Peterson Air Force Base HVAC Water Treatment RFQ # FA2517-17-Q-5023 Questions and Answers

The following answers are in response to the questions received for the RFQ:

Question 1 – Per PWS section 1.3.4 regarding Bldg 1470 Cooling Tower, treatment of micro-biological growth, there was a question about sludge in the cooling tower and whether is was recently cleaned.

Answer: The cooling tower was recently cleaned for the summer cooling season.

Question 2 – Per PWS section 1.2.2, what are the volumes for the closed loop cleaning?

Answer: The rough estimate volume’s for the loop cleaning systems are as follows:

Bldg. 1013 – 180 Gallons

Bldg. 1143 – 190 Gallons

Bldg. 121 – 110 Gallons

Bldg. 910 – 40 Gallons