This is a Salient Characteristics document for a federal facilities project at Patrick Space Force Base, Florida, dated April 7, 2026. The document specifies requirements for the procurement and installation of one Trane air-cooled scroll packaged chiller, model CGAM020A2, with a capacity of 20 nominal tons operating at 208 volts, 3 phases. The chiller must include manufacturer startup and service to maintain warranty coverage, and features extra efficiency/performance capabilities with R-454B refrigerant charge.
The specified equipment includes factory-installed components such as freeze protection, refrigerant isolation valves with discharge valve, flow switch set at 60 cm/second, 1.25-inch factory insulation for high humidity/low evaporator temperature environments, wide ambient capability, complete coat lanced aluminum fins with BLYGOLD coating for corrosion protection, and a water strainer. The chiller requires an across-the-line starter with direct online control, single-point main line power connection (ancillary items requiring separate power), high fault-rated circuit breaker control panel with BACnet MS/TP interface, elastomeric isolators, and architectural louvered panels. The vendor must provide a 10-year parts, labor, and refrigerant warranty. The project is identified as 26_16342058 under the 45 Civil Engineer Squadron, Operations Flight.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
Base: PATRICK SPACE FORCE BASE, FL
Unit: 45 CES / OPERATIONS FLIGHT
Date: 07 April 2026
Project #: 26_16342058 Form 9
Title: 1 TRANE CHILLER Air-Cooled Scroll Packaged Chiller/CGAM020A2
Description:
Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored 20 nominal tons 208 volt 3 phases
Extra efficiency/performance
Refrigerant Charge R-454B
With factory installed freeze protection
Refrigerant isolation valves (discharge valve)
Factory installed flow switch - set point 60 cm/sec
Standard Cooling
Grooved pipe connection
Factory insulation 1.25" - high humidity/low evaporator temperature
Wide Ambient
Complete Coat lanced aluminum fins
BLYGOLD coating for cabinet & casings
Across the line starter/direct online
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel BACnet MS/TP Interface
Elastomeric isolators
With water strainer factory installed
Architectural louvered panels
Ten (10) year parts, labor & refrigerant warranty