Contractor Q and A Answers.docx

DOCX document 18 KB Posted

Attached to
57 AMXS Hangar 199 CONNEX
Solicitation number
F3G3AA6103A001
Issued by

About this file

This is a Contractor Question and Answer document that clarifies technical specifications for a 20-foot standard shipping container modification required under Solicitation Number F3G3AA6103A001 for the 57 AMXS Hangar 199 CONNEX project at Nellis Air Force Base, Nevada.

The document addresses 28 questions regarding interior and exterior modifications to the container. Key specifications include: a 36-inch steel entry door with Kwikset lockset located on the long front left side; vertically opening windows with screens on the long sides; electrical service panel (breaker/disconnect) on the long back right side accessible from outside; four duplex 110-volt interior outlets positioned two per long wall; interior LED lighting consisting of two fixtures with two bulbs each at 4000K temperature providing 50-75 foot-candles at 30 inches from floor, controlled by a dimmer switch near the entrance; and a 4000K-5000K floodlight above or near the entrance door. Interior finishing requires spray foam insulation covered with drywall on all walls and ceiling, with the floor insulated and covered with BC sanded plywood. No exterior GFCI receptacles, window guards, or generator inlet are required. The container will connect to commercial power at the delivery location. This is the authoritative technical clarification document that bidders must reference when preparing their offers for the Firm Fixed Price contract with a 60-day delivery requirement to Nellis AFB, Nevada.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Where should the door be located?

a. The door should be located on long front left side of the container?

2. Does the 36" steel entry door require locks, and if so, what type?

a. Yes, Kwikset, standard lockset with 2 keys

3. Does the 36" door need a window?

a. No

4. Is the height of the door standard at 80"?

a. Yes

5. Do the windows need to open?

a. Yes,

6. How should the windows open?

a. Windows should open vertically

b. Window screens should be provided

7. Is vandal or tamper-resistant caging needed on the outside of the windows?

a. No

8. Where is the service panel located?

a. The electrical and comm service panels should be located on the long back right side of the container.

b. What will be the service panel? i.e. disconnect, breaker panel?

9. Is the service panel serviced from the inside or the outside?

a. Outside

10. How many internal LEDs are needed?

a. Foot-candles should equal 50-75 at 30” from floor.

b. Two (2) fixtures with two (2) bulbs each

11. What temperature should the internal LEDs be?

a. 4000K

12. Where are the internal LEDs?

a. Center of ceiling evenly spaced between the walls

13. How are the LED fixtures controlled?

a. Light switch with dimmer

14. Where are the switches for the LEDs?

a. Next to entrance door

15. What temperature should the floodlight be?

a. 4000K – 5000K

16. Where should the floodlight be?

a. Above or near entrance door

17. How many outlets, what type, and what voltage

a. Four (4) duplex, 110v outlets.

18. Where should the outlets be?

a. Two (2) on each long wall evenly spaced apart

19. How does the service panel interface with the generator inlet?

a. We plan to connect this container to commercial power. No generator inlet will be required.

20. Is the spray foam left exposed to the inside of the container, or does it require a cover, such as drywall or metal?

a. Drywall on all walls and ceiling

21. Do you want the floor insulated along with the interior?

a. Yes

22. With the interior being raw spray foamed would you like this covered or left raw?

a. The floor needs to be covered

23. Also, are we looking for interior outlets or just exterior?

a. Interior outlets

24. How many interior duplex receptacles are required?

a. Four (4) duplex receptacles. Two (2) on each long side wall evenly spaced apart.

25. Are any exterior GFCI receptacles required? If so, how many?

a. No

26. -There was no mention of the finishing over the spray foam insulation . Usually it will require some type of plywood covering . Would ½ BC sanded plywood be okay?

a. The walls and ceiling should be covered with drywall.

b. The floor can be plywood, but ¾ BC sanded plywood is required.

27. -How many 4 ft LED lights are required on the interior ?

a. (Already answered )

28. -Is container unloading by the government available at the delivery location?

a. Please see updated salient characteristics