8’-24’ Powerfoil® X

INSTALLATION GUIDE

8’ - 24’ POWERFOIL® X

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

Installation Checklist Did a structural engineer approve the mounting structure? (See p. 8 for Big Ass Fans approved mounting structures.)

Are you familiar with the function and use of the safety cable? (See p. 17 for information on properly securing the safety cable.)

Will the fan be installed so that the blades are at least 10 ft (3.05 m) above the floor?

Will the fan be installed so that the blades have at least 2 ft (0.61 m) of clearance from obstructions?

Will the fan be installed so that it is not subjected to high winds (such as from an HVAC system or near a large garage door)? Big Ass Fans recommends that a fan be installed at a distance (from HVAC equipment) no less than 2x the fan’s diameter when measured from the center of the fan to the equipment. If the fan is mounted lower than an HVAC supply and return diffuser’s discharge, the fan should be installed no less than 2x the fan’s diameter from the diffuser when measured from the center of the fan to the diffuser. If the fan is mounted at the same height or higher than a downward discharge diffuser, the fan is recommended to be installed no less than 1x the fan’s diameter from the diffuser when measured from the center of the fan to the diffuser.

Will the distance between multiple fans be at least 2.5x the fans’ diameter when measured from the centers of the fans.

If installing to an I-beam, is the upper yoke the correct size? (See p. 11 for more information on installing the fan to an I-beam.)

If you ordered multiple fans, did you keep the parts for each fan together? (It is critical that the airfoils be properly matched with the motor unit.)

Do you have the correct power circuit for the fan controller? (See p. 24 for information on selecting the correct circuit/fuse for the fan controller.)

Customer Service: 1-877-BIG-FANS (International: 1-859-233-1271) i

8’ - 24’ POWERFOIL® X

Installation Guide 8’-24’ Powerfoil® X

2425 Merchant Street Lexington, KY 40511

1-877-BIG-FANS

www.bigassfans.com

May be covered by one or more of the following United States Patents: 6,244,821;

6,589,016; 6,817,835; 6,939,108; 7,252,478; 7,284,960;

D607,988; D587, 799; 7,654,798; and other patents pending

Installation Guide:

170511- May 2011 Rev. B

This product was manufactured in a plant whose Management System is certified as being in conformity with ISO 9001:2008

3128438 Intertek

Conforms to ANSI/UL STD 507 Certified to CAN/CSA C22.2 No. 113

IMPORTANT SAFETY INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS

WARNING—TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

a. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards.

b. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

CAUTION: The installation of a Big Fan must be in accordance with the requirements specified in this installation manual and with any additional requirements set forth by the national electric code (NEC), ANSI/NFPA 70-1999, and all local codes. Code compliance is ultimately YOUR responsibility! Failure to comply with these codes could result in personal injury or property damage.

WARNING: The fan controllers contain high voltage capacitors which take time to discharge after removal of main supply.

Before working on the fan controller, ensure isolation of main supply from line inputs at the fan controller. Wait 3 minutes for capacitors to discharge to safe voltage levels. Note: darkened display LEDs are not an indication of safe voltage levels.

Failure to do so may result in personal injury or death.

CAUTION: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans at 1-877-BIG- FANS if you have any questions regarding the electrical installation of this fan.

WARNING—To reduce the risk of fire, electric shock, and injury to persons, Big Ass Fans must be installed with Big Ass Fan supplied controllers. Other parts cannot be substituted.

CAUTION: When service or replacement of a component in the fan requires the removal or disconnection of a safety device, the safety device is to be reinstalled or remounted as previously installed.

WARNING: Risk of fire, electric shock, or injury to persons during cleaning and user-maintenance! Disconnect the fan from the power supply before servicing.

WARNING—TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

a. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.

b. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.

CAUTION: Do not bend the blades when installing, adjusting, or cleaning the fan. Do not insert foreign objects in between rotating fan blades.

WARNING: Stay alert, watch what you are doing, and use common sense when installing fans. Do not install fans if tired or under the influence of drugs, alcohol, or medication. A moment of inattention while installing fans may result in serious personal injury.

CAUTION: The installation of this fan requires the use of some power tools. Follow the safety procedures found in the owner’s manual for each of these tools and do not use them for purposes other than those intended by the manufacturer.

CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure that is caused by improper installation.

ATTENTION: If installing a VESDA system, refer to the VESDA Installation Guide BEFORE hanging the fan.

CAUTION: Do not operate fan with a damaged cord or plug. Return fan to an authorized service facility for examination or repair.

Contents Introduction Thank You 1

About Big Ass Fans 1 About this Fan 2 What’s in the Box 4

Pre-Installation Parts and Hardware 5 Tools Needed 6 Recommended Torque 6 Fan Diagram 7 Preparing the Work Site 8 Understanding Airflow Patterns 9

Mounting Method 1:

I-Beam

1. Attach Upper Yoke (to I-Beam) 11

Mounting Method 2:

Angle Irons

1. Select Proper Angle Irons 12

2. Pre-drill Angle Irons 13

3. Fasten Angle Irons Together (if span is longer than 8’) 13 4a. Fasten Single Angle Irons to Roof Structure Mounting Points 14 4b. Fasten Double Angle Irons to Roof Structure Mounting Points 15

5. Attach Upper Yoke (to Angle Irons) 16

Hanging The Fan 1. Attach Extension Tube (to Upper Yoke) 17

2. Secure Safety Cable 17

3. Attach Lower Yoke (to Extension Tube) 18

4. Attach Motor Frame (to Lower Yoke) 18

Installing Guy Wires 1. Attach Locking Carabiner to Motor Assembly 19

2. Attach Beam Clamp 19

3. Route Guy Wire through Gripple® 20

4. Install Three Remaining Guy Wires 20

Installing Airfoils 1. Attach Winglets to Airfoils 21

2. Position Airfoils 21

3. Attach Airfoils to Hub 22

Installing Hub Cover 1. Attach Hub Cover (to Junction Box) 23

2. Attach Center Cap (to Hub Cover) 23

Electrical Installation Electrical Installation Safety 24 Power Requirements 24 Wiring Data Cable for Wall Control 25 Mounting Controller 25 Delta Secondary 26 Branch Circuit Protection 27 Wiring: Fan Controller (200-250V & 400-480V Three Phase) 28 Wiring: Fan Controller with EMI Filter (200-250V & 400-480V Three Phase) 29 Wiring: Fan Controller (200-250V & 400-480V Three Phase) 30 Wiring: Fan Controller with EMI Filter (200-250V & 400-480V Three Phase) 31 Wiring: Fan Controller (200-250V Single Phase) 32

Getting the Most Out of Your Fan

Understanding Wall Control Operation 33 Cycling through Main LED Display Modes 33 Toggling the Fan’s Command Source 34 Starting, Stopping, and Direction Control 34 Changing the Fan Speed 34 Other Wall Control Functions 35

Getting the Most Out of Your Fan

Understanding and Clearing Fan Faults 35 Programming and Parameter Changes 35 Fan Maximum Operating Frequencies 35 Daisy Chaining 36 Basic Distributed I/O Interface; LOCAL Control 38 Basic Distributed I/O Interface; EXTERNAL Control 39 ESFR Interfacing 40 Basic Timer and Thermostat Interfacing 42 Fan Error Codes 43

Operating the Fan Heating Season 44 Cooling Season 44

User Servicing Annual Preventive Maintenance 45

Troubleshooting General Troubleshooting 46

Optional Parts Optional Parts Order Form 47

Warranty Big Ass Fans Warranty Policy 50 Warranty Claim Form Instructions 52 Acknowledgment & Return Instructions 53 Warranty Claim Form 54 Responsibility Agreement 55

Annual Maintenance Checklist

Annual Maintenance Checklist 56

Big Ass Fan Certified Installers

Check-In Procedure 58 Close-Out Procedure 60

8’ - 24’ POWERFOIL® X

Introduction Thank You Thank you and congratulations on your Big Ass Fans purchase! You now have an efficient and cost-effective way to stay cool in the summer and warm in the winter. The sleek revolutionary design of our fans will look great in any commercial or industrial setting.

More importantly, you can rest assured that you have a product that is backed by extensive research, thorough testing, and quality manufacturing.

If you have any questions or comments, contact us at 1-877-BIG-FANS or visit our Web site at www.BigAssFans.com.

Who We Are and What We Do FOUNDED IN 1999, Lexington, KY-based Big Ass Fan Company is the preeminent designer and manufacturer of high volume/low speed (HVLS) ceiling and vertical fans designed to improve facility and worker comfort in large commercial, industrial, agricultural, and institutional buildings worldwide.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

About this Fan

Powerfoil® X Specifications (with Powerfoil Winglets) FAN DIAMETER: 8 ft (2.4 m) 10 ft (3 m) 12 ft (3.6 m) 14 ft (4.3 m) AIR DISP. @ MAX SPEED: 41,905 cfm (19,777 l/s) 73,215 cfm (34,554 l/s) 103,460 cfm (48,828 l/s) 137,556 cfm (64,919 l/s) MOTOR SIZE: 1.0 HP (.75 kW) 1.0 HP (.75 kW) 1.0 HP (.75 kW) 1.5 HP (1.1 kW)

REQUIRED SUPPLY

CIRCUIT SIZE:

10A @ 200-250V 3Φ 10A @ 400-480V 3Φ 20A @ 200-250V 1Φ

10A @ 200-250V 3Φ 10A @ 400-480V 3Φ 20A @ 200-250V 1Φ

10A @ 200-250V 3Φ 10A @ 400-480V 3Φ 20A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

FULL LOAD CURRENT: 3.4A @ 200-250V,

1.7A @ 400-480V

3.4A @ 200-250V, 1.7A @ 400-480V

3.4A @ 200-250V, 1.7A @ 400-480V

5.6A @ 200-250V, 2.8A @ 400-480V

MAX RPM: 118 RPM 101 RPM 84 RPM 72 RPM

AIRFOIL LENGTH: 37.5 in (0.95 m) 49.5 in (1.26 m) 61.5 in (1.56 m) 73.5 in (1.87 m) FAN WEIGHT*: 272 lbs (123 kg) 289 lbs (131 kg) 305 lbs (138 kg) 322 lbs (146 kg)

SUGGESTED DISTANCE

FROM CEILING**: 3 ft (0.61 m) 3 ft (0.61 m) 3 ft (0.61 m) 4 ft (0.91 m)

(cont.)

FAN DIAMETER: 16 ft (4.9 m) 18 ft (5.5 m) 20 ft (6.1 m) 24 ft (7.3 m)

AIR DISP. @ MAX SPEED: 162,831 cfm (76,848 l/s) 200,817 cfm (94,775 l/s) 218,392 cfm (103,070 l/s)

345,941 cfm (163,266 l/s)

MOTOR SIZE: 1.5 HP (1.1 kW) 1.5 HP (1.1 kW) 2.0 HP (1.5 kW) 2.0 HP (1.5 kW)

REQUIRED SUPPLY

CIRCUIT SIZE:

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

FULL LOAD CURRENT: 5.6A@ 200-250V,

2.8A@ 400-480V

5.6A@ 200-250V, 2.8A@ 400-480V

6.4A@ 200-250V, 3.2A@ 400-480V

6.4A@ 200-250V, 3.2A@ 400-480V

MAX RPM: 63 RPM 55 RPM 47 RPM 42 RPM

AIRFOIL LENGTH: 85.5 in (2.17 m) 97.5 in (2.48 m) 109.5 in (2.78 m) 133.5 in (3.39 m) FAN WEIGHT*: 338 lbs (153 kg) 354 lbs (161 kg) 406 lbs (184 kg) 439 lbs (199 kg)

SUGGESTED DISTANCE

FROM CEILING**: 4 ft (0.91 m) 4 ft (0.91 m) 5 ft (1.22 m) 5 ft (1.22 m)

*Weight does not include mounting yokes or extension tube. Add 36 lbs for standard mount kit with 1 ft extension, and 4 lbs for every additional foot of extension length. Add 5 lbs more for large upper yoke.

**The distance of the fan from the ceiling should be measured from the top of the winglet to the ceiling.

CAUTION—Big Ass Fans requires that the Powerfoil X fan be supplied from one of the following types of transformers:

400-480V models: 480V / 277V Wye Secondary (Neutral not utilized) 200-250V models: 208V / 120V Wye Secondary (Neutral not utilized) 240V / 120V Delta Secondary (Wild / High Phase B)

Integration into any other power distribution scheme may result in improper fan operation or premature hardware failure! See

p. 24 for more information.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

About this Fan (cont.)

Powerfoil® X Specifications (with PowerfoilPlus Winglets) FAN DIAMETER: 10 ft (3 m) 12 ft (3.6 m) 14 ft (4.3 m) 16 ft (4.9 m) AIR DISP. @ MAX SPEED: 100,871 cfm (47,606 l/s) 132,536 cfm (62,550 l/s) 144,556 cfm (68,223 l/s) 184,944 cfm (87,284 l/s) MOTOR SIZE: 1.0 HP (.75 kW) 1.5 HP (1.1 kW) 1.5 HP (1.1 kW) 1.5 HP (1.1 kW)

REQUIRED SUPPLY

CIRCUIT SIZE:

10A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

FULL LOAD CURRENT: 3.4A @ 200-250V,

1.7A @ 400-480V

5.6A @ 200-250V, 2.8A @ 400-480V

5.6A @ 200-250V, 2.8A @ 400-480V

5.6A @ 200-250V, 2.8A @ 400-480V

MAX RPM: 84 RPM 72 RPM 63 RPM 56 RPM

AIRFOIL LENGTH: 49.5 in (1.26 m) 61.5 in (1.56 m) 73.5 in (1.87 m) 85.5 in (2.17 m) FAN WEIGHT*: 296 lbs (134 kg) 312 lbs (141 kg) 329 lbs (149 kg) 345 lbs (156 kg)

SUGGESTED DISTANCE

FROM CEILING**: 7 ft (2.1 m) 7 ft (2.1 m) 7 ft (2.1 m) 7 ft (2.1 m)

(cont.)

FAN DIAMETER: 18 ft (5.5 m) 20 ft (6.1 m) 24 ft (7.3 m)

AIR DISP. @ MAX SPEED: 210,046 cfm (99,111 l/s) 235,148 cfm (110,978 l/s)

368,516 cfm (173,920 l/s)

MOTOR SIZE: 1.5 HP (1.1 kW) 2.0 HP (1.5 kW) 2.0 HP (1.5 kW)

REQUIRED SUPPLY

CIRCUIT SIZE:

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

15A @ 200-250V 3Φ 10A @ 400-480V 3Φ 30A @ 200-250V 1Φ

FULL LOAD CURRENT: 5.6A @ 200-250V,

2.8A @ 400-480V

6.4A @ 200-250V, 3.2A @ 400-480V

6.4A @ 200-250V, 3.2A @400-480V

MAX RPM: 47 RPM 46 RPM 39 RPM

AIRFOIL LENGTH: 97.5 in (2.48 m) 109.5 in (2.78 m) 133.5 in (3.39 m) FAN WEIGHT*: 361 lbs (164 kg) 413 lbs (187 kg) 446 lbs (202 kg)

SUGGESTED DISTANCE

FROM CEILING**: 7 ft (2.1 m) 7 ft (2.1 m) 7 ft (2.1 m)

*Weight does not include mounting yokes or extension tube. Add 36 lbs for standard mount kit with 1 ft extension, and 4 lbs for every additional foot of extension length. Add 5 lbs more for large upper yoke.

**The distance of the fan from the ceiling should be measured from the top of the winglet to the ceiling.

CAUTION—Big Ass Fans requires that the Powerfoil X fan be supplied from one of the following types of transformers:

400-480V models: 480V / 277V Wye Secondary (Neutral not utilized) 200-250V models: 208V / 120V Wye Secondary (Neutral not utilized) 240V / 120V Delta Secondary (Wild / High Phase B)

Integration into any other power distribution scheme may result in improper fan operation or premature hardware failure! See

p. 24 for more information.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

(10) Airfoils

Airfoil Box

What’s in the Box The fan is shipped in multiple boxes. The larger box contains the motor/hub assembly, upper yoke (with beam clips and spacers), lower yoke, extension tube (if 3 ft or shorter in length) with attached safety cable, winglets (Powerfoil® or Powerfoil®Plus), hub cover (with junction box and center cap), wall control (with wall control mounting plate), and hardware. The smaller box contains the airfoils. If the extension tube is 4 ft or longer, it will also be shipped in a separate box. If a light was ordered, it will also be shipped in a separate box.

CAUTION: If you ordered multiple fans, be sure to keep the components of each fan together. The fans each have differently rated components that are not interchangeable.

Note: Dashed lines indicate internal boxes. Drawings below are not to scale.

(2) Lower Yoke

(2) Beam Clip &

(2) Spacer Upper Yoke

(10) Winglet3

Extension Tube4 & Safety Cable

Main Box

1. Adapter cable and CAT 5 patch cable are included in the box with the wall control. Adapter cable is connected to the wall control and must be utilized for proper fan operation. See p. 25 for installation instructions.

2. Airfoil retainers packed in bag with Installation Guide; winglet hardware packed in winglet box; hub cover hardware packed with junction box and center cap; guy wires (if ordered) are bagged separately in main box.

3. Powerfoil® (shown) or Powerfoil®Plus.

4. Safety cable is attached to extension tube. If extension tube is 4 ft or longer, it will be shipped in a separate box.

(2) Hardware2

Motor & Hub Center Cap

Hub Cover

Wall Control1

Wall Control Mounting Plate

Extension Tube Box

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Hardware

Beam Clip Hardware

(4) 1/2-13 x 2” GR 8 Bolt

(8) 1/2” Flat Washer

(4) 1/2-13 Nylock Nut

Single Pivot Hardware

(2) 1/2-13 x 5” GR 8 Bolt

(4) 1/2” Flat Washer

(2) 1/2-13 Nylock Nut

Lower Yoke Hardware

(2) 1/2-13 x 5” GR 8 Bolt

(4) 1/2” Flat Washer

(2) 1/2-13 Nylock Nut

Motor Hub Hardware

(4) 1/2-13 x 1 3/4” GR 8 Bolt

(8) 1/2” Flat Washer

(4) 1/2-13 Nylock Nut

Winglet Hardware

(10) 10-24 x 1/2” Bolt

(10) 10-24 x 3/4” Barrel

Airfoil Hardware

(20) 5/16-18 x 2” GR 8 Bolt

(40) 5/16” Flat Washer

(20) 5/16-18 Nylock Nut

Hub Cover Hardware1

(4) 8-32 x 3/8” Screw

(4) Gripple Hardware2

(1) Locking Carabiner

(1) 1/4” Beam Clip

(1) 1/4-20 x 1” Eyebolt

(1) 1/4-20 Hex Nut

(1) Gripple™

(1) Guy Wire

(4) Wire Rope Clip

Parts Included Note: Drawings below are not to scale.

Note: No hardware substitutions are acceptable.

1. The Hub Cover Hardware is packed in the hub cover box.

2. Guy wires are designed to constrain fan’s lateral movement and are only included in some fan packages. Big Ass Fans recommends using guy wires if the fan’s extension tube is 4 ft or longer, if the fan is exposed to high winds, or if the fan is close to any building fixtures. Gripple/Eyebolt hardware is bagged separately from hardware boards.

3. Safety cable is attached to extension tube.

4. Shackle included on hardware boards.

Airfoils

(10) Airfoils

(10) Powerfoil® Winglets

(10) Powerfoil®Plus Winglets

(10) Airfoil Retainers

Mounting

(2) Beam Clip & (2) Spacer

Upper Yoke (2) Lower Yoke

Motor & Hub Extension Tube, Safety Cable3, & Shackle4

Hub Cover

Hub Cover Center Cap or

Pre-Installation

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Recommended Torque

Application Thread Size Torque Mounting Bolts 1/2-13’’ UNC 40 ft·lb (54.2 N·m)

Airfoil Bolts 5/16-18’’ UNC 29 ft·lb (39 N·m)

Tools Needed

Mechanical Installation Electrical Installation Standard Wrench Set Phillips and Flat Head Screwdriver Standard Socket Set with Ratchet 1/4” Nut Driver Torque Wrench capable of 40 ft·lb (54.2 N·m) 5/16” Nut Driver Phillips and Flat Head Screwdriver Pair of #10 to #14AWG Crimpers Standard and Metric Allen Wrench Set Pair of Medium Size Channel Locks

Multimeter

Important Weights

Part Weight Part Weight

Single Pivot Mounting Kit (7/10) 32 lbs (14 kg)

Motor Assembly (1 HP) 204 lbs (93 kg) Motor Assembly (2 HP) 240 lbs (109 kg)

Single Pivot Mounting Kit (10/15) 37 lbs (16 kg)

Hub Cover 2 lbs (1 kg) Hardware 6 lbs (3 kg)

1 ft Extension 4 lbs (2 kg) Light Fixture (Optional) 14 lbs (6 kg) 2 ft Extension 8 lbs (4 kg) 8 ft Powerfoil foils 62 lbs (28 kg) 3 ft Extension 13 lbs (6 kg) 10 ft Powerfoil foils 80 lbs (36 kg) 4 ft Extension 17 lbs (8 kg) 12 ft Powerfoil foils 94 lbs (42 kg) 5 ft Extension 21 lbs (10 kg) 14 ft Powerfoil foils 110 lbs (49 kg) 6 ft Extension 25 lbs (11 kg) 16 ft Powerfoil foils 127 lbs (57 kg) 7 ft Extension 29 lbs (13 kg) 18 ft Powerfoil foils 141 lbs (63 kg) 8 ft Extension 33 lbs (15 kg) 20 ft Powerfoil foils 164 lbs (74 kg) 9 ft Extension 37 lbs (17 kg) 24 ft Powerfoil foils 195 lbs (88 kg) 10 ft Extension 42 lbs (19 kg)

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Fan Diagram

A. Safety Cable: A redundant safety feature that secures the fan to the mounting structure.

B. Upper Yoke: Secures the fan to the mounting structure and allows the fan to adjust its center of gravity.

C. Extension Tube: Extends the fan from the ceiling.

D. Lower Yoke: Connects motor/controller assembly to mounting assembly.

E. Motor/Controller Assembly: Includes the motor, on board controller, gearbox, lower cable, and hub (see

pp. 2-3 for more information).

F. Airfoil: Provides air movement. In the event of a collision, safety retainers secure the airfoils to the fan hub.

G. Winglet (Powerfoil® [shown] or Powerfoil®Plus):

Improves the efficiency of the fan by reducing drag.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Preparing the Work Site Mechanical Installation

• A 24-ft (7.3 m) Powerfoil fan (our largest model) weighs, at maximum, 475 lbs (215 kg). A scissor lift, or other suitable means for lifting the weight of the fan, and up to two installation personnel will be required.

• Big Ass Fans can only be hung from an I-beam or angle irons. If mounting from an I-beam, the I-beam must be part of the existing building structure. For specific requirements, see installation instructions starting on p. 11. Do not mount the fan to a single purlin, truss, or bar joist. Consult a structural engineer for installation methods not covered in the manual.

CAUTION: Mount fan only to an angle iron or I-beam.

Angle Iron

I-Beam

• To reduce the risk of injury to persons, install the fan so that the blades are at least 10 ft (3.05 m) above the floor.

• The fan installation area must be free of obstructions such as lights, cables, sprinklers, or other building structure. The fan blades should have at least 2 ft (0.61 m) of clearance from any obstructions.

• Big Ass Fans recommends that a fan be installed at a distance (from HVAC equipment) no less than 2x the fan’s diameter when measured from the center of the fan to the equipment. If the fan is mounted lower than an HVAC supply and return diffuser’s discharge, the fan should be installed no less than 2x the fan’s diameter from the diffuser when measured from the center of the fan to the diffuser. If the fan is mounted at the same height or higher than a downward discharge diffuser, the fan is recommended to be installed no less than 1x the fan’s diameter from the diffuser when measured from the center of the fan to the diffuser.

• The distance between multiple fans should be no less than 2.5x the fans’ diameter when measured from the centers of the fans.

• The mounting system must be able to withstand the torque forces generated by the fan. A 24-ft diameter fan generates nearly 300 ft·lb (406.7 N·m) of torque during operation.

• Fans mounted on lightweight I-beams (common in steel buildings) could cause the beam to flex and the fan to move significantly during operation. If this flexing causes a clearance problem, we suggest installing a stiffening strut to a nearby beam.

• If the fan’s extension tube is 4 ft (1.2 m) or longer, the fan’s lateral movement must be secured using guy wires (see p. 19 for more information). If the fan is close to any building fixtures it is recommended to secure the fan with guy wires as a safety measure.

• If installing a VESDA system, refer to the VESDA Installation Guide BEFORE hanging the fan.

Electrical Installation

• To reduce the risk of electric shock, wiring should be performed by a qualified electrician! Incorrect assembly can cause electric shock or damage the motor and the controller!

• The installation of a Big Ass Fan must be in accordance with the National Electrical Code, ANSI/NFPA 70-1999, and all local codes.

• AC supply feeds for one fan controller may share the same conduit with AC supply feeds for one or more controllers.

• All unused conductors that share a conduit with the AC supply feeds must be grounded on both ends.

• If required, a local disconnect should be installed per NEC and all local codes.

• Refer to specifications on p. 24 for appropriate circuit requirements.

• Each fan requires dedicated branch circuit protection.

• To avoid damage to the VFD and fan controller, test the VFD and fan controller with a test cable before wiring the CAT 5 cable!

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Understanding Airflow Patterns

Airflow with Streamlined Obstruction Obstructions on the floor tend to block the horizontally moving air. Thin or streamlined obstructions do not block much airflow, regardless of size. The air tends to flow smoothly around these obstructions, losing little momentum, and leaving only a small stagnant area behind the obstruction.

Overhead View

Overhead View

Side View

Overhead View

Overhead View

Airflow with Wide, Blunt Obstruction A wide, blunt, or flat-faced obstruction forces the air to change direction, turning upward and outward. There is a stagnant area behind these obstructions that is wider and higher than the obstructions themselves.

Overhead View

Overhead View

Side View

Side View

Airflow in an Enclosed Area The floor jet radiates outward until it reaches the walls. The walls deflect the jet upward. After it hits the ceiling, the upward flow is directed inward, back toward the low pressure area above the fan where it is then pulled back toward the floor. This creates a convection-like air current that gathers momentum. Once this current is established, the fan begins to move air outside of the current, escalating its cooling effects.

Airflow in an Open Area The airflow moves from the fan toward the floor.

Once the airflow hits the floor, it moves outward in all directions. When airflow is deflected off of the floor it is called a floor jet. The depth of this floor jet varies depending on the size and speed of the fan. A 20-ft (6-m) Big Ass Fan at standard speed creates a floor jet 9 ft (2.7 m) deep.

Airflow with Multiple Fans Where there are multiple fans appropriately spaced, the expanding jets of adjacent fans meet to create a pressure zone. The pressure zone acts like a wall, causing each fan to behave more like a single enclosed fan. Typically, a single fan’s performance will increase when working in conjunction with other fans.

Overhead View

Overhead View

Side View

Understanding Airflow Patterns (cont.)

Powerfoil®Plus The PowerfoilPlus hybrid airfoil creates a jet of air that flows outward from the fan at a 45° angle, ignoring floor obstructions and delivering airflow in a much broader pattern. The airflow generated from a 24-ft PowerfoilPlus fan can effectively maintain an operative temperature in an area up to 168 ft away from the fan.

The same principles of airflow apply to the PowerfoilPlus, but, when planning fan placement, consider its much larger coverage area as illustrated in the diagrams on the previous page.

Tips Below are some techniques that make a dramatic difference in congested areas of your facility. You can treat air like water and scoop, direct, and channel it to where you need it most. If you are using a PowerfoilPlus fan, you will notice that it delivers air from a much higher angle, resolving many of the obstacles outlined below.

• Make sure people are not hidden behind structures that would block airflow. This may seem obvious, but work areas are routinely blocked by shelving, crates, and machinery.

• Position large obstructions so that their smallest profile is perpendicular to the direction of air movement. For example, a sheet metal press brake might have five times the frontal area if it is facing the airflow rather than if it is turned sideways.

• Wherever possible, position welding curtains, partitions, sheet materials, etc., to scoop air into the work area rather than deflect it.

• Take advantage of the air moving near the floor by creating ground level openings in your work area. It is better to have a work area blocked by materials stacked to the ceiling with an opening below than to have low stacks 3 ft (0.9 m) to 6 ft (1.8 m) high sitting on the floor.

8’ - 24’ POWERFOIL® X

Mounting Method 1: I-Beam Big Ass Fans can only be hung from an I-beam or angle irons. See the following page for angle iron mounting instructions. Consult a structural engineer for installation methods not covered in this manual.

WARNING: The fan should not be installed unless the structure on which the fan is to be mounted is of sound construction, undamaged, and capable of supporting the loads of the fan and its method of mounting. A structural engineer should verify that the structure is adequate prior to fan installation. Verifying the stability of the mounting structure is the sole responsibility of the customer and/or end user, and Big Ass Fans hereby expressly disclaims any liability arising therefrom, or arising from the use of any materials or hardware other than those supplied by Big Ass Fans or otherwise specified in these installation instructions.

ATTENTION: It is not recommended to mount a Big Ass Fan to a fabricated I-beam.

ATTENTION: The I-beam on which the fan will mount must be part of the existing building structure.

ATTENTION: If installing a VESDA system, refer to the VESDA Installation Guide BEFORE hanging the fan.

1. Attach Upper Yoke (to I-Beam)

Measure the flange width of the I-beam from which the fan will be hung. Consult the tables and diagram below to determine what size upper yoke is included with your fan package. Select the upper yoke mounting holes that match the flange width of the I-beam.

CAUTION: Install the spacers only if the thickness of the I-beam flange exceeds 3/8” (1 cm). The mounting holes on the spacer are closer to one side than the other. Make sure this side is facing the I-beam.

Secure the upper yoke to the I-beam with the Beam Clip Hardware as shown. Tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Proceed to “Hanging the Fan” (p. 17).

Beam Clip Hardware (BAF-Supplied):

a. (4) 1/2-13 x 2” GR 8 Bolt

b. (8) 1/2’’ Flat Washer

c. (4) 1/2-13 Nylock Nut

d. (2) Beam Clamp

e. (2) Spacer

Small Upper Yoke 13-3/4’’ (45.7 cm) x 9 5/8” (24.4 cm)

I-Beam Flange Width

Upper Yoke Mounting Holes

5” (12.7 cm) - 6 5/8” (16.8 cm) inner holes

>6 5/8” (16.8 cm) - 8 1/4” (21 cm) middle holes

>8 1/4”(21 cm) - 9 7/8”(25 cm) outer holes

Large Upper Yoke 18-1/2’’ (57.7 cm) x 9 5/8” (24.4 cm)

I-Beam Flange Width

Upper Yoke Mounting Holes

9 7/8” (25 cm) - 11 3/8” (28.9 cm) inner holes

>11 3/8” (28.9 cm) - 13” (33 cm) middle holes

>13” (33 cm) - 14 5/8” (37.1 cm) outer holes

Upper Yoke (top view) outer hole middle hole inner hole outer hole middle hole inner hole

Upper Yoke (top view) outer holes inner holes middle holes

Side View a b c b d e

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

1. Select Proper Angle Irons

Note: Angle irons and angle iron hardware are not included with the fan.

CAUTION: Do not install the fan from a single purlin, truss, or bar joist.

CAUTION: Unsupported angle iron spans should not exceed 12 ft (3.7 m).

Follow the table below when selecting angle irons for fan installation.

Height

Width

Ø 9/16” (1.4 cm)

Thickness:

1/4” (6 mm)

Angle Iron Side View (see table for dimensions)

Thickness

Angle Iron Span (between mounting points)

Minimum Angle Iron Dimensions (W x H x T)

Number of Angle Irons Needed

6 ft (1.8 m) or less 2.5” (6.4 cm) x 2.5” (6.4 cm) x 0.25” (0.6 cm) 2 over 6 ft (1.8 m)-8 ft (2.4 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm) 2 over 8 ft (2.4 m)-12 ft (3.7 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm) 4* *2 pairs of angle irons. Pairs should be placed back to back and fastened in center (see step 2).

Mounting Method 2: Angle Irons If you are installing the fan to an I-beam and have attached the upper yoke (p. 11), proceed to “Hanging the Fan”

(p. 17).

WARNING: The fan should not be installed unless the structure on which the fan is to be mounted is of sound construction, undamaged, and capable of supporting the loads of the fan and its method of mounting. A structural engineer should verify that the structure is adequate prior to fan installation. Verifying the stability of the mounting structure is the sole responsibility of the customer and/or end user, and Big Ass Fans hereby expressly disclaims any liability arising therefrom, or arising from the use of any materials or hardware other than those supplied by Big Ass Fans or otherwise specified in these installation instructions.

WARNING: Never use beam clamps when mounting the fan to angle irons! Beam clamps are only intended for I-beam installations.

ATTENTION: If installing a VESDA system, refer to the VESDA Installation Guide BEFORE hanging the fan.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Mounting Method 2: Angle Irons (cont.)

3. Fasten Angle Irons Together (if span is longer than 8 ft)

If the angle iron span is 8 ft (2.4 m) or less, proceed to step 4a on the following page.

If the angle iron span is longer than 8 ft (2.4 m), it is necessary to use double angle irons.

Locate the center of the angle iron length. Drill Ø 9/16” (1.4 cm) hole through the center of the vertical wall of the angle iron. Drill a total of four angle irons.

Place two drilled angle irons back to back. Fasten the angle irons together with customer-supplied Grade 8 hardware.

Align the angle irons to each other and tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Repeat step for remaining two (2) angle irons.

Proceed to step 4b.

Grade 8 Hardware (Customer-Supplied):

a. (2) 1/2-13 Bolt

b. (4) 1/2” Washers

c. (2) 1/2” Nut

Side View ab bc

2. Pre-drill Angle Irons

Drill two Ø 9/16”(1.4 cm) holes exactly 5-3/8” (13.7 cm) apart in the centers of two angle irons.

Measure the distance between the mounting points of the roof structure that the angle irons will span. Measure the same distance on the angle irons and drill Ø 9/16” (1.4 cm) holes through each end of the angle irons. Drill holes in two angle irons if span is 8 ft (2.4 m) or less. Drill holes in 4 angle irons if span is greater than 8 ft (2.4 m).

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

4a. Fasten Single Angle Irons to Roof Structure Mounting Points

If installation requires double angle irons (i.e., span is greater than 8 ft [2.4 m]), proceed to step 4b.

CAUTION: Do not install the fan from a single purlin, truss, or bar joist.

CAUTION: The angle irons must be fastened to the roof structure at each end.

Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown.

ATTENTION: Do not tighten the hardware until the upper yoke has been mounted to the angle irons.

Proceed to step 5.

Grade 8 Hardware (Customer-Supplied):

a. (4) 1/2-13 Bolt

b. (8) 1/2” Washers

c. (4) 3” Square Washer (BAF-Supplied; see diagram)

d. (4) 1/2” Nut b a c b d

Mounting Method 2: Angle Irons (cont.)

3” (7.6 cm)

3” (7.6 cm)

Ø 9/16” (1.4 cm)

Thickness:

1/4” (6 mm)

Square Washer

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

4b. Fasten Double Angle Irons to Roof Structure Mounting Points

CAUTION: Do not install the fan from a single purlin, truss, or bar joist.

CAUTION: The angle irons must be fastened to the roof structure at each end.

Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown.

CAUTION: The angle irons with fan mounting holes should be positioned on the inside, facing each other.

ATTENTION: Do not tighten the hardware until the upper yoke has been mounted to the angle irons.

Grade 8 Hardware (Customer-Supplied):

a. (8) 1/2-13 Bolt

b. (16) 1/2” Washers

c. (8) 3” Square Washer (BAF-Supplied; see diagram)

d. (8) 1/2” Nut

A b a c b d

Mounting Method 2: Angle Irons (cont.)

3” (7.6 cm)

3” (7.6 cm)

Ø 9/16” (1.4 cm)

Thickness:

1/4” (6 mm)

Square Washer

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

5. Attach Upper Yoke (to Angle Irons)

Secure the upper yoke directly to the angle irons with the Beam Clip Hardware as shown. Consult the diagrams below for distances between the angle irons.

CAUTION: The angle irons should be aligned with the outermost holes of the upper yoke.

Tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Note: If you are installing a VESDA system with your fan, proceed to the VESDA Installation Manual.

CAUTION: After attaching the upper yoke to the angle irons, tighten all the bolts securing the angle irons to the roof structure to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Beam Clip Hardware (BAF-Supplied):

a. (4) 1/2-13 x 2” GR 8 Bolt

b. (8) 1/2’’ Flat Washer

c. (4) 1/2-13 Nylock Nut

Mounting Method 2: Angle Irons (cont.)

Note: Dashed lines represent angle irons.

Side View a b c b

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Hanging the Fan

2. Secure Upper Safety Cable

WARNING: The safety cable is a crucial part of the fan and must be installed correctly. If you have any questions, call Customer Service at 1-877-BIG-FANS.

Secure the safety cable to the I-beam or angle irons by wrapping the safety cable around it and securing the looped ends with the shackle as shown. The cable must be drawn tightly around the I-beam or angle iron, leaving as little slack as possible. If possible, the shackle should be on the topside of the I-beam or angle iron. Securely tighten the shackle.

Angle Iron MountI-Beam Mount Shackle

Direct Mount

ATTENTION: If installing a VESDA system, refer to the VESDA Installation Guide BEFORE hanging the fan.

1. Attach Extension Tube (to Upper Yoke)

Fasten the extension tube to the upper yoke with the Single Pivot Hardware as shown. Before tightening the bolts, allow the extension tube to hang freely and balance itself.

Tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Single Pivot Hardware (BAF-Supplied):

a. (2) 1/2-13 Nylock Nut

b. (4) 1/2’’ Flat Washer

c. (2) 1/2-13 x 5’’ GR 8 Bolt ba cb

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Hanging the Fan (cont.)

c a b b

3. Attach Lower Yoke (to Extension Tube)

Attach the lower yoke to the bottom of the extension tube with the Lower Yoke Hardware as shown.

Tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

Lower Yoke Hardware (BAF-Supplied):

a. (2) 1/2-13 x 5’’ GR 8 Bolt

b. (4) 1/2’’ Flat Washer

c. (2) 1/2-13 Nylock Nut b a c b

4. Attach Motor Frame (to Lower Yoke)

Attach the motor frame to the lower yoke with the Motor/Hub Hardware as shown. Do not rest the motor and hub unit on the ground! Position the lower cable between the lower yoke brackets as shown on the right.

CAUTION: Do not remove motor from its protective packaging prior to hanging it!

CAUTION: To prevent damage, avoid contact with the bottom of the motor and hub unit!

CAUTION: The motor frame is heavy. Use caution when raising it.

CAUTION: Secure all electrical cord/cable from interfering with this installation.

Tighten the bolts to 40 ft·lb (54.2 N·m) using a 3/4” socket with torque wrench.

ATTENTION: Do not discard the motor unit packaging and foam. It should be used if the fan is ever moved or relocated.

Motor/Hub Hardware (BAF-Supplied):

a. (4) 1/2-13 x 1 3/4” GR 8 Bolt

b. (8) 1/2’’ Flat Washer

c. (4) 1/2-13 Nylock Nut

ATTENTION: If installing a VESDA system with your Powerfoil X fan, refer to p. 3 of the VESDA Installation Guide for further instructions before installing guy wires and airfoils.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Installing Guy Wires Guy wires may not be included in your fan order. They are intended to constrain the fan’s lateral movement and are included with fans that have extension tubes 4 ft (1.2 m) or greater in length.

ATTENTION: If installing a VESDA system, do not install airfoils until all VESDA piping is installed.

1. Attach Locking Carabiner to Motor Assembly

Secure the locking carabiner to the guy wire clip on the motor as shown.

Securely tighten the carabiner.

2. Attach Beam Clamp

Attach the beam clamp to an I-beam or angle iron. The guy wire must be at a 30°-45° angle from the roof to the extension tube. Place the beam clamp accordingly.

Fasten the small eyebolt and nut onto the beam clamp. The nut will be on the outside of the beam clamp.

Loop the guy wire through its crimped end to secure it to the eyebolt as shown.

Gripple/Eyebolt Hardware (BAF-Supplied):

a. 1/4” Beam Clamp

b. 1/4-20 x 1” Eyebolt

c. 1/4-20 Hex Nut

d. Guy Wire

30˚- 45˚

Beam Clamp a dc

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

4. Install Three Remaining Guy Wires

Follow steps 1-3 to install the three remaining guy wires.

CAUTION: The guy wires should be spaced evenly around the fan and clear of the path the fan blades will rotate.

Evenly cinch all four guy wires into place using the Gripples. The wires should be taut.

Maintain a distance of 6”-8” between the Gripple and the frame mounting eyebolt.

CAUTION: Over-tightening the guy wires could throw the fan off balance.

Once all of the guy wires are taut, secure their loose ends with the wire rope clips as shown. The wire rope clip nearest the eyebolt should create a loop of approximately 2” in length. The second wire rope clip should be located 3”-4” from the first clip. Trim the cables so there is no more than 1”-3” extending from the end of the Gripple.

Ensure all electrical cords/cable are unobstructed by guy wire system.

Torque specification for wire rope clamps: 4.5 ft·lb

Wire Rope Clip

3. Route Guy Wire Through Gripple®

Route the guy wire through the Gripple, the carabiner on the motor, and back through the Gripple as shown.

ATTENTION: To back the guy wire out of the Gripple, insert 1/16 (1.5 mm) Allen wrench into the small hole on the Gripple.

ATTENTION: Do not tighten the Gripple until the remaining guy wires have been installed.

Installing Guy Wires (cont.)

Gripple

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Installing Airfoils Big Ass Fans recommends completing electrical installation (p. 24) before installing the airfoils.

WARNING: Disconnect power to the fan before installing the airfoils.

ATTENTION: If installing a VESDA system, do not attach airfoils until all VESDA piping is installed.

Powerfoil a b

PowerfoilPlus

1. Attach Winglets to Airfoils

Attach the winglet to the airfoil using the Winglet Hardware as shown. You will need to use both a Phillips head and flat head screwdriver to properly secure the fasteners.

ATTENTION: The Powerfoil® winglets and Powerfoil®Plus winglets will be attached the same way, using the same hardware kit.

Attach winglets to all 10 airfoils before attaching the airfoils to the fan.

Winglet Hardware Kit (BAF-Supplied):

a. (10) 10-24 x 1/2” Bolt

b. (10) 10-24 x 3/4” Barrel

2. Position Airfoils

Slide the airfoils onto the tabs of the fan hub. An airfoil will only attach to the fan hub in one direction. Do not force an airfoil into place.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

3. Attach Airfoils to Hub

WARNING: Disconnect power to the fan before installing the airfoils.

Attach the 10 airfoil retainers using the Airfoil Hardware. Moving clockwise around the fan hub, position the airfoil retainers end over end as shown. Hole A should be positioned over top of Hole B. Do not tighten the bolts until all the airfoil retainers have been attached!

First, tighten the bolts along the outside perimeter to 29 ft·lb (39 N·m) using a 1/2” socket with torque wrench.

Second, tighten the bolts along the inside perimeter to 29 ft·lb (39 N·m) using a 1/2” socket with torque wrench.

Airfoil Hardware Kit (BAF-Supplied):

a. (20) 5/16-18 x 2’’ GR 8 Bolt

b. (40) 5/16” Flat Washer

c. (20) 5/16-18 Nylock Nut

Hole A Hole B

Airfoil Retainer a b c

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

2. Attach Center Cap (to Hub Cover)

Snap the center cap into the hub cover.

1. Attach Hub Cover (to Junction Box)

Attach the hub cover to the junction box using the four (4) screws.

Note: Adhere to a 50-lb maximum attachment load.

Hub Cover Hardware:

(4) 8-32 x 3/8” Screw

Installing Hub Cover If your fan order included accessories (e.g., light, camera, etc.), consult the instructions packaged with those accessories.

WARNING: Disconnect power to the fan before installing the hub cover.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Electrical Installation Electrical Installation Safety

WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician! Incorrect assembly can cause electric shock or damage the motor and the controller! Hazard of electric shock!

WARNING: The installation of a Big Ass Fan must be in accordance with the requirements specified in this installation manual and with any additional requirements set forth by the national electric code (NEC), ANSI/NFPA 70-1999, and all local codes.

Code compliance is ultimately YOUR responsibility! Failure to comply with these codes could result in personal injury or property damage.

WARNING: The fan controllers contain high voltage capacitors which take time to discharge after removal of mains supply.

Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect (L1, L2, L3). Wait 3 minutes for capacitors to discharge to safe voltage levels. (Note: darkened display LEDs are not an indication of safe voltage levels.) Failure to do so may result in personal injury or death.

CAUTION: An incorrectly installed controller can result in component damage or reduction in the fan’s life. Wiring or application errors such as under-sizing the controller, incorrect or inadequate AC supply, or excessive ambient temperatures may result in a malfunction of the fan system. Verify correct voltage, phase, and horsepower before beginning installation!

WARNING: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans at 1-877-BIG- FANS if you have any questions regarding the electrical installation of this fan.

CAUTION: For use with manufacturer-supplied variable frequency drive only. Not for use with other speed control devices!

CAUTION: To avoid a short circuit, be very careful not to get any metal chips in the control!

CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure that is caused by improper installation.

CAUTION: Do not operate fan with a damaged cord or plug. Return fan to an authorized service facility for examination or repair.

ATTENTION: To avoid damage to the VFD and fan controller, test the VFD and fan controller with a test cable before wiring the CAT 5 cable! See the following page for more information.

Power Requirements

Power Requirements

Fan Size Controller HP (kW) Nominal Input Voltage Motor FLA Req’d Min. Branch

Circuit

8’ Powerfoil-12’ Powerfoil, 10’ PowerfoilPlus 1.0 (0.75)

200-250V 3Φ, 400-480V 3Φ 200-250V 1Φ

3.4A 1.7A 3.4A

10A 10A 20A

14’ Powerfoil-18’ Powerfoil, 12’ PowerfoilPlus-18’ PowerfoilPlus 2.0 (1.5)

200-250V 3Φ, 400-480V 3Φ 200-250V 1Φ

5.6A 2.8A 5.6A

15A 10A 30A

20’ Powerfoil-24’ Powerfoil, 20’ PowerfoilPlus-24’ PowerfoilPlus 2.0 (1.5)

200-250V 3Φ 400-480V 3Φ 200-250V 1Φ

6.4A 3.2A 6.4A

15A 10A 30A

All Fan Models:

1. Remote wall interface included (user-supplied parts required: 1 RJ-11 Connector, 1 RJ-45 Connector, CAT-5/5E cable up to 300 meters)

2. Optional EMI/RFI filter (see pp. 29 & 31): 200-250V 3Φ 400-480V 3Φ

22RF9P5AL 22RF5P7AL

*Both models suitable for Class A environments up to 100 meters and Class B environments up to 5 meters.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Wiring Data Cable for Wall Control WARNING: Failure to install the adapter cable may result in damage to the fan or controller and void all warranty!

The patch cable can be configured to 568A or 568B wiring standards. A 5-ft patch cable is included with the wall control for testing purposes prior to airfoil installation.

Mounting Wall Control

• Using the Mounting Plate as a template, mark the two screw locations and the one RJ-11 connector pass-through.

• Attach mounting plate to wall surface using BAF-supplied hardware (6-32 X 7/8” countersunk) and appropriate anchors. Connect the control cable coming through the wall, and snap the wall control into the mounting plate.

• Mount the wall controller so that the fan(s) it controls is visible from wall controller location.

7.

.4 c m

3.85” (9.8 cm)

Depth: 1” (2.5 cm)

Ø .15" (1.4 cm)

2.83

.06

.66

.75

.250

1.26

2.88

.40

3.25

.40

.37

1.20

R.20

3.84

7.25

2.75

.15 THRU CSK

TO .28

(TYP. 2 HOLES)

A

A

B B

.97

Mounting Plate (fits standard electrical wall box)Wall Controller

ATTENTION: To avoid damage to the VFD and fan controller, test the VFD and fan controller with a test cable before wiring the CAT 5 cable!

The controller cable to be installed between wall controller and the fan should be Category 5 or 5e cable. The distance limitation between the wall controller and the Powerfoil X fan is 1000 feet.

The short adapter cable included with the fan’s wall control enables the installer to use a CAT5 or CAT5e patch cable for communications between the controller and the wall pad. The RJ-11 connector should be used on the wall control end of the cable and the RJ-45 Connector should be used on the fan end of the cable. Note: For the RJ-11, Brown and Orange/White are not used.

WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED

8’ - 24’ POWERFOIL® X

Delta Secondary

There are many different arrangements available for industrial and commercial power…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .