Text version
SHIP-TO-SHORE
The FCXtreme Series provides reliable solid-state converters that are designed to provide 400Hz ground power with a small footprint in applications such as inside aircraft hangars, in electrical equipment rooms, or in maintenance shops.
All models optimized and tested to perform a continuous output power rating with 200% overload capacity in 24/7 operations.
• Individual phase regulation, improved efficiency, and lower input current distortion
• Innovative, adaptive wave optimization and voltage stabilization
• Laminated bus design eliminates transient voltage surges for high performance and increased reliability
• Lightweight powder-coated steel enclosure with sealed electronics compartment superior to typical aluminum enclosures to reduce RF emissions
• Full-featured user interface with detailed troubleshooting menus added to the advanced diagnostic and logging system
• High contrast LED display with 16-button keypad and separate standalone controls to ensure ease of use for most frequent functions
• Standard RS485 Modbus communication and integration capability with available RJ45 Ethernet and Wi-Fi connection capability www.fcxinc.com | 304.983.0400 | sales@fcxinc.com
Ground POWER Solutions For All Generations Of Aircraft
ISO 9001:2008
UNIT PERFORMANCE
Efficiency 93% or better at 100% load
28VDC Output Available 600A rated 28VDC output with 400% surge rating
MTTR Mean time to repair: less than 30 minutes
Operational Life 20 to 25 years
MTBF Mean time between failure: 24,000 hours
Suitable For:
Fixed and Rotary Wing Aircraft and All Other 400 Hz Applications
X60 - X180
Through an innovative design, advanced diagnostic and logging systems, and rugged modular construction, FCXtreme Series products assure maximum power availability and minimal maintenance time.
60 KVA - 180 KVA
New X60 - X180 delivers improved performance in a package over 50% smaller than previous design.
60.0
18.0
20.0 30.0 50.0
7.0
24.0
FORKLIFT
CHANNELS
APPROXIMATE
CENTER OF
GRAVITY
78.0
RIGHT SIDE VIEW
INPUT CONDUITOUTPUT CONDUIT
FRONT VIEW
DOOR MOUNTED
CONTROLS DETAIL
D
C
B
E
F
SPECIFICATIONS
INPUT POWER
Input Voltage 480VAC +/- 10% standard, other input voltages available
Input Frequency 60Hz +/- 1Hz standard, 50Hz optional
Input Phase Rotation Any (automatic phase lock)
Inrush Current None (soft start to rated power)
Protection Overload, short circuit, over voltage, temperature, access door interlock
Input ITHD <5% at rated load, <8% at any load
OUTPUT POWER
Output Power Rating 60kVA continuous
75kVA continuous 90kVA continuous 120kVA continuous
Output Frequency 400Hz, +/- 0.01% for any load condition
Output Voltage 200V L-L / 115V L-N – adjustable +/- 10%
Voltage Regulation +/- 1% Maximum
Voltage Recovery Meets or exceeds limits of MIL-STD-704F, typically less than 50 milliseconds with a 100% load change
Voltage Balance +/- 1% for balanced loads, +/- 2% for 25% unbalanced loads
Harmonic Content 1.5% max., 1% typical (line to line or line to neutral)
Overload Capacity 125% for one hour, 150% for 5 minutes, 200% for 20 seconds
Protection Overload, short circuit, over and under voltage per MIL-STD-704F, over temperature, isolation, aircraft 28VDC E/F interlock, access door interlock
MONITORING AND CONTROLS
Display 4 x 20 character backlit display and dedicated indicator lights, with LED configuration for harsh environments
Control 16-key matrix keypad for full control and monitoring, as well as dedicated stand alone push button controls for Start, Stop/Reset, and Output On/Off control for user friendly operation
Metering Full three-phase monitoring and display of input and output voltage, current, and frequency; built-in troubleshooting guide in display; dedicated elapsed time meter also provided
ENVIRONMENTAL & MECHANICAL
Enclosure NEMA 4 (IP66) equivalent rated steel enclosure with durable powder coat finish. Standard color: RAL9006 “White Aluminum” (gray), other colors available.
Size/Weight 1981mm high x 1270mm wide x 706mm deep (78”H x 50”W x 27.8”D)
Ambient Temp. Range Operating: -40˚C to +50˚C (-40˚F to +122˚F)
Humidity 0 - 100%, non-condensing
Audible Noise Level Less than 68dbA typical @ 1m
CODES AND STANDARDS
Meets or Exceeds UFGS 26 35 43 NFPA 70
MIL-STD-704F SAE ARP-5015
BS2G-219 DFS-400
OPTIONS AND ACCESSORIES
28.5VDC Output with 600A rating
Integral single cable rack
Freestanding or wall mount cable racks
Output circuit breaker for distributed power applications
Dual or Triple output contactors
Unity power factor rating
ISO 9001:2008
www.fcxinc.com | 304.983.0400 400 FCX Lane | Morgantown, WV 26501 sales@fcxinc.com
Engineered for Endurance
Wi-Fi communications integration
Remote operators station(s)
Output power cables
Power usage monitoring
300% overload for 60/90 kVA units
140kVA continuous 160kVA continuous 180kVA continuous
Built-in Troubleshooting Guide in Display
SERVICE AND SUPPORT
At FCX Systems, we take pride in our highly trained support staff, dedicated to providing the best operational and technical support in the industry. Factory technicians are available for on-site training, maintenance and repair services, either in conjunction with our available maintenance plans, or as standalone services. Operational and maintenance training are also available at our factory. With FCX you can rest assured that you will have the support you need, when you need it, from a friendly, professional and experienced staff, 24/7/365.
Electronics Compartment Allows Calibration Without
Arc Flash Gear