Vault List

View the file

Other files for this federal contract opportunity

Other files attached to Steam Traps Maintenance, newest first.
File Type Posted
FA2835-16-C-0012_FBO_Award.pdf PDF
FINAL_Steam_Traps_Combined_Synopsis.pdf PDF
FINAL_Combined_Solicitation.pdf PDF
Amended_PWS_Steam_Trap_Maintenance.docx DOCX document
2016_Bid_Schedule_Maintenance_and_Testing_of_Steam_Traps.pdf PDF
Hanscom_AFB_Fulll_Trap_Listing_2016.xlsx XLSX spreadsheet
PWS_Steam_Trap_Maintenance__8_1_16.pdf PDF
8-29_CORRECTED_REVISED_Steam_Traps_Combined_Synopsis.pdf PDF
2016_List_of_17_MH_ _Mech_rooms2.pdf PDF
Wage_Determinations_R19.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Hanscom AFB - Distribution 2016 - Steam Trap Efficiency Report

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB13

(4) Valves

(3) Valves greased and exercised. Piping and insulation OK. Steam trap #70128 Blowing.

(1) Condensate main valve closed.

Distribution /

Ground / Vault JB14

(5) Valves

(4) Valves greased and exercised. Piping and insulation OK. Electric sump pump OK.

Steam trap #36165 NIS. (1) Valve closed on outlet of trap.

Hanscom employees report problems in associated mechanical room.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB16

(7) Valves

(7) Valves greased and exercised. Piping and insulation OK.

Steam trap #36166 OK.

Steam eductor not functioning.

Distribution /

Ground / Vault JB17

(3) Valves

(3) Valves greased and exercised. Piping OK. Steam trap #36167 Blowing.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB18

(4) Valves

(4) Valves greased and exercised. Piping and insulation OK.

Steam trap #3618 NIS.

Steam eductor isolated due to sticking float.

Condensate main dead headed due to problems in mechanical rooms.

Distribution /

Ground / Vault

JB18A

(1) Valve

(1) Valve greased and exercised. Piping OK. Piping insulated except valve. Blind flange on condensate line. Supply/return to building blind flanges.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB19

(4) Valves

(3) Valves greased and exercised. (1) Valve closed with blind flange to Exchange.

Piping and insulation OK.

Distribution /

Ground / Vault JB20

(9) Valves

(6) Valves greased and exercised. (2) Valves closed. (1) Valve locked out.

Piping and insulation OK. Steam trap #36169 Plugged. Steam eductor not functioning.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB21

(4) Valves

(4) Valves greased and exercised. Piping and insulation OK.

Distribution /

Ground / Vault JB33

(2) Valves

(2) Valves greased and exercised. Piping and insulation OK.

Steam trap #76151 Plugged.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB62

(5) Valves

(3) Valves greased and exercised. (1) Steam valve to Lincoln Lab gearbox failed. (1) Steam valve going west closed. Piping and insulation in fair condition. Steam eductor and electric sump pump. Steam trap #36170 Leaking.

Isolation valve to steam eductor leaking from bonnet.

Vault vent bent and piping rusted.

Distribution /

Ground / Vault

JB62/63

(0) Valves

Piping and insulation OK. Steam trap #36171 NIS.

Steam isolated.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB64

(4) Valves

(4) Valves greased and exercised.

Piping and insulation OK. Steam trap #36172 NIS.

Distribution /

Ground / Vault JB65

(7) Valves

(7) Valves greased and exercised. Insulation OK. Steam trap #36173 OK.

The main support beam is rotted out.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB66

(2) Valves

(2) Valves greased and exercised. Piping and insulation OK.

Distribution /

Ground / Vault JB67

(3) Valves

(3) Valves greased and exercised. Piping and insulation OK.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB68

(5) Valves

(4) Valves greased and exercised. (1) Condensate valve to west locked out.

Main piping and insulation OK.

Steam trap #36174 Repaired and tested OK

Distribution /

Ground / Vault JB69

(6) Valves

(6) Valves grease and exercised. Insulation OK. Steam trap #36178 NIS.

Steam leak on line to eductor. Steam eductor not functioning.

Steam trap tagged out by D’Amico. Outlet of steam trap tied into storm basin system.

Building / Floor /

Room

Number Of

Valves Comments/ Condition

Distribution /

Ground / Vault JB70

(4) Valves

(4) Valves grease and exercised. Insulation Ok Steam Trap #36177 OK

The condensate return valve at trap station is leaking and should be replaced.

Distribution /

Ground / Vault JB71

(5) Valves

(5) Valves greased and exercised. Main piping and insulation OK.

Steam trap #70158 Repaired and tested OK

Hanscom Air Force Base 2015 - Steam Trap Efficiency Report

VAULTS

7. VAULTS COMMENTS AND IMAGES

Location / Room Number of Valves

Comments / Condition

Distribution /

Vault JB11 /

2 Valves In Junction Box, 2 Not Exercised, Valves Closed.

Distribution /

Vault JB12 /

2 Valves In Junction Box, 2 Valves Greased And Exercised.

Distribution /

Vault JB12A /

Valves In Junction Box, 3 Valves Greased And Exercised..

Distribution /

Vault JB2 /

4 Valves In Junction Box, 1 Valves Greased And Exercised.

3 Not Exercised, Valves Closed.

Distribution /

Vault JB25 /

9 Valves In Junction Box, 8 Valves Greased And Exercised.

1 Not Exercised, Valve Closed

Additional Equipment: 4 Pressure Operated Pumps/Condensate Receiver.

Distribution /

Vault JB26 /

Grenier/Barksdale

Valves In Junction Box, 6 Valves Greased And Exercised.

Distribution /

Vault JB26A /

Grenier And

Barksdale

5 Valves In Junction Box, 4 Valves Greased And Exercised.

1 Not Exercised, Valve Closed.

Distribution /

Vault JB26B /

Barksdale/Grenier

No Valves In Junction Box

Additional Equipment: Electric Sump Pump.

Distribution /

Vault JB27 /

1 Not Exercised, Valve Closed. Trap 70135 Repaired.

Distribution /

Vault JB28 /

Minuteman

Commons

6 Valves In Junction Box, 6 Valves Greased And Exercised.

Distribution /

Vault JB29 /

7 Valves In Junction Box, 7 Valves Greased And Exercised.

Distribution /

Vault JB3 /

1508 Rear

4 Valves In Junction Box, 2 Valves Greased And Exercised.

2 Not Exercised, Valves Closed.

Distribution /

Vault JB30 /

3 Valves In Junction Box, 3 Valves Greased And Exercised.

Additional Equipment: Electric Sump Pump. Trap 70134 Repaired.

Distribution /

Vault JB32 /

6 Valves In Junction Box, 6 Valves Greased And Exercised..

Distribution /

Vault JB36 /

1508 Rear In Yard

Distribution /

Vault JB4 /

5 Valves In Junction Box, 4 Valves Greased And Exercised.

1 Not Exercised, Valve Closed.

Distribution /

Vault JB5 /

4 Valves In Junction Box, 1 Valves Greased And Exercised.

3 Not Exercised, Valves Closed.

Distribution /

Vault JB52 /

Barksdale And

Marrett

5 Valves In Junction Box, 4 Valves Greased And Exercised.

1 Not Exercised, Valve Closed.

Distribution /

Vault JB53 /

5 Valves In Junction Box, 5 Valves Greased And Exercised.

Distribution /

Vault JB54 /

5 Valves In Junction Box, 2 Valves Greased And Exercised.

3 Not Exercised, Valves Closed.

Distribution /

Vault JB55 /

Valves In Junction Box, 6 Valves Greased And Exercised.

Distribution /

Vault JB56 /

Snack Bar

3 Valves In Junction Box, 2 Valves Greased And Exercised.

Distribution /

Vault JB57 /

Snack Bar

Distribution /

Vault JB58 /

Valves In Junction Box, 2 Valves Greased And Exercised.

2 Not Exercised, Valves Closed.

Distribution /

Vault JB59 /

Valves In Junction Box, 5 Valves Greased And Exercised..

Distribution /

Vault JB60 /

Valves In Junction Box, 2 Valves Greased And Exercised..

Distribution /

Vault JB61 /

5 Valves In Junction Box, 3 Valves Greased And Exercised.

2 Not Exercised, Valves Closed. Trap 70121 Repaired.

Distribution /

Vault JB9 /

Corner Of 1305

Parking Lot

Additional Equipment: Pressure Operated Pump.

Distribution /

Vault JB7B /

Across From Garage

No Valves In Junction Box

Pages from Hanscom AFB - Distribution Steam Trap Efficiency Report 050416
Pages from Hanscom Air Force Base Vaults Steam Trap Efficiency Report 092215