Solicitation F17PS00727 Roof Replacement & Clerestory Ventilation Control at NCTC

Question and Answer Set 1

Question 1: The Terne-coated stainless steel that is specified for the coping is no longer available. What type of material would be acceptable to be used in its place?

Answer 1: A Tin/Zinc Alloy is acceptable:

http://freedomgrey.com/

Also, a Lead Coated Copper available at:

Cambridge Street Metal Riverside Sheet Metal Unimet Metal Supply Inc.

This information will be incorporated by amendment to the solicitation.

Question 2: I'm looking for clarity to be brought to the item for dry pipe fire sprinkler system modification. I'm surprise were not seeing a separate line item for this item.

Answer 2: The line items are separated out by the building for which work is being completed, and not a line item for every task to be completed. The specification section 21 13 16.00 20 states the dry pipe modifications are in the attic space in Instructional West and Instructional East. The costs for this work should be included within the costs for line items 0020 and 0030.