Attachment 3 - Vault Design.pdf
PDF 535 KB Posted
- Attached to
- 820 RHS Pre-Cast Concrete Vaults
- Solicitation number
- F3GHBA5148A001
About this file
This document is a technical design drawing and layout assembly for a precast concrete vault (Part Number 200061707) manufactured by Jensen Precast, designed to meet Puget Sound Energy (PSE) specifications. The vault has an approximate weight of 9,933.61 lbs, with a 5.0' bury depth, and is designed to ASTM C857 and ACI 318 standards.
Key technical features include a 5078x44 rectangular bottom section with a knockout sump, a 5078x13 slab top, and a 36x72 galvanized steel H-20 rated hatch that is spring-assisted and 180° capable. The vault includes multiple technical components such as four 0.5" galvanized pulling irons, 13/16"x1-5/8" unistrut on side and end walls, 18"x24" knockouts on all walls, two 2" ground rod knockouts, brass ground inserts, and zinc-plated threaded insert lifters. Each piece will be labeled with manufacturer, date of manufacture, and weight. The drawing notes that the design is not yet approved by the agency and recommends contacting Jensen Precast for complete design and product information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Items List and Specifications.pdf | ||
| Attachment 2 - Drawing.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ISO LAYOUT
BILL OF MATERIALS
WEIGHT (LBS)DESCRIPTIONPART NUMBERQTYITEM
6716.878Vault 5078x44 Rect. Bottom Section Knockout Sump20006170411
3218.276Vault 5078x13 Slab Top 3672"C20006170612
7.
id w
SHEET:
REV:
A-4
9/13/2021 10/17/2022MODIFIED:CREATED:
PART NUMBER: DRAWN BY:
DESCRIPTION:
Vault 5078 Layout Assembly
AGENCY SPEC:AGENCY:
DESIGN SPEC: LOADING SPEC:
BURY DEPTH:
WWW.JENSENPRECAST.COM
0.0' - 0.0' to Top
WATER LEVEL:
A-16 (AASHTO HS20-44)
5.0' APPROX. WEIGHT: 9933.61 Lbs
200061707 T.Larson
ASTM C857,ACI 318
©2022 Jensen Precast- All rights reserved.
All materials appearing as Jensen Precast documents and the like are proprietary work product and are protected under U.S. copyright and other laws.
Unless in conjunction with business conducted with Jensen Precast, any use of Jensen Precast work product without express, written consent is prohibited, and recipient is prohibited from distributing any and all work product to non-approved third parties under penalty of civil action.
LAYOUT REVIEW
DESIGN NOTES
■ DESIGNED TO MEET SPECIFICATIONS OF PUGENT SOUND ENERGY (PSE) 7663200.
NOT YET APPROVED BY AGENCY.
■ FOR COMPLETE DESIGN AND PRODUCT INFORMATION CONTACT JENSEN PRECAST.
CHANGE HISTORY
NO. DESCRIPTION DATE BY
1 DRAWING CREATED 3/29/2022 T.Larson
36x72 GALVANIZED STEEL HATCH:
H-20 RATED, SPRING ASSISTED,
180° CAPABLE, DIAMOND PLATE
STANDARD, TRAXPLATE OPTIONAL
EACH PIECE
LABELED WITH
MANUFACTURER,
DATE OF MANUFACTURE,
AND WEIGHT
PLAN VIEW
SECTION A-A SECTION B-B
PLAN VIEW
(SHOWING INSIDE FLOOR)
A
A
B B
7.
id w
SHEET:
REV:
A-4
9/13/2021 10/17/2022MODIFIED:CREATED:
PART NUMBER: DRAWN BY:
DESCRIPTION:
Vault 5078 Layout Assembly
AGENCY SPEC:AGENCY:
DESIGN SPEC: LOADING SPEC:
BURY DEPTH:
WWW.JENSENPRECAST.COM
0.0' - 0.0' to Top
WATER LEVEL:
A-16 (AASHTO HS20-44)
5.0' APPROX. WEIGHT: 9933.61 Lbs
200061707 T.Larson
ASTM C857,ACI 318
©2022 Jensen Precast- All rights reserved.
All materials appearing as Jensen Precast documents and the like are proprietary work product and are protected under U.S. copyright and other laws.
Unless in conjunction with business conducted with Jensen Precast, any use of Jensen Precast work product without express, written consent is prohibited, and recipient is prohibited from distributing any and all work product to non-approved third parties under penalty of civil action.
LAYOUT DRAWING
GRD
88"
60"
60"
12"
48"
70" 9"9"
11 3/8"
37 1/4"
11 3/8"
18"X24"
KNOCKOUT
2 EACH ON
ALL WALLS
13/16"x1-5/8"
UNISTRUT
1 EACH SIDE WALL
72" LONG
13/16"x1-5/8"
UNISTRUT
1 EACH SIDE WALL
24" LONG
13/16"x1-5/8"
UNISTRUT
1 EACH END WALL
36" LONG
Ø0.5" GALV
PULLING IRON (x4)
13"
13"
11"
18"
30"
16" 16" 26" 26" n1 1/2"
LIFT HOLE
1 EACH SIDE WALL
5" 50" 5"
60"
5" 78" 5"
88"
48"
21 1/2"
TYP.
35 1/2"
TYP.
32"
TYP.
18"
TYP.
n2" GROUND ROD
KNOCKOUT (x2) n12"x2.5"
SUMP
4"
1/2"x36" BRASS
GROUND INSERT
1 EACH ON
SIDE WALLS
WITH PROTECTIVE
CAPS
UTILITY MARKING
OF "POWER"
WITH 2 INCH
LETTER HEIGHT
Ø3/4" RECESSED
ZINC PLATED
THREADED INSERT
LIFTERS (x4)
55 1/2"
25 FT - #3
REBAR FOR
GROUNDING
13"
"GRD" LABELED
ADJACENT TO
GROUNDING
INSERTS
File details come from the government source that posted it. Updated .