This document is a Lenel Security System Requirements specification for USDA APHIS (Animal and Plant Health Inspection Service) detailing security system infrastructure and installation requirements. The security system must be LENEL-compliant, with all devices installed by certified technicians and integrated into USDA APHIS's access control architecture. Specific requirements include installing FIPS-compliant dual technology card readers at primary exterior entrances, intrusion detection devices on other exterior doors, and alarm monitoring through Federal Protective Service Megacenter's.
The Lessor must prepare the space with several specific infrastructure components: a 4' x 8' fireproof plywood wall mount, a dedicated 20-amp electrical circuit, an analog POTS line for the alarm dialer, a LAN/WAN IT drop, and single-gang work boxes with conduit at card reader doors. The system components will remain USDA APHIS property and may be removed at lease end. USDA APHIS will be responsible for equipment maintenance and labor, while ensuring all security devices are compatible with their existing enterprise security system.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA APHIS Lenel Security System Requirements
LESSOR: _______ GOVERNMENT: _______
Security System – USDA, APHIS owns a security enterprise system. All devices installed must be compliant to that system. Currently LENEL is used by USDA, APHIS as a compliant system. All devices will be installed by certified technicians. All access control devices will be tied into the USDA, APHIS access control architecture. Compliant access control panels and FIPS compliant dual technology card readers will be installed at a minimum on the most frequently used exterior entrances. All other exterior doors will have intrusion detection devices; door contacts, glass breaks or motion sensors in each room accessible from the perimeter to detect intrusions into space through exterior windows and doors. Federal Protective Service (FPS) Megacenter’s, will provide alarm monitoring service. USDA, APHIS will be responsible for maintenance of equipment and labor. The system components will remain the property of USDA, APHIS, and may be removed by USDA, APHIS, at the end of the lease.
Lessor to prepare the space as follows:
- (1) 4' x 8', 5/8" fireproof plywood mounted on wall
- (1) 20 amp, 120VAC dedicated electrical circuit. Mounted on left side of security system panel plywood. 24" AFF, in 1900 box with cover. No receptacle - will be used to hard wire security power.
- (1) dedicated analog POTS line for security system alarm dialer
- (1) LAN/WAN IT drop mounted on left side of security system panel plywood. 54" AFF
- At each identified card reader door, install a single gang work box with conduit either stubbed above drop ceiling or if required a conduit path to the telco closet.
- Where possible have door sub-contractor prep doors/frames for specific security equipment application.