This is a Salient Characteristics document for a federal facilities project at Patrick Space Force Base, Florida, dated April 7, 2026. The document specifies requirements for the procurement and installation of one Trane air-cooled scroll packaged chiller, model CGAM020A2, with a capacity of 20 nominal tons operating at 208 volts, 3 phases. The chiller must include manufacturer startup and service to maintain warranty coverage, and features extra efficiency/performance capabilities with R-454B refrigerant charge.

The specified equipment includes factory-installed components such as freeze protection, refrigerant isolation valves with discharge valve, flow switch set at 60 cm/second, 1.25-inch factory insulation for high humidity/low evaporator temperature environments, wide ambient capability, complete coat lanced aluminum fins with BLYGOLD coating for corrosion protection, and a water strainer. The chiller requires an across-the-line starter with direct online control, single-point main line power connection (ancillary items requiring separate power), high fault-rated circuit breaker control panel with BACnet MS/TP interface, elastomeric isolators, and architectural louvered panels. The vendor must provide a 10-year parts, labor, and refrigerant warranty. The project is identified as 26_16342058 under the 45 Civil Engineer Squadron, Operations Flight.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

Base: PATRICK SPACE FORCE BASE, FL

Unit: 45 CES / OPERATIONS FLIGHT

Date: 07 April 2026

Project #: 26_16342058 Form 9

Title: 1 TRANE CHILLER Air-Cooled Scroll Packaged Chiller/CGAM020A2

Description:

Air-Cooled Scroll Packaged Chiller

Startup Included - Trane Service must start equipment for warranty to be honored 20 nominal tons 208 volt 3 phases

Extra efficiency/performance

Refrigerant Charge R-454B

With factory installed freeze protection

Refrigerant isolation valves (discharge valve)

Factory installed flow switch - set point 60 cm/sec

Standard Cooling

Grooved pipe connection

Factory insulation 1.25" - high humidity/low evaporator temperature

Wide Ambient

Complete Coat lanced aluminum fins

BLYGOLD coating for cabinet & casings

Across the line starter/direct online

Single point connection main line unit power-ancillary items require other power

Circuit breaker-high fault rated control panel BACnet MS/TP Interface

Elastomeric isolators

With water strainer factory installed

Architectural louvered panels

Ten (10) year parts, labor & refrigerant warranty