Questions and Answers for Solicitation

F3QCCM0050A001

Question 1: Statement: humidity control system is extremely expensive.

Answer 1: The humidity control system will not require to be programmable, but it should stay within the range listed that is a technical requirement for painting.

Question 2: Assumption: Contractor shall be supplying the Ductwork / duct connection

Answer 2: The contractor will supply duct work.

Question 3: Please clarify that no holes are to be made through the roof for the stacks and fresh air makeup unit?

Answer 3: There will be a requirement to cut the holes for the exhaust and air makeup unit. The pressure differential needs to be the drop across all three stages not each individual stage.

Question 4: Are there any progress payments on this project?

Answer 4: No.

Question 5: Please confirm that a natural-gas fired oven is acceptable for this project.

Answer 5: Natural gas can be used for the cure oven.