Sheet1
| Contractor Question | Government Response | |
| 1 | Are all buildings listed on Appendix A to be included in the bid? | Yes, all buildings listed on Appendix A are included in the bid. |
| 2 | Does the Government have a specific testing lab to be used or recommended? | No, the Government does not have a specific testing lab to be used, nor do they recommend one. |
| 3 | Can all cleanings be arranged to be completed at the same time period? | Yes, all cleanings can be arranged to be completed at the same time period. |
| 4 | Is there a current contract performing this type of work? If so, what is the contract number and who is the incumbent Contractor? | The incumbent contract is FA2835-15-P-0039 with Your Environmental Solutions, Inc. It was awarded for $56,700.00. |
| 5 | Are there any pumps, grinders, disconnects, etc. associated with the separators? | No, there are no pumps, grinders, disconnects, etc. associated with the separators. |
| 6 | Does each separator need to be sampled prior to scheduling the cleaning? If so, how far in advance must the sampling be done? | Yes each separator needs to be sampled prior to scheduling the cleaning. The sampling should be performed approximately one month before cleaning, to allow time for sampling to be reviewed by Hanscom enviromental personnel. |
| 7 | Are Contractors responsible for providing water for rehydration? | Yes, Contractors are responsible for providing water for rehydration. |
| 8 | Will there be another opportunity for a site visit at Hanscom? | No, there will not be another site visit opportunity. |
| 9 | The PWS states the contract is expected to require entry into confined spaces and that units over 1,000 gallons must be entered to clean appropriately. Is this strictly a size consideration or is this requirement due to unique configurations limiting access? | This is a strictly a size consideration. |
| 9a | Will the systems located near buildings 1302E, 1642 MP North, 1707, and 1994 require entry? | Yes, the systems located near buildings 1302E, 1642 MP North, 1707, and 1994 will require entry. |
| 10 | Is the Child Development Center a 16,000 gallon OWS or is it a grease trap? What is it used for? | Yes, the Child Development Center is a 16,000 gallon OWS. |
| 11 | Are there any lids, grates, or manways that require more than manual lifting for removal? If so, will the base provide mechanical lifting equipment? | Only Building 1201 OWS requires mechanical lifting equipment. The base will provide mechanical lifting support for this location. |
| 12 | Are the most recent analytical results for existing units available? | Yes |
| 13 | Is the 18,000 gallon unit located at 1302I an OWS with a working capacity of 18,000 gallons or is the total volume similar to Hanger fire suppression systems overflow tanks? | Yes, the 18,000 gallon unit located at 1302I is an OWS with a working capacity of 18,000 gallons. |
| 14 | Do the troughs listed in Appendix A have bolted lids or grating? | They have grating. |
| 15 | What are the dimensions of the trough for Building 1700 BITS? | The dimensions of the trough for Building 1700 BITS are 50 feet long X 12 inches wide X 10 inches deep. |