN WATER LEADER
SOUTH
SUSPENDED ACOUSTICAL TILE CEILING
SOLID CORE
SEAT COVER DISPENSER
SCHEDULE
SCREEN
SOAP DISPENSER, STORM DRAIN
SECRETARIES
SECTION
SHELF
SHOWER
SHEET
SIMILAR
SANITARY NAPKIN DISPENSER
SANITARY NAPKIN RECEPTACLE
SPACE
SPECIFICATION
SQ
SSK (SS)
SST
STA
STD
STL
STOR
STRL (STRUCT)
SUSP
SYM (SYMM)
SYST
T&G
TB
TBD
TC
TEL
TER
THK
T.O.
TOC
TOS
TP
TPD
TRD(T)
TV
TW
TYP
UNF (UNFIN)
UON
UPS
UR
VCT
VERT
VEST
VIF
VSC
VTR
W/ W/O W
WC
WD
WH
WP
WNSCT
WR
WT
SQUARE
SERVICE SINK
STAINLESS STEEL
STATION
STANDARD
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SYMMETRICAL
SYSTEM
TONGUE AND GROOVE
TOWEL BAR
TO BE DETERMINED
TOP OF CURB
TELEPHONE
TERRAZZO
THICK
TOP OF
TOP OF CONCRETE
TOP OF STEEL
TOP OF PAVEMENT
TOILET PAPER DISPENSER
TREAD
TELEVISION
TOP OF WALL
TYPICAL
UNFINISHED
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
URINAL
VINYL COMPOSITION TILE
VERTICAL
VESTIBULE
VERIFY IN FIELD
VERTICAL SLIDE CLIP
VENT THRU ROOF
WITH
WITHOUT
WEST (WIDTH)
WATER CLOSET
WOOD
WATER HOSE OR (WALL HYDRANT)
WATERPROOF
WAINSCOT
WATER RESISTANT
WEIGHT
ABBREVIATIONS CODE ANALYSIS
PROJECT NAME: ANG REPAIR B3500 CHILLER, ANG PROJECT # AJAX142503
LOCATION: HQ ANG COMMAND POST
BUILDING 3500 NORTH EAST ADDITION
JOINT BASE ANDREWS, MARYLAND
CODES: IBC 2009, IFC, IPC, IMC, IECC, NFPA 101 2009
NFPA 70 (NEC), ANG ETL 01-1-1
SHEET LIST
LOCATION MAP
PROJECT
SITE
SHEET GENERAL PRE-FINAL
G-001 COVER SHEET
G-002 GENERAL NOTES
MECHANICAL
M-001 MECHANICAL GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
M-101 MECHANICAL DEMO NEW AND TEMPORARY WORK PLANS (PHASE 1)
M-102 MECHANICAL DEMOLITION AND NEW WORK PLANS (PHASE 2)
M-401 MECHANICAL ENLARGED PLANS AND CHILLED WATER DIAGRAMS
M-501 MECHANICAL DETAILS & CONTROLS
ELECTRICAL
E-001 ELECTRICAL NOTES, SYMBOLS AND LEGENDS
E-100 ELECTRICAL SITE PLAN
E-200 ELECTRICAL EXISTING AND NEW WORK PLAN
E-300 ELECTRICAL DEMO AND NEW POWER WORK
GALV
GB
GFCI
GFE
GL
GND
GR
GYP
GYP BD
HB
HC
HDWD
HDW (HW)
HM
HMI
HORIZ
HP
HR
HT (HGT) (H)
GALVANIZED
GRAB BAR
GOVERNMENT FURNISHED/
CONTRACTOR INSTALLED
GOVERNMENT FURNISHED EQUIPMENT
GLASS
GROUND
GRADE
GYPSUM
GYPSUM WALLBOARD
HOSE BIB
HOLLOW CORE
HARDWOOD
HARDWARE
HOLLOW METAL
HOLLOW METAL INSULATED
HORIZONTAL
HIGH POINT
HOUR
HEIGHT
V
T
S
1. REFER TO SPECIFICATIONS FOR TRACER CABLE CAPACITY
2. PROVIDE HEAT TRACING FOR ALL CHS, CHR, & D PIPING
HEAT TRACING
NOTES:
INSULATION
VALVE
VALVE BODY AS RECOMMENDED BY TRACER MFGR
PIPE
FORM LOOP & WRAP HEAT TRACING AROUND
PIPE SECTION
PIPE
HEATING CABLE
INSULATION
ALUMINUM JACKET
LINING
2" INSULATION
PIPE
DISCONNECT SWITCH IN NEMA 4 ENCL.
LEAD TO POWER SOURE
LEAD TO
OTHER PIPE
POWER JUNCTION BOX MOUNTED ON PIPE
DUAL CONDUCTOR CABLE COLD LEAD
HOT TO COLD LEAD JUNCTION
THERMOSTAT MOUNTED
ON PIPE
SENSING BULB IN
PIPE WELL PROVIDE
WELL IN PIPE
PROVIDE RUBBER SHIELD
BETWEEN PIPE & CLAMP OF
DISSIMILAR METAL.
VERTICAL CHANNEL,
SECURE TO FLOOR
BELOW
TUBING CLAMP
PROVIDE SADDLES FOR
INSULATED PIPING.
"B-LINE" B62 STEEL CHANNEL
12" ABOVE FLOOR, 12" BELOW
CEILING AND AT MIDPOINT.
BOLT TO VERTICAL CHANNELS.
DRAIN ALL LOW POINTS AS INDICATED ABOVE.
ELEVATION
WELDED PIPINGTHREADED PIPING
ELEVATION
NOTES:
PROVIDE HOSE CAP NUT
ADAPTER TO 20 MM (3/4") HOSE THREAD.
3/4" (20 MM) BALL VALVE
REDUCER, IF REQUIRED
TYPICAL WATER PIPING
LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
WATER PIPING
6" MIN.
3/4" BALL VALVE
PRESSURE SNUBBER
REDUCING BUSHING
PRESSURE GAUGE
WATER PIPE
THREADOLET
NOTE: FOR PIPES 2" AND SMALLER, USE FITTING
INSTEAD OF THREADOLET OR WELDOLET.
HOUSEKEEPING PAD
CONCRETE
CONNECTION
FLANGED
(TYP.)
AIR COOLED CHILLER
FLOW SWITCH
BALANCING VALVE
(TYP.)
RESTRAINED
SPRING
ISOLATOR
FLEXIBLE CONNECTION (TYP.)
1. HEAT TRACE CABLE SHALL BE SELF REGULATING
HEAT TRACE
CONTROL PANEL HEAT TRACE
NOTES:
A. TEMPERATURE SETPOINTS AND SCHEDULES SHALL BE FULLY
ADJUSTABLE THROUGH THE EXISTING BAS SOFTWARE.
B. EXISTING BAS SHALL SEQUENCE NEW CHILLER ON AS REQUIRED TO
MEET COOLING LOAD. CHILLER SHALL OPERATE UNDER PACKAGED
CONTROLS TO MAINTAIN 38°F DISCHARGE TEMPERATURE.
C. EXISTING PRIMARY CHILLED WATER PUMP (P-1.1, P-1.2) SHALL
CIRCULATE CHILLED WATER.
D. EXISTING BYPASS VALVE V-2 SHALL MODULATE AS REQUIRED TO
MAINTAIN 38°F CHS.
E. CHILLER SHALL BE DEACTIVATED WHEN (E) BAS SIGNALS THAT
MECHANICAL COOLING IS NOT REQUIRED.
F. CHILLER SHALL SEND ALARM TO (E) BAS TO INDICATE IF CHILLER IS
COMMANDED "ON" BUT A NO-FLOW CONDITION IS DETECTED.
CHILLER OPERATION
1. NEW CHILLER SEQUENCE OF OPERATION SHALL MATCH EXISTING
"CHILLER ONLY MODE" SEQUENCE OF OPERATION. PROVIDE SIMILAR
INPUTS/OUTPUTS TO AND FROM (E) BAS. REFER TO SPEC. SECTION 230993.
2. NEW CHILLER CONTROLLER SHALL HAVE FULL COMMUNICATION WITH (E) BAS.
CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROL EQUIPMENT,
ACCESSORIES, AND WIRING, AS REQUIRED.
3. RE-USE EXISTING CONTROLS INTERFACE (INCLUDING CONTROL CONDUIT) TO
CONNECT NEW CHILLER TO EXISTING EQUIPMENT.
4. THE CONTROL POINTS SHOWN DO NOT REPRESENT THE EXACT NUMBERS OR
TYPES OF POINTS REQUIRED. PROVIDE SUFFICIENT NUMBER OF POINTS FOR
EACH TYPE (AI, AO, DI, DO) TO ENABLE THE BAS TO EXECUTE THE SEQUENCES OF
OPERATION.
NOTES
CHILLER
VFD
CHILLER
CONTROLLER
TO CHILLER CONTROLLER
INTERFACE
WITH BAS
A1
1A
B
A
SECONDARY PUMP OPERATION:
1. WHEN EMCS CALLS FOR MECHANICAL COOLING,
ACTIVATE LEAD CHILLED WATER PUMP.
2. ON A FURTHER CALL FOR COOLING, ACTIVATE
LAG CHILLED WATER PUMP SO THAT BOTH PUMPS
RUN SIMULTANEOUSLY.
3. MODULATE PUMPS UNDER VFD CONTROL TO
MAINTAIN A CONSTANT DIFFERENTIAL PRESSURE
AS SENSED BY PUMP DIFFERENTIAL PRESSURE
SENSORS.
4. DURING LEAD/LAG OPERATION, IF THE LEAD PUMP
FAILS AS SENSED BY DIFFERENTIAL PRESSURE
SENSOR, AN ALARM SHALL BE SIGNALED TO THE
EMCS AND THE LAG PUMP SHALL BE ACTIVATED
AFTER A 15 SECOND DELAY.
5. DURING SIMULTANEOUS OPERATION, AN ALARM
SHALL BE SIGNALED TO THE EMCS.
6. EMCS SHALL ALTERNATE THE LEAD/LAG
ASSIGNMENT EVERY WEEK, ADJUSTABLE.
7. PUMP DIFFERENTIAL PRESSURE VALVE SHALL BE
SET FOR DIFFERENTIAL PRESSURE OF 5'
GREATER THAN PUMP DESIGN HEAD AND 150
GPM.
(FA A/V DEVICE
9'-6" MAX
MIN.
PUSH BUTTON
FIRE FIGHTER'S TELEPHONE
GENERAL ABBREVIATIONS
TYPICAL DEVICE MOUNTING HEIGHT DETAIL
RECEPTACLES
TELEPHONE/DATA OUTLETS
FIRE ALARM PULL STATION
1'-6"
7'-6"
6'-8"
4'-0"
EQUIPMENT LEGEND
( REFER TO LIGHTING FIXTURE SCHEDULE FOR MORE INFORMATION )
WIRING DEVICE LEGENDLIGHTING EQUIPMENT LEGEND
ELECTRICAL LEGEND
OR MASS
NOTIFICATION)
RECESSED FLUORESCENT LIGHT FIXTURE
RECESSED FLUORESCENT LIGHT FIXTURE
ON EMERGENCY CIRCUIT
DIRECT/INDIRECT RECESSED
FLUORESCENT FIXTURE
DIRECT/INDIRECT RECESSED FLUORESCENT
FIXTURE ON EMERGENCY CIRCUIT
PENDANT MOUNTED LIGHT FIXTURE
PENDANT MOUNTED LIGHT FIXTURE ON
EMERGENCY CIRCUIT
SURFACE MOUNTED FLUORESCENT
LIGHT FIXTURE EMERGENCY
SURFACE MOUNTED FLUORESCENT
LIGHT FIXTURE
FLUORESCENT STRIP LIGHT, SEE LIGHTING FIXTURE SCHEDULE FOR
INFORMATION
FLUORESCENT STRIP LIGHT ON EMERGENCY CIRCUIT
INCANDESCENT / FLUORESCENT / HID DOWNLIGHT, SEE LIGHTING FIXTURE
SCHEDULE FOR INFORMATION
INCANDESCENT / FLUORESCENT / HID DOWNLIGHT ON EMERGENCY CIRCUIT
WALL MOUNTED HID / INCANDESCENT / FLUORESCENT LIGHT FIXTURE, SEE
LIGHTING FIXTURE SCHEDULE FOR INFORMATION
WALL MOUNTED HID / INCANDESCENT / FLUORESCENT LIGHT FIXTURE ON
EMERGENCY CIRCUIT
WALL WASHER FIXTURE, SEE LIGHTING FIXTURE SCHEDULE FOR
INFORMATION, AIM TOWARD OPEN END OR ARROW
EXIT SIGN, CEILING OR WALL MOUNTED, PROVIDE DIRECTIONAL ARROWS AS
INDICATED. SHADED AREAS INDICATE NUMBER OF FACES.
FLOOD LIGHT, SEE LIGHTING FIXTURE SCHEDULE FOR INFORMATION
SITE LIGHTING FIXTURE, SEE LIGHTING FIXTURE SCHEDULE FOR
INFORMATION
SITE LIGHTING DECORATIVE POLE OR BOLLARD. HATCHING INDICATES
HOUSE SIDE SHIELD LOCATION
DECORATIVE, PENDANT AND LIGHT FIXTURE
WALL MOUNTED FLUORESCENT LIGHT FIXTURE
WALL MOUNTED FLUORESCENT LIGHT FIXTURE ON EMERGENCY CIRCUIT
WALL MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE ON EMERGENCY CIRCUIT
FLUORESCENT STRIP LIGHT,
WALL MOUNTED COVE OR UNDERCOUNTER LIGHT FIXTURE REFER TO
TRACK LIGHTING
SINGLE POLE SWITCH, 20A, 120/277V, "a" DENOTES SWITCH CONTROL
KEY OPERATED SWITCH PROVIDED BY COILING DOOR MANUFACTURER
DOUBLE POLE SWITCH, 20A, 120/277V
THREE-WAY SWITCH, 20A, 120/277V
FOUR-WAY SWITCH, 20A, 120/277V
DIMMER SWITCH, REFER TO SPECIFICATIONS FOR DETAILS.
PROGRAMMABLE 277V, FLUORESCENT.
THREE-WAY DIMMER SWITCH, 1500VA
WEATHERPROOF SWITCH, 20A, 120/277V
SINGLE POLE SWITCH WITH PILOT LAMP, 20A, 120/277V
SINGLE POLE TOGGLE SWITCH WITH INTEGRAL VACANCY SENSOR. 20A,
120/277V.
CEILING MOUNTED OCCUPANCY SENSOR, REFER TO LIGHTING CONTROL
SPECS. US INDICATES ULTRASONIC, DT INDICATES DUAL TECHNOLOGY.
DUPLEX RECEPTACLE, NEMA 5-20R, 125 VOLT, 2 POLE, 3 WIRE, 20 AMP "WP"
INDICATES WEATHERPROOF TYPE, "CP" INDICATES CHILD PROOF TYPE
QUADRUPLEX RECEPTACLE, NEMA 5-20R, 125 VOLT, 2 POLE, 3 WIRE, 20 AMP
DUPLEX RECEPTACLE, "GFI" (GROUND FAULT INTERRUPTER) TYPE, "WP"
INDICATES WEATHERPROOF TYPE, 125 VOLT, 2 POLE, 3 WIRE, 20 AMP, 5-20R
"CP" INDICATES CHILD PROOF FACEPLATE
DUPLEX RECEPTACLE MOUNTED ON THE CEILING FOR PROJECTORS WHERE
LABELED "C", ON THE WALL AT MOUNTING HEIGHT SPECIFIED BY THE AV
DRAWINGS WHERE INDICATED WITH "LCD". 125 VOLT, 2 POLE, 3 WIRE, 20 AMP,
NEMA 5-20R.
SPECIAL RECEPTACLE. NEMA 14-30R, 30A, 208/120V, 3W, +18" AFF U.O.N.
PROVIDE WITH 4#10 AWG AND 1#10AWG GND IN 3/4" C. "WP" INDICATES
WEATHER PROOF TYPE
IF INDICATED REPRESENTS, NEMA 18-30R, 30A, 208, 4W, +18" AFF U.O.N.
PROVIDE WITH 4#10 AWG AND 1#10AWG GND IN 3/4" C.
SURFACE MOUNTED FLOOR BOX W/120 V DUPLEX RECEPTACLE NEMA 5-20R
PROVIDE TWIST LOCK WHERE INDICATED
SURFACE MOUNTED QUADRUPLEX RECEPTACLE ON FLOOR/TROUGH AS
INDICATED NEMA 5-20R, 125 VOLT, 2 POLE, 3 WIRE, 20 AMP. PROVIDE TWIST
LOCK WHERE INDICATED
SURFACE MOUNTED SPECIAL RECEPTACLE - FLOOR/TROUGH MOUNTED, NEMA
L6-30R, 208V, 2 POLE, 3 WIRE, 30A TWISTLOCK
TELEPHONE OUTLET WITH PULL WIRES THROUGH 3/4" EMPTY CONDUIT OUT TO
ACCESSIBLE CEILING U.O.N. STUB 4" INTO ACCESSIBLE CEILING SPACE
DATA OUTLET WITH PULL WIRES THROUGH 3/4" EMPTY CONDUIT OUT TO
ACCESSIBLE CEILING U.O.N. STUB 4" INTO ACCESSIBLE CEILING SPACE
COMBINATION OF TELE./DATA OUTLET WITH PULL WIRES THROUGH 3/4" EMPTY
CONDUIT OUT TO ACCESSIBLE CEILING U.O.N. STUB 4" INTO ACCESSIBLE
CEILING SPACE.
FLOOR RECESS MOUNTED TELEPHONE OUTLET WITH PULL WIRES THROUGH
FLOOR POKE THRU RECESS MOUNTED OUTLET TYPE AMD8 WITH DATA, BRASS
TRIM FLANGE AND BRASS FACEPLATE
FLOOR RECESS MOUNTED COMBINATION OF TELE./DATA OUTLETS WITH PULL
WIRES
FLOOR MOUNTED JUNCTION BOX
TRANSITION BOX FOR FURNITURE FEED FROM MODULAR WIRING.
FLUSH FLOOR OUTLET BOX.
TELECOMMUNICATION PLYWOOD BASEBOARD, 4' X 8' X 3/4" U.O.N.
SHEET NOTE DESIGNATION
FEEDER SIZE DESIGNATION
SITE DISTRIBUTION FEEDER NOTE
SINGLE LINE DIAGRAM - FEEDER CONTINUATION DESIGNATION, TOP NUMBER
INDICATES CONTINUATION LETTER, BOTTOM LETTER INDICATES DRAWING
NUMBER
FLOOR PLANS - DETAIL DESIGNATION, TOP NUMBER INDICATES DETAIL
NUMBER, BOTTOM LETTER INDICATES DRAWING NUMBER
SECTION OR ELEVATION DESIGNATION, TOP NUMBER INDICATES SECTION
NUMBER, BOTTOM LETTER INDICATES DRAWING NUMBER
PRESET DIMMER CONTROL STATION, MOUNT +48" AFF
REMOTE CONTROL DIMMING STATION, MOUNT +48" AFF, REFER TO SPECS FOR
DESCRIPTION OF EACH DEVICE.
SHADE CONTROL SWITCH
DIMMING SYSTEM A/V INTERFACE
CEILING MOUNTED DIMMING SYSTEM IR PARTITION CONTROL
PHOTO RELAY
LOW VOLTAGE LIGHTING CONTROL OVERRIDE SWITCH. A1 INDICATES
CORRESPONDING RELAY PANEL & MANUAL SWITCH NUMBER.
CEILING MOUNTED DAYLIGHT SENSOR
DIMMING SYSTEM POWER BOOSTER
TV OUTLET. PROVIDE 3/4" CONDUIT WITH PULL STRING FROM BOX TO
ACCESSIBLE CEILING. STUB 4" INTO ACCESSIBLE CEILING
PLUGMOLD. REFER TO PLANS FOR DETAILS
COORDINATE WALL MTD
FIXTURE MOUNTING
HEIGHT WITH
ARCHITECTURAL
ELEVATIONS AND RCP
FIRE ALARM AUDIO/VISUAL
DEVICES
SWITCHES/DIMMERS
NOTES:
1. DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE
WHEREVER POSSIBLE.
2. ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON
THIS DETAIL UNLESS OTHERWISE NOTED.
NON-FUSED DISCONNECT SWITCH, NUMBERS INDICATE POLE AND AMPERE
RATING, NEMA 1 ENCLOSURE U.O.N. 3R INDICATES NEMA ENCLOSURE IF
OTHER THAN TYPE 1
FUSED DISCONNECT SWITCH, NUMBERS INDICATES POLES, AMPERE RATING
AND FUSE SIZE, "*" INDICATES FUSE SIZE ACCORDING TO EQUIPMENT
MANUFACTURER RECOMMENDATION, NEMA 1 ENCLOSURE U.O.N. 3R
INDICATES NEMA ENCLOSURE IF OTHER THAN TYPE 1
DISCONNECT SWITCH, PROVIDED INTEGRAL WITH EQUIPMENT
MAGNETIC MOTOR STARTER, TYPE IN ACCORDANCE WITH NEMA, IEEE, AND
ANSI "3" INDICATES NEMA SIZE. NEMA 1 ENCLOSURE U.O.N. 3R INDICATES
NEMA ENCLOSURE IF OTHER THAN TYPE 1
COMBINATION OF MAGNETIC MOTOR STARTER AND FUSED DISCONNECT
SWITCH "3" INDICATES NEMA SIZE. SEE FUSED DISCONNECT FOR
DISCONNECT RATING DESIGNATION. NEMA 1 ENCLOSURE U.O.N. 3R
INDICATES NEMA ENCLOSURE IF OTHER THAN TYPE 1
ENCLOSED CIRCUIT BREAKER, NUMBERS INDICATE POLES AND AMPERE
RATING, NEMA 1 ENCLOSURE U.O.N. "ST" INDICATES SHUNT TRIP
SOLID STATE MOTOR STARTER W/ FUSED DISCONNECT SWITCH. NUMBERS
INDICATE POLES/FRAME SIZE/FUSE SIZE
MANUAL MOTOR STARTER, SINGLE PHASE WITH THERMAL OVERLOAD
PROTECTORS, "MP" INDICATES WITH PILOT LAMP
MOTOR INDICATION, NUMBER INDICATES HORSE POWER RATING
CEILING MOUNTED JUNCTION BOX
WALL FLUSH/SURFACE MOUNTED JUNCTION BOX MOUNTED +18" AFF UON
CONNECTION TO MOTORIZED DAMPER
JUNCTION BOX MOUNTED ABOVE CEILING FOR POWER CONNECTION TO
MOTORIZED SCREEN
JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT
JUNCTION BOX MOUNTED ABOVE CEILING FOR HANDICAPPED DOOR OPENER
JUNCTION BOX FOR HEAT TRACE ON PIPING BY DIVISION 22/23. LOCATE IN
CLOSE PROXIMITY TO MECHANICAL SYSTEM PIPING IN THE LOCATION
SHOWN
DRY TYPE TRANSFORMER, REFER TO DRY TYPE TRANSFORMER SCHEDULE
FOR DESCRIPTION
120/208 VOLT PANEL
FLUSH MOUNTED 120/208V PANEL
277/480 VOLT PANEL
JUNCTION BOX WITH FINAL CONNECTION FOR SMOKE VAV CONTROL.
HVAC CONTROL PANEL
MOTOR CONTROL CENTER
VARIABLE FREQUENCY DRIVE
TIME CLOCK SWITCH
CONTACTOR
EMERGENCY POWER OFF PUSH BUTTON
MECHANICAL EQUIPMENT TAG. REFER TO MECHANICAL EQUIPMENT
SCHEDULE FOR CIRCUIT, WIRING, STARTER AND DISCONNECT SIZES.
UNIT HEATER
TYPICAL DIMENSION CALL OUT FOR MOUNTING HEIGHT ON CENTER ABOVE
FINISHED FLOOR
EMERGENCY CALL STATION PROVIDED BY SECURITY CONTRACTOR
WATER HEATER
MOTORIZED PROJECTION SCREEN MOTOR.
MOTORIZED SHADE MOTOR.
KITCHEN EQUIPMENT CONNECTION TAG
ADA DOOR NOTIFICATION DOORBELL. MOUNT TIGHT TO CEILING.
WALL MOUNTED ADA DOOR NOTIFICATION STROBE. MOUNT +80" AFF.
EXHAUST FAN BY DIVISION 15 WITH INTEGRAL LIGHT FIXTURE
GARBAGE DISPOSAL
CCTV CAMERA. RACEWAY AND BOXES ONLY. EQUIPMENT BY OTHERS.
CARD READER. RACEWAY AND BOXES ONLY. EQUIPMENT BY OTHERS.
INTERCOM. RACEWAY AND BOXES ONLY. EQUIPMENT BY OTHERS.
ELECTRIC DIGITAL METER
UNDERVOLTAGE RELAY
COMBINATION INSTANTANEOUS OR INVERSE TIME OVERCURRENT RELAY
NEUTRAL INVERSE TIME RELAY
GROUND FAULT RELAY
OVERVOLTAGE RELAY
FREQUENCY RELAY
TRANSFER RELAY
LOCKOUT RELAY
DIESEL GENERATOR U.O.N.
MOLDED CASE CIRCUIT BREAKER, TOP NUMBER INDICATES AMPERE FRAME
RATING, BOTTOM NUMBER INDICATES AMPERE TRIP RATING. NUMBER IN
PARENTHESIS INDICATES THE CIRCUIT BREAKER TAG.
CURRENT TRANSFORMER. NUMBERS INDICATE PRIMARY AND SECONDARY
RATING
VOLTAGE TRANSFORMER (NUMBER INDICATES QUANTITY)
POWER TRANSFORMER WITH SIZE AND RATING AS INDICATED ON PLAN
AUTOMATIC TRANSFER SWITCH (ATS), SIZE AND RATING AS INDICATED ON
PLAN
SWITCH AND FUSE. "AS" INDICATES SWITCH SIZE, "AF" INDICATES FUSE SIZE
CONTACTOR NUMERAL DENOTES NEMA SIZE
THERMAL OVERLOAD
SINGLE PHASE FRACTIONAL HP MOTOR STARTER WITH THERMAL OVERLOAD
LIGHTNING ARRESTOR AND GROUNDING
MAGNETIC MOTOR STARTER WITH THERMAL OVERLOAD RELAY IN EACH
UNGROUNDED CONDUCTOR, FULL VOLTAGE, NON-REVERSING NUMERAL
DENOTES NEMA SIZE. "RA" DENOTES REDUCED VOLTAGE
AUTOTRANSFORMER CLOSED TRANSITION TYPE. "RY" DENOTES REDUCED
VOLTAGE STAR-DELTA TYPE. "PB" AND "HOA" DENOTE PUSH-BUTTON AND
HAND-OFF-AUTOMATIC CONTROL IN STARTER COVE RESPECTIVELY
CONTROL TRANSFORMER
OVERLOAD CONTACT
GROUND FAULT SENSOR AND RELAY
N/O RELAY OR CONTACTOR CONTACT
N/C RELAY OR CONTACTOR CONTACT
INDICATING LIGHT, "R" INDICATES RED, "G" INDICATES GREEN, "A" INDICATES
AMBER
MOMENTARY START PUSH-BUTTON SWITCH
MOMENTARY STOP PUSH-BUTTON SWITCH
HAND-OFF-AUTO SELECTOR SWITCH
HIGH VOLTAGE CABLE TERMINATION
HIGH VOLTAGE ISOLATING SWITCH
HIGH VOLTAGE LOAD BREAK SWITCH
DRAW-OUT CIRCUIT BREAKER, "AF" INDICATES FRAME SIZE, "AT" INDICATES
TRIP SETTING
HIGH VOLTAGE DRAW-OUT VACUUM CIRCUIT BREAKER
HIGH VOLTAGE DISTRIBUTION TRANSFORMER
MAIN-TIE-MAIN LOGIC CONTROLLER
LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER
LOW VOLTAGE DISCONNECT SWITCH
LOW VOLTAGE GROUND FAULT INTERRUPTER
PROGRAMMABLE LOGIC CONTROLLER
TRANSFORMER OR PAD MOUNTED EQUIPMENT
TRANSIENT VOLTAGE SURGE SUPPRESSOR, NUMBER INDICATES MINIMUM
PER PHASE SURGE CAPACITY
BLOWN FUSE DETECTION AND TRIP
STATIC TRANSFER SWITCH
SINGLE PHASE DETECTION AND OPERATOR (FOR BLOWN FUSE)
KIRK KEY INTERLOCK
AMPERES
ABOVE COUNTER HEIGHT
ACCESS CONTROL PANEL
AUTONOMOUS CONTROL UNIT
AMERICANS WITH DISABILITIES
AMP FRAME
ABOVE FINISHED CEILING
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
ABOVE PIT FLOOR
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMERICAN NATIONAL STANDARDS
INSTITUTE
AREA OF RESCUE ASSISTANCE
ARCHITECT
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC TEMPERATURE
CONTROL
AMERICAN WIRE GAUGE
BUILDING AUTOMATION SYSTEM
BELOW FINISH CEILING
BELOW FINISH GRADE
BUILDING
CONDUIT
CATALOG
CABLE ACCESS TELEVISION
CIRCUIT BREAKER
CERTIFIED BALLASTS
MANUFACTURERS
COMPACT FLUORESCENT
CIRCUIT
CENTERLINE
CURRENT LIMITING FUSE
COLUMN
CONTROL POWER TRANSFORMER
CARD READER
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COPPER
DIRECT BURIED
DIAMETER
DRAWING
ENCASED BURIED
EMPTY CONDUIT
EXHAUST FAN
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICALLY OPERATED
EMERGENCY POWER OFF
EQUIPPED SPACE
EMERGENCY TRANSFER DEVICE
ELECTRIC WATER COOLER
EXISTING TO REMAIN
FAN COIL UNIT
FULL LOAD AMPERES
FLUORESCENT
FLEXIBLE METAL CONDUIT
FEET
FULL VOLTAGE NON REVERSING
GROUND FAULT INTERRUPTER
GROUND FAULT RELAY
GROUND OR GROUNDING
GALVANIZED RIGID METALLIC
CONDUIT
HANDICAPPED
HANDHOLE
HAND, OFF, AUTOMATIC SWITCH
IN ACCORDANCE WITH
INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INTERLOCK OR INTERIORS
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT AMPERES
A
ACH
ACP
ACU
ADA
AF
AFC
AFF
AFG
APF
AHJ
AHU
AIC
AL
ANSI
ARA
ARCH
AT
ATS
ATC
AWG
BAS
BFC
BFG
BLDG
C
CAT
CATV
CB
CBM
CF
CKT
CL
CLF
COL
CPT
CR
CRI
CT
CU
DB
DIA
DWG
EB
EC
EF
ELEV
EM
EMT
E.O.
EPO
ES
ETD
EWC
(EX)
FCU
FLA
FLUOR
FMC
FT
FVNR
GFI
GFR
GND,G
GRMC
HC
HH
HOA
IAW
IEEE
IG
IMC
INT
JBOX
KCMIL
KVA
KILOWATTS
LIQUID CRYSTAL DISPLAY
LEAK DETECTION CONTROLLER
LIGHT EMITTING DIODE
LIGHTING
LIQUIDTIGHT FLEXIBLE METAL
CONDUIT
MAGNETIC STARTER
MANUAL STARTER
METAL CLAD CABLE
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION FRAME
MANUFACTURER
MANHOLE
MISCELLANEOUS
MAIN LUGS ONLY
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NATIONAL ELECTRICAL
MANUFACTURES ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NON FUSED NORMALLY OPEN OR
NUMBER
NOT TO SCALE
ON CENTER
POLE
PUSHBUTTON
POWER DISTRIBUTION UNIT
PHASE
PROGRAMMABLE LOGIC
CONTROLLER
POWER MONITORING AND CONTROL
SYSTEM
PANEL
PROVIDED UNDER OTHER SECTIONS
POLYVINYL CHLORIDE
POWER
QUANTITY
REMOTE DISTRIBUTION CABINET
REQUIRED
ROOM
RIGID METAL CONDUIT
ROOT MEAN SQUARED
RIGID NON-METALLIC CONDUIT
ROOF TOP UNIT
SCHEDULE
SPARE
SOFT STARTER
SUB SYSTEM GROUND BUS
SHUNT TRIP
STATIC TRANSFER SWITCH
SWITCH
SYMMETRICAL
TELEPHONE
TELEPHONE GROUND BUS
TOTAL HARMONIC DISTORTION
THERMAL MAGNETIC CIRCUIT
BREAKER
TELECOMMUNICATIONS MAIN
GROUND BUS TRANSPONDER
TWISTED SHIELDED PAIR
TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYPICAL
UNDERGROUND OR UNDERGRADE
UNIT HEATER
UNDERWRITERS LABORATORIES
UNLESS OTHERWISE NOTED (OR AS
UON)
UNINTERRUPTIBLE POWER SUPPLY
ULTRAVIOLET
VOLT
VARIABLE FREQUENCY DRIVE
VOLTAGE TRANSFORMER
WIRE
WATER HEATER
WEATHER PROOF
TRANSFORMER
KW
LCD
LDC
LED
LTG
LFMC
MAG
MAN
MC
MCB
MCC
MCP
MDF
MFR
MH
MISC
MLO
NC
NEC
NEMA
NFPA
NF NO
NTS
OC
P
PB
PDU
PH
PLC
PMCS
PNL
POS
PVC
PWR
QTY
RDC
REQ'D
RM
RMC
RMS
RNMC
RTU
SCH
SP
SS
SSGB
ST
STS
SW
SYM
TEL,TELE
TGB
THD
TMCB
TMGB
TRSP
TSP
TVSS
TYP
UG
UH
UL
U.O.N.
UPS
UV
V
VFD
VT
W
WH
WP
XFMR
CIRCUITRY, RACEWAYS AND FEEDERS LEGEND
CONDUIT WITH WIRING TURNED UP
CONDUIT WITH WIRING TURNED DOWN
CONDUIT WITH CAPPED
CONDUIT WITH WIRING CONCEALED IN SLAB, CEILING OR WALL
CONDUIT WITH WIRING BELOW GRADE
CIRCUIT HOMERUN TO PANEL. ARROWS INDICATE NUMBER OF CIRCUITS,
HATCH MARKS INDICATE NUMBER OF CONDUCTORS NUMBER ADJACENT TO
HATCH MARKS INDICATES WIRE SIZE IF LARGER THAN #12, LETTERS
INDICATES NAME OF PANEL AND NUMBER INDICATES ASSOCIATED CIRCUIT
BREAKER. PROVIDE EQUIPMENT GROUNDING CONDUCTOR FOR ALL BRANCH
CIRCUITS. EQUIPMENT GROUND CONDUCTOR IS NOT INCLUDED IN TICK
MARKS. LARGE TICK MARKS INDICATE NEUTRAL CONDUCTORS, SMALL TICK
MARKS INDICATE PHASE CONDUCTORS, TICK MARKS WITH A DOT INDICATE
ISOLATED GROUND CONDUCTORS. INCREASE ALL CIRCUITS WITH 900VA AND
EXCEEDING 100FT IN LENGTH TO TO #10 AWG CONDUCTORS. PROVIDE 2#12
AWG AND A GROUND IN 3/4" CONDUIT WHERE NO TICK MARKS ARE INDICATED.
ANNOTATION FOR LIGHTING INDICATES FIXTURE TYPE, TYPICAL OF ALL
FIXTURES. REFER TO FIXTURE SCHEDULE.
TYPICAL LIGHTING NOTATION LEGEND
FIRE ALARM/MASS NOTIFICATION EQUIPMENT LEGEND
GENERAL PROJECT NOTES
1. INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS
VERSION OF THE IBC, P-100, NFPA, NEC, AND THE AUTHORITY HAVING
JURISDICTION.
2. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. FIELD MEASURE FOR EXACT
BUILDING DIMENSIONS.
3. CONDUIT ROUTING SHOWN ON THESE PLANS IS DIAGRAMMATIC ONLY. THE
CONTRACTOR SHALL ROUTE CABLE AND CONDUIT ALONG THE SHORTEST, MOST
COST EFFECTIVE AND MOST CONSTRUCTABLE ROUTE WHERE POSSIBLE, WHILE
REMAINING IN COMPLIANCE WITH THE SPECIFICATIONS.
4. SYMBOLS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS. SOME SYMBOLS MAY
NOT BE USED ON THIS PROJECT.
5. ANY ELECTRICAL EQUIPMENT OR CONDUIT AND WIRING ON SITE THAT ARE
REQUIRED TO BE RELOCATED DUE TO CONSTRUCTION, SHALL BE DONE AT THE
CONTRACTOR'S EXPENSE. CONTRACTOR SHALL BE RESPONSIBLE FOR
MAINTAINING SERVICE TO ANY SUCH EQUIPMENT. COORDINATE WITH
GOVERNMENT PRIOR MAINTAIN CIRCUIT CONTINUITY OF ALL SYSTEMS OARTIALLY
DEMOLISHED.
6. COORDINATE ALL ELECTRICAL EQUIPMENT WITH ALL OTHER TRADES TO AVOID
CONFLICTS. PROVIDE ALL NECESSARY FITTINGS, EQUIPMENT, HANGERS, OFFSETS,
ROUTING, ETC. TO AVOID CONFLICTS AT NO ADDITIONAL COST TO OWNER.
7. COORDINATE JUNCTION BOX AND RECEPTACLE MOUNTING HEIGHTS FOR
EQUIPMENT FURNISHED BY OTHER TRADES. ADJUST AS NECESSARY TO
ACCOMMODATE THE EQUIPMENT SELECTED. PROVIDE ALL ELECTRICAL
CONNECTIONS TO HARD WIRED EQUIPMENT.
8. PROVIDE INSULATED BUSHINGS ON ALL STUBBED UP CONDUITS. PROVIDE A PULL
STRING IN ALL EMPTY CONDUITS.
ELECTRICAL RISER/SINGLE LINE DIAGRAM
FIRE FIGHTERS TELEPHONE
CEILING MOUNTED FIRE ALARM COMBINATION OF SPEAKER/STROBE DEVICE,
"15" DESIGNATES CANDELA RATING
FIRE ALARM VISUAL DEVICE, "15" DESIGNATES CANDELA RATING
WALL MOUNTED COMBINATION OF SPEAKER/STROBE, "15" DESIGNATES
CANDELA RATING
WALL MOUNTED NOTIFICATION STROBE MARKED "ALERT" WITH AMBER LENS,
NUMBER INDICATES CANDELA RATING
WALL MOUNTED FIRE ALARM COMBINATION OF AUDIO/VISUAL DEVICE, "15"
DESIGNATES CANDELA RATING
WALL MOUNTED FIRE ALARM AUDIO DEVICE
FIRE ALARM SPEAKER, CEILING MOUNTED U.O.N.
FIRE ALARM SPEAKER/STROBE COMBINATION , CEILING MOUNTED U.O.N.
FIRE ALARM SPEAKER, WALL MOUNTED U.O.N. "WP" INDICATES WEATHER
PROOF
CEILING MOUNTED SMOKE DETECTOR U.O.N.
SMOKE DETECTOR LISTED FOR HIGH AIR VELOCITY
WALL MOUNTED MULTI STATION SMOKE DETECTOR
MULTI STATION SMOKE DETECTOR WITH INTEGRAL VISUAL DEVICE
CEILING MOUNTED SMOKE DETECTOR, "E" INDICATES FOR ELEVATOR
RECALL
DUCT SMOKE DETECTOR
CEILING MOUNTED SMOKE DETECTOR FOR DOOR RELEASE, INCLUDE RELAY
BASE
CEILING MOUNTED HEAT DETECTOR
FIRE ALARM MANUAL PULL STATION
TAMPER SWITCH
FLOW SWITCH
PRESSURE SWITCH
FIRE ALARM TERMINAL CABINET
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM NOTIFICATION CIRCUIT POWER SUPPLY
FIRE ALARM TRANSPONDER CABINET
AIR SAMPLING DETECTOR
ADDRESSABLE CONTROL MODULE
ADDRESSABLE MONITOR MODULE
END OF LINE RESISTOR
POST INDICATOR VALVE
LOCAL CONTROL UNIT-MASS NOTIFICATION
FIRE ALARM DIGITAL DIAL OUT
WALL MOUNTED FIRE ALARM MAGNETIC DOOR HOLDER
FLOOR MOUNTED FIRE ALARM MAGNETIC DOOR HOLDER
GENERAL NOTES:
1. REFER TO DRAWINGS E-001 FOR ELECTRICAL SYMBOLS.
NOTES AND ABBREVIATIONS.
KEYED NOTES:
1 NEW BELOW GRADE 2-4" CONDUIT WITH 2 SETS 3# 500 KCM + 1
#1/O G FOR TEMPORARY CHILLER.
NEW WALL MOUNTED WEATHER PROOF PULL BOX. WATER
TIGHT SEAL BETWEEN BOX AND BUILDING. DRILL OPENINGS IN
WALL FOR PENETRATION OF BRANCH CIRCUIT TO TEMPORARY
CHILLER. COORDINATE FINAL LOCATION WITH EXISTING
CONDITIONS AND PROJECT MANAGER.
EXISTING 3" CONDUITS BELOW GRADE TO REMAIN.
REFER TO SHEET E-300 FOR DETAILS.
EXISTING MAIN DISTRIBUTION
SWITCHBOARD "MDS"
3000A, 480/277V, 3 PHASE, 4W
UNIT SPACE
UNIT SPACE
UNIT SPACE
NO. LOAD LOAD
UNIT SPACE CHILLER
CHILLER SPACE
SPACE HP1A
HP2B HPWS
ELEV 1,2 COMPUTER RM
HP3C HPC1B
HP2C HPC1A
HP3A SPACE
HP2A HP1B
T2A SPACE
HP3B HPC1C
SPARE MCC-R
SPARE NEW CHILLER
600A BRAKER UNIT SPACE
ATS
UNIT SPACE
UNIT SPACE
TEMP. CHILLER
HP
SPARE
(2) (3)
(4) (5)
(6) (7)
(8) (9)
(10) (11)
(12) (13)
(14)
(15)
(19) (20)
(21) (22)
(23) (24)
(25) (26)
(27) (28)
(29) (30)
(33)
UNIT SPACEUNIT SPACE
(31) (32)
(1)
(16) (34)
(18)
(17)
GENERAL NOTES:
1. REFER TO DRAWINGS E-001 FOR ELECTRICAL SYMBOLS.
NOTES AND ABBREVIATIONS.
KEYED NOTES:
1 PROVIDE A 800 A/3P, 480v CIRCUIT BRAKER FOR THE
INSTALATION OF A TEMPORARY CHILLER.
THE 800 A/3P CIRCUIT BRAKER SHALL BE REUSE FOR THE NEW
PERMANENT CHILLER.
NOTE: ALL EQUIPMENT IS EXISTING TO REMAIN AND TO BE MAINTAINED.
NOTE: ALL BREAKERS ARE EXISTING TO REMAIN AND TO BE MAINTAINED UNLESS OTHERWISE NOTED.
CH-1
TST-2 TST-1EXISTING
CHILLER
TEMPORARY CHILLER
EXISTING LIGHTS
(TYP).
CHIB
TEMPORARY
TRAILER GROUNDING IS
PROVIED BY CHILLER
MANUFACTURER
CH-1
EXISTING LIGHTS
(TYP).
CHIB
NEW
CHILLER
CHIB#8+10 CHIB#12
1. REFER TO DRAWINGS E-001 FOR ELECTRICAL SYMBOLS.
NOTES AND ABBREVIATIONS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION AND
RATING OF ALL EQUIPMENT PRIOR TO DEMOLITION.
3. CONTRACTOR SHALL PROVIDE CONTROL CABLE, CONDUIT,
JUNCTION BOX AND ACCESSORIES AS REQUIRED FOR A
COMPLETE AND FULLY OPERATIONAL CHILLER SYSTEM.
INSTALL NEMA 3R 800 A FUSED DISCONNECT SWITCH, WITH
700A FUSES TO SERVE THE TEMPORARY CHILLER EQUIPMENT.
MOUNT DISCONNECTS ON THE VERTICAL STEEL CHANNELS.
CHANNELS SHALL BE MINIMUM 12 GAGVE 1"X1-5/8" MINUMUN.
COATED WITH PVC TO MINIMUM THICKNESS OF 40 MILS.
JUNCTION BOX FOR POWER CONNECTION TO HEAT TRACE (208,
2 POLE, 30 AMPS) 2 #10 + 1 # 12 GRD IN 3/4 " CONDUIT. REFER TO
MECHANICAL DRAWINGS FOR EXACT LOCATION OF HEAT
TRACE.
PROVIDE NEMA 3R 800A FUSED DISCONNECT SWITCH WITH
700A FUSES FOR NEW CHILLER.
JUNTION BOX FOR CONTROL PANEL FOR NEW CHILLER.
PROVIDE 800A 3 POLE CIRCUIT BREAKER FOR TEMPORARY CHILLER.
PROVIDE 2 SETS OF 3 #500 KCM + 1 #1/0 G IN 4" CONDUIT.
PROVIDE 600V,800A FUSED DISCONNECT SWITCH WITH 700A FUSES TO SERVE THE
TEMPORARY CHILLER.
DISCONNECT EXISTING FEEDER SERVING THE EXISTING CHILLER. EXISTING FEEDER
AND CONDUITS TO BE
REMAIN FOR NEW CHILLER.
DISCONNECT AND REMOVE FUSED SWITCH SERVING THE EXISTING CHILLER.
PROVIDE NEW 600V, 800A FUSED DISCONNECT SWITCH WITH 700 A FUSES TO SERVE
NEW CHILLER.
EXTEND EXISTING CIRCUITRY TO ACCOMMODATE NEW CHILLER. REFER TO STEP 4
FOR FINAL MULTI POINT CONNECTION.
DISCONNECT AND REMOVE TEMPORARY DISCONNECT SWITCH SERVING TEMPORARY
CHILLER. EXISTING FEEDER AND CONDUIT TO BE REMAIN FOR MULTI POINT
CONNECTION NEW CHILLER.
MAKE THE CIRCUIT BREAKER SERVING THE TEMPORARY CHILLER TO BE REMAIN FOR
NEW CHILLER.
EXTEND EXISTING CIRCUITRY AND CONNECT TO NEW OWNER FURNISHED CHILLER.12