- General Services Administration (GSA) seeks to lease the following space: El Paso, Texas
- Solicitation number
- 5TX0875
About this file
This document is an Agency Specific Requirements (ASR) exhibit for a federal lease space to accommodate the Federal Public Defender's Office in El Paso, Texas. The office requires 13,101 usable square feet (16,817 rentable square feet) of contiguous, self-contained space located on the second floor or above, within walking distance of the Albert Armendariz Sr. United States Courthouse. The space must maintain physical separation from the U.S. Attorney's Office, U.S. Marshals Service, U.S. Probation Office, Pretrial Services Office, Bureau of Prisons, and other law enforcement agencies due to the independent role of the Federal Public Defender in the legal process.
The facility must incorporate comprehensive security measures including a built-in screening counter in the reception area, duress alarm devices at multiple locations, card reader or keypad access controls, and a U.S. Marshals Service Entry Control Package with exterior camera, entry intercom, and electric strike door latch. The lessor must provide infrastructure (electrical and communications boxes, conduits, and power) for USMS installation of duress, entry control, and perimeter security systems. The office requires 43 secured reserved structured parking spaces and must feature acoustic confidentiality in all offices and conference rooms through slab-to-slab partitions with 5/8" drywall, sound gaskets on doors, and sound attenuation in ductwork. Additional specifications include a 300 usable square foot server room with dedicated 24/7 cooling (68-70 degrees), static dissipative tile flooring, specialized electrical outlets, copper grounding equipment, and sealed conduits. All interior doors must be solid core wooden (1.75 inches minimum thickness) with 16-gauge steel frames and dead bolt locks. The space must include cable trays, fiber optic capability, comprehensive electrical and data outlet infrastructure, and means for accepting and transporting furniture via freight elevator and loading dock. The space design allocates areas for executive offices with private conference rooms, supervisory attorney offices, line attorney offices, support staff, training/conference rooms, server room, work areas, break room, file storage, and modular cubicles with circulation space.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Exhibit C
LESSOR: ________ GOVERNMENT: ________
AGENCY SPECIFIC REQUIREMENTS (ASR)
FEDERAL DEFENDER’S OFFICE
EL PASO, TX
GENERAL
The Federal Public Defender Office provides counsel to people charged with federal criminal offenses who are financially unable to obtain adequate private representation.
The Federal Public Defender Office functions as an independent law office, it must be readily accessible to clients during and after normal working hours and must provide the appearance of a dignified and professional law office. The office requires public access to its reception area;
restricted access for office staff must be provided during both day and evening hours.
The Federal Public Defender Office must be distanced from the Office of the U.S. Attorney, USMS, U.S. Probation Office, Pretrial Services Office, Bureau of Prisons and any other law enforcement agency. This separation is important due to the different role the Federal Public Defender plays in the legal process. The Federal Public Defender is seeking 13,101 USF (16,817 RSF). The Federal Public Defender leased space shall be within walking distance of the Albert Armendariz Sr. United States Courthouse, where they principally conduct business.
The Federal Defender Office shall be located on the second floor of the building or above.
Office space must be contiguous, self-contained, and the public may not access space without authorized entry at the reception area door.
SECURITY
The screening counter in the reception area should be a built-in, stand-up counter. Additionally, duress alarm devices must be placed at the reception/public counter, the Federal Public Defender’s office and selected inner areas, depending on the layout of the offices. This area should also restrict access of the general office areas to authorized personnel only, by means of a card reader or keypad.
Offices, conference room, server room, IT switch closet, work room, file storage room, and the local area network room should either be keyed, card reader or keypad accessible.
The main entry shall have a USMS Entry Control Package (ECP) consisting of these components:
unobtrusive camera at the exterior, entry intercom, electric strike door latch. Connected to these at the reception desk will be a camera monitor, intercom, and a door release device. The equipment will be furnished and installed by the USMS. Other monitors, intercoms, and door releases will be required depending on the selected space.
Coordinate with the US Marshals Service (USMS) and provide the infrastructure (electrical & communications) boxes, conduits, and power for USMS’s sub-contracted provision of and installation of duress (see first bullet point above), entry control, and perimeter security systems.
PARKING SPACE
The Federal Public Office requires 43 secured reserved structured parking spaces.
Parking spaces would be utilized for judges, court unit executives, and staff using personal vehicles office business.
ACOUSTICS
All office and conference rooms must be designed to provide acoustic confidentiality.
All slab-to-slab partitions to be 5/8” drywall, taped, ‘mudded’ each side and caulked at the base and top of the wall with acoustical batt insulation at full height.
Provide sound gaskets on all office doors, 2’ overlay of sound batts over walls, above ceiling for all offices, sound attenuation in duct work for all offices and conference rooms
DESIGN/FINISH
It is preferred that the main reception area be adjacent to the open secretarial area. It is also preferred that the main conference room be near the reception area.
Any means of access to the local area network room and IT switch closets through the ceiling plenum, pipe chase or other similar spaces must be eliminated. The construction of walls will extended from structural floor deck to structural ceiling or roof deck with fire-rated conduits.
The exhibit storage, client property storage and supply storage rooms should all have space for adjustable-height, open shelving.
All doors will be solid core wooden doors not less than 1.75 inches thick, hung in 16-gauge steel frames. All perimeter doors will be secured with dead bolt locks.
All walls should be a 5/8-inch gypsum board with paint finish except for the main conference room which will have vinyl wall covering or paint, to be selected by the tenant.
The carpet should be commercial grade wall-to-wall carpeting or commercial carpet squares, to be selected by the tenant.
SPACE DESIGN:
NETWORK/SERVER ROOM AND SWITCH CLOSETS:
● The Federal Defender space requirement includes a 300 USF computer room with 24/7 cooling at temperatures ranging from 68-70 degrees.
● Provide dedicated, supplemental A/C in the server room with tenant sub-meter and thermostat. A/C in the server room shall be maintained by the lessor.
● The maximum heat load of computer equipment is 23,000 BTUs per hour with a 40% load of 7,200 degrees.
● Provide and install ¾” thick F.R. treated, non-com painted plywood equipment boards.
Mount from 4” AFF to 8’-4” AFF from wall to wall in the server room and switch closets.
Agency will make this determination when a layout is provided to them.
● Static dissipative tile flooring with copper grounding straps will be provided and installed per manufacturer’s recommendations.
● Install four (4) Dedicated NEMA 5-20R 120 Volt / 20 AMP dedicated duplex electrical outlets mounted on ceiling in the server room, in a location determined by the agency when a layout is provided to them.
● Quantity Nema 5-20R duplex electrical outlets: Agency will make this determination when a layout is presented to them.
● Provide and Install Copper, 10 in Grounding Bar Lg, (16) 1/4 in Grounding Bar. Agency will make location determination when a layout is provided.
● Provide a 3” sealed conduit with pull string from server room to demark.
● Provide 2” sealed conduit with pull string from server room to switch closets.
● USMS will provide power plan requirements to lessor for USMS equipment rack in server room.
● The room should also maintain 60 degrees relative humidity per the Server Room Analysis below:
SPECIAL IT REQUIREMENTS OR STANDARDS
● Are cable trays required? Yes – to be installed by lessor
● Who is purchasing data cable? Agency
● Who is responsible for installing the data cable? Agency
● Who is purchasing telecommunications cable? Agency
● Who is responsible for installing the telecommunications cable? Agency
● Are sealed conduits required for wall mounted outlets? Yes, back to demark.
● Who is responsible for termination data/telecommunication connections? Agency
● Lessor is responsible for purchasing and installing all back boxes and conduit for data and telecommunications cable. The agency will hire its own contractor to pull and terminate wire.
SPECIAL REQUIREMENTS
● Adjacencies: Locate Clerical near reception. Locate AFD Offices together with admin and paralegal adjacent to each office.
● Breakroom to have sink, counter tops, base cabinets (approx. 8 LF of cabinet space) microwave shelf, area for fridge (provided by agency).
● Provide sound gaskets on all office doors, 2’ overlay of sound batts over walls, above ceiling for all offices, sound attenuation in duct work for all office, conference and audio tape listening room.
● Provide MEDECO locks on all perimeter doors to the office suite.
● MECO shades preferred
● Carpet and/or Luxury Vinyl Tile (LVT) – ceramic tile in restrooms
ELECTRICAL REQUIREMENTS
● Quantity Nema 5-20R duplex electrical outlets (Offices): Agency will make this determination when a layout is presented to them.
● Quantity data outlets (Offices): Agency will make this determination when a layout is presented to them. All data outlets must have 1” conduits with pull string from outlet to junction box and/or above accessible ceiling.
● Provide electrical outlets for copier, FAX, shredder, printer, microwave, coffee maker, and fridge.
The agency will make determination of the location of electrical outlets for work room equipment (i.e. copier, shredder, etc) when a layout is presented to them.
● A large Training/Conference room and Private Executive Conference room will have Television and VTC equipment Provide electrical for this equipment, (1) tele/data outlet and (1) duplex outlet on each wall and 66” AFF on wall selected for mounted TV. Proper support/bracing will be installed to support mounted TV. The agency will make location determination when a layout is presented to them.
● A large Training/Conference room and Private Executive Conference room will have a flush floor outlet provided for electrical and data runs with a secured conduit.
● Reception, Library, and Conference Room areas: Provide (1) tele/data outlet and (1) elect outlet on each wall. Provide convenience outlets in corridors for janitorial services.
● Sealed conduit for telecommunications.
● Building must have the potential to bring in fiber optic cabling if multi-mode system not already in place
ROOM SCHEDULE AND DETAILS
● Flooring Type: Carpet and/or Luxury Vinyl Tile (LVT) – ceramic tile in restrooms
● Wall Finish: Paint
● Wall Type (Interior Partitions): Demising partitions shall be slab-to-slab with
“confidential” privacy level (NIC 55). Interior walls shall extend 6 inches above acoustical ceilings and have sound insulation in walls.
● Ceiling Height : 9 Feet
● Ceiling Type: Acoustical Tile
OTHER REQUIREMENTS
● The agency requires means to accept and transport furniture within the building such as a freight elevator and loading dock.