This document is a Security Unit Price List that is part of a federal lease solicitation for a 19,500 ABOA warehouse in Poplar Bluff, Missouri issued by the Department of Veterans Affairs.

The Security Unit Price List details the required security countermeasures for the facility, including emergency power, access control, intrusion detection, CCTV monitoring, and other physical security elements. The offeror must provide unit pricing for the tenant improvement and building-specific security items, which will be incorporated into the overall lease offer. The document specifies which security requirements are considered part of the building shell versus tenant improvements. Additional security measures may be required as determined by the government. The offeror is instructed to use this form to provide the requested pricing, which is subject to negotiation.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LESSOR: ________ GOVERNMENT: ________ SECURITY REQUIREMENTS (LEVEL I)

REV (06/22/18)

SECURITY REQUIREMENTS - FACILITY SECURITY LEVEL I

THESE PARAGRAPHS CONTAIN SECURITY REQUIREMENTS, AND, UNLESS INDICATED

OTHERWISE, ARE TO BE PRICED AS PART OF THE BUILDING SHELL. WHERE THEY ARE IN

CONFLICT WITH ANY OTHER REQUIREMENTS ON THIS LEASE, THE STRICTEST SHALL

APPLY.

DEFINITIONS:

CRITICAL AREAS - The areas that house systems that if damaged or compromised could have significant adverse consequences for the facility, operation of the facility, or mission of the agency or its occupants and visitors. These areas may also be referred to as “limited access areas,” “restricted areas,” or “exclusionary zones.” Critical areas do not necessarily have to be within Government-controlled space (e.g., generators, air handlers, electrical feeds which could be located outside Government-controlled space).

SENSITIVE AREAS – Sensitive areas include vaults, Sensitive Compartmented Information Facilities (SCIFs), evidence rooms, war rooms, and sensitive documents areas. Sensitive areas are primarily housed within Government-controlled space.

FACILITY ENTRANCES, LOBBY, COMMON AREAS, NON-PUBLIC, AND UTILITY

AREAS.

FACILITY ENTRANCES AND LOBBY

EMPLOYEE ACCESS CONTROL AT ENTRANCES (SHELL)

The Lessor shall provide key or electronic access control for the entrance to this building. All Government employees, under this lease, shall be allowed access to the leased space (including after-hours access).

COMMON AREAS, NON-PUBLIC, AND UTILITY AREAS.

PUBLIC RESTROOM ACCESS

The Government reserves the right to control access to public restrooms located within the Space.

SECURING CRITICAL AREAS

The Lessor shall secure areas designated as Critical Areas to restrict access:

A. Keyed locks, keycards, or similar security measures shall strictly control access to mechanical areas. Additional controls for access to keys, keycards, and key codes shall be strictly maintained. The Lessor shall develop and maintain accurate HVAC plans and HVAC system labeling within mechanical areas.

Exhibit D

B. Roofs with HVAC systems shall also be secured. Fencing or other barriers may be required to restrict access from adjacent roofs based on a Government Building Security Assessment. Roof access shall be strictly controlled through keyed locks, keycards, or similar measures. Fire and life safety egress shall be carefully reviewed when restricting roof access.

C. At a minimum, Lessor shall secure building mechanical and janitorial areas including sprinkler rooms, electrical closets, telecommunications rooms and janitor closets.

VISITOR ACCESS CONTROL

Entrances are open to the public during business hours. After hours, visitor entrances are secured, and have a means to verify the identity of persons requesting access prior to allowing entry into the Space.

INTERIOR (GOVERNMENT SPACE)

DESIGNATED ENTRANCES

The Government shall have a designated main entrance.

IDENTITY VERIFICATION

The Government reserves the right to verify the identity of persons requesting access to the Space prior to allowing entry.

FORMAL KEY CONTROL PROGRAM

The Government reserves the right to implement a formal key control program. The lessor shall have a means of allowing the electronic disabling of lost or stolen access media, if electronic media is used.

SITES

SIGNAGE

POSTING OF SIGNAGE IDENTIFYING THE SPACE AS GOVERNMENTAL

The Lessor shall not post sign(s) or otherwise identify the facility and parking areas as a Government, or specific Government tenant, occupied facility, including during construction, without written Government approval.

POSTING OF REGULATORY SIGNAGE

The Government may post or request the Lessor to post regulatory, statutory and site specific signage at the direction of the Government.

LANDSCAPING

LANDSCAPING REQUIREMENTS

Lessor shall maintain landscaping (trees, bushes, hedges, land contour, etc,) around the facility. Landscaping shall be neatly trimmed in order to minimize the opportunity for concealment of individuals and packages/containers. Landscaping shall not obstruct the views of security guards and CCTV cameras, or interfere with lighting or IDS equipment.

CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN

The Lessor shall separate from public access, restricted areas as designated by the Government, through the application of Crime Prevention Through Environmental Design (CPTED) principles by using trees, hedges, berms, or a combination of these or similar features, and by fences, walls, gates and other barriers, where feasible and acceptable to the Government.

SECURITY SYSTEMS

No requirements

STRUCTURE

Lessor shall provide written emergency shutdown procedures for air handlers.

OPERATIONS AND ADMINISTRATION

LESSOR TO WORK WITH FACILITY SECURITY COMMITTEE (FSC)

The Lessor shall cooperate and work with the buildings Facility Security Committee (FSC) throughout the term of the lease.

ACCESS TO BUILDING INFORMATION

Building Information—including mechanical, electrical, vertical transport, fire and life safety, security system plans and schematics, computer automation systems, and emergency operations procedures—shall be strictly controlled. Such information shall be released to authorized personnel only, approved by the Government, by the development of an access list and controlled copy numbering. The Contracting Officer may direct that the names and locations of Government tenants not be disclosed in any publicly accessed document or record. If that is the case, the Government may request that such information not be posted in the building directory.

Lessor shall have emergency plans and associated documents readily available in the event of an emergency.

CYBERSECURITY (SHELL)

A. Lessors are prohibited from connecting any portion of their building and access control systems (BACS) to any federally-owned or operated IT network. BACS include systems providing fire and life safety control, physical access control, building power and energy control, electronic surveillance, and automated HVAC, elevator, or building monitoring and control services (including IP addressable devices, application servers, or network switches).

B. In the event of a cybersecurity incident related to BACS, the Lessor shall initially assess the cyber incident, identify the impacts and risks to the Building and its occupants, and follow their organization’s cyber and IT procedures and protocols related to containing and handling a cybersecurity incident. In addition, the Lessor shall immediately inform the Lease Contracting Officer’s (LCO’s) designated representative, i.e., the Lease Administration Manager (LAM), about cybersecurity incidents that impact a federal tenant’s safety, security, or proper functioning.

C. Lessors are encouraged to put into place the following cyber protection measures in order to safeguard facilities and occupants:

1. Engineer and install BACS to comply with the Department of Homeland Security Industrial Control Systems Computer Emergency Response Team (DHS ICS-CERT) cyber security guidance and recommendations (https://ics-cert.us-cert.gov/Recommended-Practices).

2. Refer to the National Institute of Standards and Technology Cyber Security Framework (NIST- CSF) (https://www.nist.gov/cyberframework) and cybersecurity guidance in the DHS Commercial Facilities Sector-Specific Plan (https://www.dhs.gov/publication/nipp-ssp-commercial-facilities-2015) for best practices to manage cyber risks.

3. Encourage vendors of BACS to secure these devices and software through the following:

a. Develop and Institute a proper Configuration Management Plan for the BACS devices and applications, so that the system can be supported.

b. Safeguard sensitive data and/or login credentials through the use of strong encryption on devices and applications. This means using NIST- approved encryption algorithms, secure protocols (i.e., Transport Layer Security (TLS) 1.1, TLS 1.2, TLS 1.3) and Federal Information Processing Standard (FIPS) 140-2 validated modules.

c. Disable unnecessary services in order to protect the system from unnecessary access and a potential exposure point by a malicious attacker. Examples include File Transfer Protocol-FTP (a protocol used for transferring files to a remote location) and Telnet (allowing a user to issue commands remotely). Additionally, use of protocols that transmit data in the clear (such as default ZigBee) should be avoided, in favor of protocols that are encrypted.

d. Close unnecessary open ports to secure against unprivileged access.

e. Monitor and free web applications and supporting servers of common vulnerabilities in web applications, such as those identified by the (Open Web Application Security Project (OWASP) Top 10 Project (https://www.owasp.org/index.php/Category:OWASP_Top_Ten_Project).

f. Enforce Least Privilege, where proper permissions are enforced on a device or application so that a malicious attacker cannot gain access to all data. Enforcing Least Privilege will only allow users to access data they are allowed to see. Additional information can be found at https://www.beyondtrust.com/blog/what-is-least-privilege/

g. Protect against Insufficient User Access Auditing, where device or application does not have a mechanism to log/track activity by user. Enforce changing of factory default Username and Password to prevent unauthorized entry into the BACS system.

h. Use updated antivirus software subscription at all times. Kaspersky-branded products or services, prohibited from use by the Federal Government, are not to be utilized.

i. Conduct antivirus and spyware scans on a regular basis. Patching for workstations and server Operating System (OS), as well as vulnerability patching should follow standard industry best practices for software development life cycle (SDLC).

j. Discontinue the use of end of life (EOL) systems and use only applications/systems that are supported by the manufacturer.

k. Operating Systems must be supported by the vendor for security updates (e.g., do not use Windows Server 2003).

l. Proposed standard installation, operation, maintenance, updates, and/or patching of software shall not alter the configuration settings from the approved United States Government Configuration Baseline (USGCB) or tenant agency guidance (if applicable).

m. Disallow the use of commercially-provided circuits to manage building systems and install building systems on a protected network, safeguarded by the enterprise firewalls in place.

Workstations or servers running building monitor and control systems are not connected and visible on the public internet.

n. Systems should have proper system configuration hardening and align with Center for

Internet Security (CIS) benchmarks or other industry recognized benchmarks. Additional information can be found at https://www.cisecurity.org/cis-benchmarks/.

SECURITY UNIT PRICE LIST

Solicitation for Offers

DATE:

NAME:

The following security countermeasures are required by the Release for Proposals (RLP). Using this form, the offeror must quote unit prices on all security countermeasures identified in the RLP as "Tenant Improvement" or "Building Specific Security." The totals of these countermeasures will be entered on the GSA Form 1364 as appropriate by category. Shell security costs do not have to be quoted here, but must be included as part of the "Shell Rental Rate" on the GSA Form 1364. Quotes are subject to negotiation.

Refer to "Lease Security Standards" of the RLP for additional details. This form must be submitted with all offers.

Solicitation Reference (Lease Security Standards Section)

Include on Form 1364 as: Unit Price Quantity Total

1 Emergency Power to Critical Systems (e.g., alarm systems, monitoring systems, fire detection systems, entry control, lighting)

Shell Shell break-out not required

1a Emergency Power to Agency Special Equipment Tenant Improvement $ $ 2 Mechanical Areas and Building Roofs

(specifically: maintain controls for access to keys, keycards, and key codes; develop and maintain accurate HVAC diagrams and labeling; secured roof.)

Shell Shell break-out not required

Shell break-out not required 3 Access to Building Information Shell Shell break-out not required 4 Posting of Government Rules and Regulations Shell Shell break-out not required 5 Occupant Emergency Plan Shell Shell break-out not required 5a Sheltering in Place Plan Shell Shell break-out not required 6 Emergency Voice/Alarm Communication System Shell Shell break-out not required 7 Additional Security Measures as Determined by the

Government

[FPS and Realty Specialist list here]

Tenant Improvement (or Building Specific if ISC required)

8 Security Guard Service

(guards furnished by government) N/A N/A

9 X-ray Machine Building Specific or Tenant Improvement $ $

Magnetometer Building Specific or Tenant Improvement $ $

10 Entry Security: Intrusion Detection System Tenant Improvement $ $ 11 Entry Security: Peepholes Tenant Improvement $ $

12 Entry Security: Intercom Tenant Improvement $ $ 13 Entry Security: Entry Control with CCTV Tenant Improvement $ $ with Door Strikes Tenant Improvement $ $

14 Occupant/ Visitor Screening N/A N/A

15 Secure HVAC: Outdoor Air Intakes Building Specific or Tenant Improvement $

Secure HVAC: Dedicated HVAC for Lobbies, Mailrooms, and Loading Docks

Building Specific or Tenant Improvement $

17 Secure HVAC: Airborne Hazards Shell Shell break-out not required 18 Secure HVAC: Secure Return-Air Grilles Shell Shell break-out not required 19 Parking Security Requirements

Fencing to restrict access to official Government vehicles Building Specific $ $ Reserve parking spaces Building Specific $ $ Post signs for towing of unauthorized vehicles Building Specific $ $ ID system for authorized parking Building Specific $ $

20 CCTV Monitoring: Surveillance with Time Lapse Video Recording

Building Specific $ $

21 CCTV Monitoring: Post signs Building Specific $ $ 22 Shatter-resistant Window Protection Building Specific $ $

Installation Building Specific $ $

Certification Building Specific $ $ 23 Security Design Criteria for detail, see above "Additional Security Measures as Determined by the Government"

Building Specific $ $

24 Security Design Criteria: Setback Building Specific $ $ 25 Security Design Criteria: Façade Protection Building Specific $ $ 26 Security Design Criteria: Blast-Resistant Glazing Building Specific $ $ 27 Security Design Criteria: HVAC Shell Shell break-out not required

Security Design Criteria: Design and Engineering Documents N/A N/A

TOTALS: $ $

INITIALS: _____ LESSOR

Page 2 of 2 ______ GOV'T