Hood & Duct Maintenance Amendment #1 FA2550-14-T-1010
1. Question: Do you have blueprints of the duct systems?
Government Response:
No
2. What is the length of the hood canopies and number of hoods per exhaust fan?
System Type Manufacturer Building Length # of Hoods
Exhaust System Gaylord 300 Dining Hall 14 1
Exhaust System Gaylord 300 Dining Hall 32 3
Exhaust System Captive Air 60 CDC 20 2
Exhaust System Larkin 717 Fire Station 6 1
3. What is the estimated height of the duct from hood canopy to exhaust fan?
System Type Manufacturer Building Height Hood to Fan
Exhaust System Gaylord 300 Dining Hall 12-15 ft
Exhaust System Gaylord 300 Dining Hall 12-15 ft
Exhaust System Captive Air 60 CDC 10-12 ft
Exhaust System Larkin 717 Fire Station 8-10 ft
4. Can you identify which of these hoods are the Gaylord System or Captive Aire System?
Government Response: Stated in Section 1.1 of PWS
5. Which systems will be serviced quarterly or semi-annually and their location?
System Type Manufacturer Building Quarterly
Service
Semi-
Annual
Service
Exhaust System Gaylord 300 Dining Hall X
Exhaust System Gaylord 300 Dining Hall X
Exhaust System Captive Air 60 CDC X
Exhaust System Larkin 717 Fire Station X