25QB012 Q and A.docx
DOCX document 19 KB Posted
- Attached to
- HVAC Materials
- Solicitation number
- FA252125QB012
About this file
This document is a Question and Answer (Q&A) file related to Solicitation FA252125QB012 for HVAC Materials required for a K-Span structure project at the Kennedy Space Center for the Department of the Air Force Space Command.
The key details are:
- The solicitation requires various HVAC equipment and materials, including liquid-tight conduit, thermostats, screws, gripple hooks and hangers, piping, and duct components.
- Vendors requested clarification on acceptable substitutes for discontinued or specified items, as well as required quantities and sizes for certain line items.
- The government provided responses confirming acceptable alternatives and clarifying the required specifications.
- The solicitation due date was extended to the following Tuesday to accommodate vendor requests.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HVAC 25QB012 Salient Characteristics Rev3.xlsx | XLSX spreadsheet | |
| 25QB012 Q and A.docx | DOCX document | |
| Dri Steem Specs.pdf | ||
| 25QB012 Brand Name JA Humidifier.pdf | ||
| 25QB012 Salient Characteristics Rev1.pdf | ||
| 25QB012 CSS Rev1.pdf | ||
| Dri Steem Schedule.pdf | ||
| Trane Schedule.pdf | ||
| Trane Specs.pdf | ||
| 25QB012 Salient Characteristics.xlsx | XLSX spreadsheet | |
| 25QB012 Brand Name JA.pdf | ||
| 25QB012 Clauses.pdf | ||
| 25QB012 CSS Final.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA252125QB012
HVAC
Q and A
1.Could you please specify the required length for the liquid tight roll?
The available options are 50 ft and 150 ft.
-50ft is wanted
2.Additionally, the Dayton thermostat (Part Number: 6EDZ8) has been discontinued. Would you accept the following alternative:
DAYTON Low Voltage Thermostat, Heat and Cool, Manual, Auto, Item 6EEA2, Mfr. Model 6EEA2?
- Ther thermostat needs a replacement, but drawings require that it have humidity/temp visible on screen and the replacement does not have humidity control nor humidity display available.
3.For Part Number 116041, would Item 2DU80, Mfr. Model U31702.021.0100, be an acceptable substitute?
- The replacement is fine. It is the same screw just 1in long instead of ¾ of an inch.
4.Please confirm if the total required quantity of item number 206F28 is just 20 units or 500 units as the part comes in packs of 25.
- We only need one pack of 25 units to complete the project.
5.Regarding the gripple hook and hanger, could you specify the required type? I’ve attached a gripple brochure for your reference.
- The required attachements types from gripple are the quick connect(XP2) and the hook(HG) on a 5ft cable length.
6.For items 24 and 25, please confirm if they refer to 3/4 " size piping.
-items 24 and 25 refer to the ¾ “ piping.
7.Part Number 654SRT has been discontinued. can you confirm if Item 52AV31, would be an acceptable option -The replacement is an acceptable option.
8.Lastly, could you clarify what item number 43 refers to?
-It is a slipjoint union. The slip joint slides onto PVC on both sides and the union screws them together. Ex. Apollo 1 in. x 1 in. PVC Slip Joint x Slip Joint Union PVCU1 - The Home Depot
9.We need a size for item 2; Duct sox with Qduct and collar system?
0. 174ft total length for both ductsox and 112sqft for both q ducts (in quote) 10.We need a qty for the bit sets on item 8: Shockware Hamme drill bit set? It comes in 3 to 33 size bit sets?
0. The 10 piece set is the qty 11.We need a size for item 30: Steel compression typer connector?
0. 1-1/4" 12.We need to know how many conductors for item 35: Comm cable 500 ft 20 AWG
0. Its one conductor in the spool
13. Line item 29 Unit’grip – Side Exit what size is required?
-The No. 2 size works for us.
14.Also, are you able to extend the due date until Tuesday?
-Yes