This is a specification document for Section 26 0923 – Lighting Control Devices for the Anchor Bay School District's 2026 Additions and Renovation project covering Ashley Elementary, Naldrett Elementary, and Middle School South (Project Numbers 2023-001.2, 2023-006, and 2023-008). The project specifications require installation of occupancy sensors, outdoor motion sensors, time switches, in-wall time switches, outdoor photo controls, digital load controllers, and associated accessories. Occupancy sensors must be sourced from approved manufacturers including Acuity Brands, Inc. or Hubbell Incorporated and must be capable of sensing both major and minor motion according to published coverage areas. Outdoor motion sensors must be wet location listed with passive infrared technology, integral photocells for dusk-to-dawn operation, and adjustable turn-off delays up to 15 minutes. Digital load controllers must feature preconfigured, plug-and-play functionality with automatic self-addressing capabilities for wireless and wired applications. A pre-installation meeting must be convened minimum two weeks prior to commencing work and attended by contractors, system installers, factory representatives, and related trades representatives. Installation must not begin until final surface finishes and painting are complete, with all lighting control devices requiring compliance with NECA 1 and NECA 130 workmanship standards.

Manufacturer warranties of five years are required for occupancy sensors and outdoor utility grade locking receptacle-mounted photo controls. Products must comply with NFPA 70 (National Electrical Code), ANSI C136.10 and C136.24 standards for photocontrols, UL 773 for plug-in photocontrols, and UL 2043 for plenum-rated components. Submittals must include product data with detailed motion detection coverage range diagrams for occupancy sensors and shop drawings indicating locations, model numbers, and orientations of all devices. Field quality control testing must verify proper operation of occupancy sensors including time delays, ambient light thresholds, and optimal coverage, with results documented in written reports. Training of owner personnel must be provided for minimum two hours covering operation, adjustment, programming, and maintenance of all installed lighting control devices. No specific contract award date, term duration, or pricing information is contained in this specification document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANCHOR BAY SCHOOL DISTRICT

ASHLEY ELEMENTARY, NALDRETT ELEMENTARY, MIDDLE SCHOOL SOUTH

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 1 Lighting Control Devices

SECTION 26 0923

LIGHTING CONTROL DEVICES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Occupancy sensors.

B. Outdoor motion sensors.

C. Time switches.

D. In-wall time switches.

E. Outdoor photo controls.

F. Digital load controllers.

G. Accessories.

1.02 RELATED REQUIREMENTS

A. Division 01 - General Requirements: Project administrative and procedural requirements.

B. Section 26 0005 - Basic Electrical Requirements.

C. Section 26 0519 - Low-Voltage Electrical Power Conductors and Cables.

D. Section 26 0526 - Grounding and Bonding for Electrical Systems.

E. Section 26 0529 - Hangers and Supports for Electrical Systems F. Section 26 0533.16 - Boxes for Electrical Systems.

G. Section 26 0553 - Identification for Electrical Systems: Identification products and requirements.

H. Section 26 0800 - Electrical Commissioning and Testing Requirements.

I. Section 26 2726 - Wiring Devices: Devices for manual control of lighting, including wall switches, wall dimmers, and fan speed controllers.

1. Includes finish requirements for wall controls specified in this section.

2. Includes accessory receptacles, switches, dimmers and wall plates, to match lighting controls specified in this section.

J. Section 26 2813 - Fuses.

K. Section 26 5100 - Interior Lighting.

L. Section 26 5600 - Exterior Lighting.

M. Section 28 4600 - xxxFire Detection and Alarm. Interface with fire alarm system for emergency lighting.

1.03 REFERENCE STANDARDS

A. 47 CFR 15 - Radio Frequency Devices; current edition.

B. ANSI C136.10 - American National Standard for Roadway and Area Lighting Equipment -

Locking-Type Photocontrol Devices and Mating Receptacles - Physical and Electrical Interchangeability and Testing; 2023.

C. ANSI C136.24 - American National Standard for Roadway and Area Lighting Equipment - Nonlocking (Button) Type Photocontrols; 2020.

D. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

E. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.

F. NEMA EN 10250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2024.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 2 Lighting Control Devices

G. NEMA 410 - Performance Testing for Lighting Controls and Switching Devices with Electronic Drivers and Discharge Ballasts; 2023.

H. NEMA ICS 2 - Industrial Control and Systems Controllers, Contactors and Overload Relays Rated 600 Volts; 2008 (Reaffirmed 2020).

I. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

J. UL 773 - Plug-in, Locking Type Photocontrols for Use with Area Lighting; Current Edition, Including All Revisions.

K. UL 1008 - Transfer Switch Equipment; Current Edition, Including All Revisions.

L. UL 2043 - Fire Test for Heat and Visible Smoke Release for Discrete Products and Their

Accessories Installed in Air-Handling Spaces; Current Edition, Including All Revisions.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate placement of lighting control devices with millwork, furniture, equipment and other potential conflicts.

2. Coordinate placement of wall switch occupancy sensors with installed door swings.

3. Coordinate placement of occupancy sensors with millwork, furniture, equipment and other potential obstructions to motion detection coverage.

4. Coordinate placement of photo sensors for daylighting controls with windows, skylights, and luminaires to achieve optimum operation. Coordinate placement with ductwork, piping, equipment, or other potential obstructions to light level measurement.

5. Coordinate lighting control device product selections with luminaire characteristics; see Section 26 5100 and lighting fixture schedule.

6. Notify Architect of conflicts or deviations from Contract Documents to obtain direction prior to proceeding with work.

B. Sequencing:

1. Do not install lighting control devices until final surface finishes and painting are complete.

1.05 SUBMITTALS

A. Contractor shall provide submittals for equipment listed herein. Refer to Division 01 - General

Requirements for submittal procedures.

B. Product Data: Include ratings, operating modes or sequence of functions, configurations, standard wiring diagrams, dimensions, colors, service condition requirements, and installed features.

1. Occupancy Sensors: Include detailed motion detection coverage range diagrams.

C. Shop Drawings:

1. Occupancy Sensors: Provide lighting plan indicating location, model number, and orientation of each occupancy sensor and associated system component.

2. Digital Load Controllers: Provide dimensioned plan views indicating locations of system components, required clearances, and field connection locations. Include system interconnection schematic diagrams showing factory and field connections. Include manufacturer product characteristics and application instructions for wired and wireless applications, including start-up and commissioning.

3. Daylighting Controls: Provide lighting plan indicating location, model number, and orientation of each photo sensor and associated system component.

D. Field quality control reports.

1.06 QUALITY ASSURANCE

A. Comply with NFPA 70.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 3 Lighting Control Devices

B. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with minimum three years documented experience.

1.07 WARRANTY

A. Provide five year manufacturer warranty for occupancy sensors.

B. Provide five year manufacturer warranty for utility grade locking receptacle-mounted outdoor photo controls.

1.08 PRE-INSTALLATION MEETINGS

A. Convene minimum two weeks prior to commencing work of this section. Meeting shall be attended by Contractor(s), System Installer, Factory authorized manufacturer's representative, and representative of all trades related to the system installation.

B. Review installation procedures and coordination required with related work and the following:

1. Confirm the location and mounting of all devices, with special attention to placement of switches, dimmers and any sensors.

2. Review the specifications for low voltage control wiring and termination.

3. Discuss the functionality and configuration of all products, including sequences of operation, per design requirements.

4. Discuss requirements for integration with other trades.

C. Inspect and make notes of job conditions prior to installation:

1. Record minutes of the conference and provide copies to all parties present.

2. Identify all outstanding issues in writing designating the responsible party for follow-up action and the timetable for completion.

3. Installation shall not begin until all outstanding issues are resolved to the satisfaction of the Architect.

PART 2 PRODUCTS

2.01 LIGHTING CONTROL DEVICES - GENERAL REQUIREMENTS

A. Provide products listed, classified, and labeled as suitable for purpose intended.

B. Unless specifically indicated as excluded, provide components necessary for complete operating system including, but not limited to, conduit, wiring, connectors, hardware, and accessories.

2.02 OCCUPANCY SENSORS

A. Manufacturers:

1. Acuity Brands, Inc: www.acuitybrands.com.

2. Hubbell Incorporated: www.hubbell.com.

3. Source Limitations: Furnish products produced by single manufacturer and obtained from single supplier.

B. General Requirements:

1. Description: Factory-assembled commercial specification grade devices for indoor use capable of sensing both major motion, such as walking, and minor motion, such as small desktop level movements, according to published coverage areas, for automatic control of load indicated.

2. Sensor Technology:

a. Passive Infrared (PIR) Occupancy Sensors: Designed to detect occupancy by sensing movement of thermal energy between zones.

b. Ultrasonic Occupancy Sensors: Designed to detect occupancy by sensing frequency shifts in emitted and reflected inaudible sound waves.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 4 Lighting Control Devices

c. Passive Infrared/Ultrasonic Dual Technology Occupancy Sensors: Designed to detect occupancy using combination of both passive infrared and ultrasonic technologies.

d. Passive Infrared/Acoustic Dual Technology Occupancy Sensors: Designed to detect occupancy using combination of both passive infrared and audible sound sensing technologies.

3. Provide LED to visually indicate motion detection with separate color LEDs for each sensor type in dual technology units.

4. Operation: Unless otherwise indicated, occupancy sensor to turn load on when occupant presence is detected and to turn load off when no occupant presence is detected during adjustable turn-off delay time interval.

5. Dual Technology Occupancy Sensors: Field configurable turn-on and hold-on activation with settings for activation by either or both sensing technologies.

6. Turn-Off Delay: Field adjustable, with time delay settings up to 30 minutes.

7. Compatibility (Non-Dimming Sensors): Suitable for controlling incandescent lighting, low-voltage lighting with electronic and magnetic transformers, fluorescent lighting with electronic and magnetic ballasts, and fractional motor loads, with no minimum load requirements.

C. Wall Switch Occupancy Sensors:

1. General Requirements:

a. Description: Occupancy sensors designed for installation in standard wall box at standard wall switch mounting height with field of view of 180 degrees, integrated manual control capability, and no leakage current to load in off mode.

b. Unless otherwise indicated or required to control load indicated on drawings, provide line voltage units with self-contained relay.

c. Operation: Field selectable to operate either as occupancy sensor (automatic on/off) or as vacancy sensor (manual-on/automatic off).

d. Manual-Off Override Control: When used to turn off load while in automatic-on mode, unit to revert back to automatic mode after no occupant presence is detected during delayed-off time interval.

e. Finish: Match finishes specified for wiring devices in Section 26 2726, unless otherwise indicated.

2. Passive Infrared (PIR) Wall Switch Occupancy Sensors: Capable of detecting motion within area of 900 square feet.

3. Passive Infrared/Ultrasonic Dual Technology Wall Switch Occupancy Sensors: Capable of detecting motion within area of 900 square feet.

D. Ceiling Mounted Occupancy Sensors:

1. General Requirements:

a. Description: Low profile occupancy sensors designed for ceiling installation.

b. Unless otherwise indicated or required to control load indicated on drawings, provide low voltage units, for use with separate compatible accessory power packs.

c. Provide field selectable setting for disabling LED motion detector visual indicator.

d. Occupancy sensor to be field selectable as either manual-on/automatic-off or automatic on/off.

e. Finish: Refer to section 26 2726 for finishes.

2. Ultrasonic Ceiling Mounted Occupancy Sensors:

a. Standard Range Sensors: Capable of detecting motion within area of 500 square feet at mounting height of 9 feet, with field of view of 360 degrees.

b. Medium Range Sensors: Capable of detecting motion within area of 1,000 square feet at mounting height of 9 feet, with field of view of 360 degrees.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 5 Lighting Control Devices

c. Extended Range Sensors: Capable of detecting motion within area of 2,000 square feet at mounting height of 9 feet.

3. Passive Infrared/Ultrasonic Dual Technology Ceiling Mounted Occupancy Sensors:

a. Standard Range Sensors: Capable of detecting motion within area of 450 square feet at mounting height of 9 feet, with field of view of 360 degrees.

b. Extended Range Sensors: Capable of detecting motion within area of 1,200 square feet at mounting height of 9 feet, with field of view of 360 degrees.

E. Power Packs for Low-Voltage Occupancy Sensors:

1. Description: Plenum rated, self-contained low-voltage class 2 transformer and relay compatible with specified low-voltage occupancy sensors for switching of line-voltage loads.

2. Provide dedicated power packs for automatically controlled wiring devices.

3. Provide quantity and configuration of power and slave packs with associated wiring and accessories as required to control load indicated on drawings.

4. Input Supply Voltage: Dual rated for 120/277 V ac.

5. Load Rating: As required to control load indicated on drawings.

2.03 OUTDOOR MOTION SENSORS

A. Manufacturers:

1. Acuity Brands, Inc: www.acuitybrands.com/

2. Hubbell Lighting, Inc: www.hubbelllighting.com/

B. Description: Factory-assembled wet location listed device suitable for wall or ceiling/eave mounting, with integral swivel for field adjustment of coverage, capable of detecting motion for automatic control of load indicated.

C. Sensor Technology: Passive Infrared (PIR) designed to detect occupancy by sensing movement of thermal energy between zones.

D. Operation: Unless otherwise indicated, motion sensor to turn load on when motion is detected and to turn load off when no motion is detected during adjustable turn-off delay time interval.

E. Turn-Off Delay: Field adjustable, with time delay settings available up to 15 minutes.

F. Integral Photocell: For dusk to dawn operation.

G. Manual Override: Activated by switching power off to unit and then back on.

H. Load Rating: 1,000 W incandescent and fluorescent load at 120 V ac.

I. Coverage: Capable of detecting motion within distance of 50 feet at mounting height of 8 feet, with field of view of 270 degrees.

2.04 DIGITAL LOAD CONTROLLERS

A. Manufacturers:

1. Acuity

2. Hubbell Control Solutions: www.hubbell.com/hubbellcontrolsolutions/en/#sle.

3. Sensor Switch Inc: www.sensorswitch.com/#sle.

B. System Description:

1. Stand-alone system, including interconnected modules and accessories, for lighting and plug load low-voltage control as indicated on drawings, schedules, written sequences of operation, and reviewed shop drawings.

2. Product standard system configurations preconfigured out of box, plug-and-play, automatically self-addressing devices for communications, and without need to field configure or program features, or requiring device setting adjustments. LEDs on unit indicate operation and troubleshooting without software intervention.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 6 Lighting Control Devices

3. Provide quantity and configuration of power and slave packs, communication modules, and load expansion modules, including associated wiring, wired and wireless components, and accessories to control loads indicated.

C. General Requirements:

1. Listed for powering and controlling line-voltage loads, power packs, contactors, relays, and other lighting control devices.

2. Input Supply Voltage: Dual rated for 120/277 VAC.

3. Cabling Terminations:

a. Include line and load wiring leads.

4. Compatibility:

a. Compatible with luminaires specified with integral sensors; include auxiliary contact closure accessory components for controls indicated.

b. Compatible with wired and wireless sensors and communication protocols for controlling line-voltage loads.

1) Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits:

Comply with FCC requirements of 47 CFR 15, for Class B application.

c. Configurable for single room control as indicated from single digital load controller.

5. Provide UL 2043 plenum rated control unit with self-contained relay(s) and low-voltage class 2 transformer, compatible with specified wired and wireless sensors, components, and ballasts/drivers.

a. Comply with NFPA 70 for use in plenum spaces.

b. Provide UL 2043 plenum rating for associated system control components for control indicated.

6. Surface Mounting: Standard junction box attachments.

7. Provide one auxiliary contact closure output where indicated.

8. Minimum Load Rating: As required to control load indicated on drawings.

9. Control Inputs:

a. Digital: Two.

b. Analog: One.

10. Output Control Capability:

a. Single Zone Switching Modules: One programmable channel.

b. Multi-Zone Switching Modules: Up to three separately programmable channels.

11. Emergency Branch Circuit Loads:

a. Comply with NFPA 70 for controlling or bypassing emergency branch circuits as indicated.

b. Provide control devices listed for interfacing with fire alarm system for override operations.

1) See Section 28 4600.

c. Provide UL 1008 listed components.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that field measurements are as indicated.

B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate devices and conductors in accordance with NFPA 70.

C. Verify that openings for outlet boxes are neatly cut and will be completely covered by devices or wall plates.

D. Verify that final surface finishes are complete, including painting.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 7 Lighting Control Devices

E. Verify that branch circuit wiring installation is completed, tested, and ready for connection to lighting control devices.

F. Verify that service voltage and ratings of lighting control devices are appropriate for service voltage and load requirements at location to be installed.

G. Verify that conditions are satisfactory for installation prior to starting work.

3.02 PREPARATION

A. Provide extension rings to bring outlet boxes flush with finished surface.

B. Clean dirt, debris, plaster, and other foreign materials from outlet boxes.

3.03 INSTALLATION

A. Install lighting control devices in accordance with NECA 1 (general workmanship) and, where applicable, NECA 130, including mounting heights specified in those standards unless otherwise indicated.

B. Coordinate locations of outlet boxes as required for installation of lighting control devices; see Section 26 0533.16.

C. Maintain separation of remote-control, signaling, and power-limited circuits.

1. See manufacturer instructions and Section 26 0519 for control wiring conductors, wiring methods, and identification requirements.

D. Install lighting control devices in accordance with manufacturer's instructions.

E. Unless otherwise indicated, connect lighting control device grounding terminal or conductor to branch circuit equipment grounding conductor and to outlet box with bonding jumper.

F. Install lighting control devices plumb and level, and held securely in place.

G. Where required and not furnished with lighting control device, provide wall plate; see Section

26 2726.

H. Provide required supports; see Section 26 0529.

I. Where applicable, install lighting control devices and associated wall plates to fit completely flush to mounting surface with no gaps and rough opening completely covered without strain on wall plate. Repair or reinstall improperly installed outlet boxes or improperly sized rough openings. Do not use oversized wall plates in lieu of meeting this requirement.

J. Occupancy Sensor Locations:

1. Location Adjustments: Within design intent, reasonably minor adjustments to locations may be made in order to optimize coverage and avoid conflicts or problems affecting coverage.

2. Locate ultrasonic and dual technology passive infrared/ultrasonic occupancy sensors minimum of 4 feet from air supply ducts or other sources of heavy air flow and as per manufacturer's recommendations, in order to minimize false triggers.

K. Daylighting Control Photo Sensor Locations:

1. Location Adjustments: Within design intent, reasonably minor adjustments to locations may be made in order to optimize control and avoid conflicts or problems affecting proper detection of light levels.

2. Unless otherwise indicated, locate photo sensors for closed loop systems to accurately measure light level controlled at designated task location, while minimizing measured amount of direct light from natural or artificial sources such as windows or pendant luminaires.

3. Unless otherwise indicated, locate photo sensors for open loop systems to accurately measure the level of daylight coming into space, while minimizing measured amount of lighting from artificial sources.

2026 ADDITIONS AND RENOVATION

PROJECT NOs. 2023-001.2, 2023-006, 2023-008

FRENCH ASSOCIATES, INC.

architects planners interiors 26 0923 - 8 Lighting Control Devices

L. Unless otherwise indicated, install switches on load side of power packs so that switch does not turn off power pack.

M. Where indicated or required, provide cabinet or enclosure for mounting of lighting control device system components; see Section 26 0533.16.

3.04 FIELD QUALITY CONTROL

A. Inspect each lighting control device for damage and defects.

B. Test occupancy sensors to verify proper operation, including time delays and ambient light thresholds where applicable. Verify optimal coverage for entire room or area. Record test results in written report to be included with submittals.

C. Test daylighting controls to verify proper operation, including light level measurements and time delays where applicable.

D. Correct wiring deficiencies and replace damaged or defective conductors, cables, and lighting control devices.

3.05 ADJUSTING

A. Adjust devices and wall plates to be flush and level.

B. Adjust occupancy sensor settings to minimize undesired activations while optimizing energy savings, and to achieve desired function as indicated or as directed by Architect.

C. Adjust position of directional occupancy sensors and outdoor motion sensors to achieve optimal coverage as required.

D. Where indicated or as directed by Architect, install factory masking material or adjust integral blinders on passive infrared (PIR) and dual technology occupancy sensor lenses to block undesired motion detection.

3.06 CLEANING

A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.

3.07 CLOSEOUT ACTIVITIES

A. Demonstration: Demonstrate proper operation of lighting control devices to Architect, and correct deficiencies or make adjustments as directed.

B. Training: Train Owner's personnel on operation, adjustment, programming, and maintenance of lighting control devices.

1. Use operation and maintenance manual as training reference, supplemented with additional training materials as required.

2. Provide minimum of two hours of training.

3. Instructor: Qualified contractor familiar with the project and with sufficient knowledge of installed lighting control devices.

4. Location: At project site.

END OF SECTION 26 0923