Vault List
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA2835-16-C-0012_FBO_Award.pdf | ||
| FINAL_Steam_Traps_Combined_Synopsis.pdf | ||
| FINAL_Combined_Solicitation.pdf | ||
| Amended_PWS_Steam_Trap_Maintenance.docx | DOCX document | |
| 2016_Bid_Schedule_Maintenance_and_Testing_of_Steam_Traps.pdf | ||
| Hanscom_AFB_Fulll_Trap_Listing_2016.xlsx | XLSX spreadsheet | |
| PWS_Steam_Trap_Maintenance__8_1_16.pdf | ||
| 8-29_CORRECTED_REVISED_Steam_Traps_Combined_Synopsis.pdf | ||
| 2016_List_of_17_MH_ _Mech_rooms2.pdf | ||
| Wage_Determinations_R19.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hanscom AFB - Distribution 2016 - Steam Trap Efficiency Report
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB13
(4) Valves
(3) Valves greased and exercised. Piping and insulation OK. Steam trap #70128 Blowing.
(1) Condensate main valve closed.
Distribution /
Ground / Vault JB14
(5) Valves
(4) Valves greased and exercised. Piping and insulation OK. Electric sump pump OK.
Steam trap #36165 NIS. (1) Valve closed on outlet of trap.
Hanscom employees report problems in associated mechanical room.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB16
(7) Valves
(7) Valves greased and exercised. Piping and insulation OK.
Steam trap #36166 OK.
Steam eductor not functioning.
Distribution /
Ground / Vault JB17
(3) Valves
(3) Valves greased and exercised. Piping OK. Steam trap #36167 Blowing.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB18
(4) Valves
(4) Valves greased and exercised. Piping and insulation OK.
Steam trap #3618 NIS.
Steam eductor isolated due to sticking float.
Condensate main dead headed due to problems in mechanical rooms.
Distribution /
Ground / Vault
JB18A
(1) Valve
(1) Valve greased and exercised. Piping OK. Piping insulated except valve. Blind flange on condensate line. Supply/return to building blind flanges.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB19
(4) Valves
(3) Valves greased and exercised. (1) Valve closed with blind flange to Exchange.
Piping and insulation OK.
Distribution /
Ground / Vault JB20
(9) Valves
(6) Valves greased and exercised. (2) Valves closed. (1) Valve locked out.
Piping and insulation OK. Steam trap #36169 Plugged. Steam eductor not functioning.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB21
(4) Valves
(4) Valves greased and exercised. Piping and insulation OK.
Distribution /
Ground / Vault JB33
(2) Valves
(2) Valves greased and exercised. Piping and insulation OK.
Steam trap #76151 Plugged.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB62
(5) Valves
(3) Valves greased and exercised. (1) Steam valve to Lincoln Lab gearbox failed. (1) Steam valve going west closed. Piping and insulation in fair condition. Steam eductor and electric sump pump. Steam trap #36170 Leaking.
Isolation valve to steam eductor leaking from bonnet.
Vault vent bent and piping rusted.
Distribution /
Ground / Vault
JB62/63
(0) Valves
Piping and insulation OK. Steam trap #36171 NIS.
Steam isolated.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB64
(4) Valves
(4) Valves greased and exercised.
Piping and insulation OK. Steam trap #36172 NIS.
Distribution /
Ground / Vault JB65
(7) Valves
(7) Valves greased and exercised. Insulation OK. Steam trap #36173 OK.
The main support beam is rotted out.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB66
(2) Valves
(2) Valves greased and exercised. Piping and insulation OK.
Distribution /
Ground / Vault JB67
(3) Valves
(3) Valves greased and exercised. Piping and insulation OK.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB68
(5) Valves
(4) Valves greased and exercised. (1) Condensate valve to west locked out.
Main piping and insulation OK.
Steam trap #36174 Repaired and tested OK
Distribution /
Ground / Vault JB69
(6) Valves
(6) Valves grease and exercised. Insulation OK. Steam trap #36178 NIS.
Steam leak on line to eductor. Steam eductor not functioning.
Steam trap tagged out by D’Amico. Outlet of steam trap tied into storm basin system.
Building / Floor /
Room
Number Of
Valves Comments/ Condition
Distribution /
Ground / Vault JB70
(4) Valves
(4) Valves grease and exercised. Insulation Ok Steam Trap #36177 OK
The condensate return valve at trap station is leaking and should be replaced.
Distribution /
Ground / Vault JB71
(5) Valves
(5) Valves greased and exercised. Main piping and insulation OK.
Steam trap #70158 Repaired and tested OK
Hanscom Air Force Base 2015 - Steam Trap Efficiency Report
VAULTS
7. VAULTS COMMENTS AND IMAGES
Location / Room Number of Valves
Comments / Condition
Distribution /
Vault JB11 /
2 Valves In Junction Box, 2 Not Exercised, Valves Closed.
Distribution /
Vault JB12 /
2 Valves In Junction Box, 2 Valves Greased And Exercised.
Distribution /
Vault JB12A /
Valves In Junction Box, 3 Valves Greased And Exercised..
Distribution /
Vault JB2 /
4 Valves In Junction Box, 1 Valves Greased And Exercised.
3 Not Exercised, Valves Closed.
Distribution /
Vault JB25 /
9 Valves In Junction Box, 8 Valves Greased And Exercised.
1 Not Exercised, Valve Closed
Additional Equipment: 4 Pressure Operated Pumps/Condensate Receiver.
Distribution /
Vault JB26 /
Grenier/Barksdale
Valves In Junction Box, 6 Valves Greased And Exercised.
Distribution /
Vault JB26A /
Grenier And
Barksdale
5 Valves In Junction Box, 4 Valves Greased And Exercised.
1 Not Exercised, Valve Closed.
Distribution /
Vault JB26B /
Barksdale/Grenier
No Valves In Junction Box
Additional Equipment: Electric Sump Pump.
Distribution /
Vault JB27 /
1 Not Exercised, Valve Closed. Trap 70135 Repaired.
Distribution /
Vault JB28 /
Minuteman
Commons
6 Valves In Junction Box, 6 Valves Greased And Exercised.
Distribution /
Vault JB29 /
7 Valves In Junction Box, 7 Valves Greased And Exercised.
Distribution /
Vault JB3 /
1508 Rear
4 Valves In Junction Box, 2 Valves Greased And Exercised.
2 Not Exercised, Valves Closed.
Distribution /
Vault JB30 /
3 Valves In Junction Box, 3 Valves Greased And Exercised.
Additional Equipment: Electric Sump Pump. Trap 70134 Repaired.
Distribution /
Vault JB32 /
6 Valves In Junction Box, 6 Valves Greased And Exercised..
Distribution /
Vault JB36 /
1508 Rear In Yard
Distribution /
Vault JB4 /
5 Valves In Junction Box, 4 Valves Greased And Exercised.
1 Not Exercised, Valve Closed.
Distribution /
Vault JB5 /
4 Valves In Junction Box, 1 Valves Greased And Exercised.
3 Not Exercised, Valves Closed.
Distribution /
Vault JB52 /
Barksdale And
Marrett
5 Valves In Junction Box, 4 Valves Greased And Exercised.
1 Not Exercised, Valve Closed.
Distribution /
Vault JB53 /
5 Valves In Junction Box, 5 Valves Greased And Exercised.
Distribution /
Vault JB54 /
5 Valves In Junction Box, 2 Valves Greased And Exercised.
3 Not Exercised, Valves Closed.
Distribution /
Vault JB55 /
Valves In Junction Box, 6 Valves Greased And Exercised.
Distribution /
Vault JB56 /
Snack Bar
3 Valves In Junction Box, 2 Valves Greased And Exercised.
Distribution /
Vault JB57 /
Snack Bar
Distribution /
Vault JB58 /
Valves In Junction Box, 2 Valves Greased And Exercised.
2 Not Exercised, Valves Closed.
Distribution /
Vault JB59 /
Valves In Junction Box, 5 Valves Greased And Exercised..
Distribution /
Vault JB60 /
Valves In Junction Box, 2 Valves Greased And Exercised..
Distribution /
Vault JB61 /
5 Valves In Junction Box, 3 Valves Greased And Exercised.
2 Not Exercised, Valves Closed. Trap 70121 Repaired.
Distribution /
Vault JB9 /
Corner Of 1305
Parking Lot
Additional Equipment: Pressure Operated Pump.
Distribution /
Vault JB7B /
Across From Garage
No Valves In Junction Box
| Pages from Hanscom AFB - Distribution Steam Trap Efficiency Report 050416 |
| Pages from Hanscom Air Force Base Vaults Steam Trap Efficiency Report 092215 |