Exhibit B - Agency Specific Requirement.pdf
PDF 22 MB Posted
- Attached to
- Vet Center space needed in Melbourne FL
- Solicitation number
- 36C24W2R0061
- Issued by
-
Department of Veterans Affairs
About this file
This document is a Statement of Work (SOW) containing Agency Specific Requirements for a Vet Center lease location in Melbourne, Florida, issued by the Department of Veterans Affairs (VA) Readjustment Counseling Service (RCS). The lessor is responsible for providing a fully serviced space with all materials, parts, and labor for completion, including utilities, janitorial services, basic cable, guest Wi-Fi, and security and CCTV system monitoring and maintenance paid through annual rent. The space must comply with both RCS standards and GSA Global Lease requirements, with the higher standard applied in cases of conflict.
The SOW specifies detailed room-by-room requirements for a modern vet center facility including a reception area, multiple group therapy rooms (quantity three), individual offices, restrooms, break room, supply and storage rooms, and telecommunications enclosure. Each room designation includes precise specifications for flooring (luxury vinyl tile or carpet tile), wall finishes (painted with two finish coats), acoustical ceiling tiles with high sound absorption ratings, electrical outlets (data and power), lighting with occupancy sensors, and sound isolation requirements (STC 45 in offices, group rooms, and restrooms). Critical infrastructure includes a video surveillance system with 30-day time-lapse recording, access control utilizing wireless key fobs, intrusion detection with motion sensors, nurse call systems, and duress alarm systems with both hardwired and wireless transmitters. The lessor must also provide specific furniture and appliances including kitchen equipment (refrigerator, microwave, dishwasher, sink), provide independent network switches and IP addresses for security and communication systems, and conduct quarterly security system testing with reports submitted to the VA. Additionally, the document includes comprehensive exterior and interior signage guides specifying Vet Center branding requirements, including preferred channel letter signage on raceways with specific color specifications (Pantone colors for red, dark blue, and light blue), ADA-compliant interior signage with raised acrylic and braille, and door decal specifications with the Vet Center logo and contact information.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10RCS/STA703 VET CENTER Page 1 | 18 Lessor Initials: ________________Date: ______________
RCS CAPITAL ASSET MANAGEMENT 11.06.2025
READJUSTMENT COUNSELING SERVICE – Melbourne VET CENTER
STATEMENT OF WORK - AGENCY SPECIFIC REQUIREMENTS
The Lessor shall provide all materials, parts, and labor to complete the space and room requirements.
The Vet Center Agency Specific Requirements will be used in conjunction with the standards and specifications found in the Request for Lease Proposal and the GSA Global Lease. If any conflict between standards or regulatory framework is found, the offeror must use the higher standard and follow the more stringent regulation.
The Lease shall be Fully Serviced with the following services paid for/provided by the Lessor through the annual rent.
1. Utilities.
2. Janitorial.
3. Basic Cable to include local channels in the Waiting Area (Lobby) and three Group Rooms.
4. Guest Business High-Speed Internet Wi-Fi.
5. Security and CCTV System monitoring and maintenance to include software/hardware updates provided by the Lessor and paid through the annual rent.
6. Security System tested quarterly by the Lessor; a copy of the report sent to VA.
A. SPACE REQUIREMENTS.
1. Space design to provide maximum co-location of staff offices and group rooms. Refer to RLP Exhibit, Space Requirements for additional details required for this location.
10RCS/STA703 VET CENTER Page 2 | 18 Lessor Initials: ________________Date: ______________
B. ROOM REQUIREMENTS Room #
1. EXTERIOR
Electric. a. Mobile Vet Center (MVC). One (1) Exterior 50 AMP outlet with dedicated circuit for the (MVC) enclosed with weatherproof and locking RV Power Outlet Box; location determined by the VA.
Safety. b. Cameras. Exterior cameras provide unobstructed monitoring of pedestrian entrances, exits, and government vehicles.
10RCS/STA703 VET CENTER Page 3 | 18 Lessor Initials: ________________Date: ______________
Other. c. Flagpole.
- Ability to display an 4x6 American Flag and a 3x5 POW flag underneath, near building main entrance.
- Illuminated during the hours of darkness.
- Minimum Height 20 feet.
- Stainless steel or aluminum in material as per VA Standard Specification section 10 75 00.
2. ENTRANCE
Door. a. Power Assisted Front Entrance Door or Automatic Single Slide Automatic Door System with Safety Sensors and Hardware.
Key Control Access. b. Access-controlled door that utilizes a wireless key fob for entry.
c. Video Intercom system to allow VA staff to view, communicate, and open the door remotely before allowing access to space.
- Compact intercom - Exterior Entrance (Qty 1)
- Compact intercom - Master Station (Qty 2); specific location determined by VA.
- Compact intercom - Portable Device. (Qty 2)
- Example Brand Name Equal. https://www.2n.com/en-US/products/indoor-stations/2n-indoor-compact/
Other. d. Vestibule. Located at the public entrance where weather conditions and heat loss are important factors.
3. LOBBY, WAITING AREA
https://www.2n.com/en-US/products/indoor-stations/2n-indoor-compact/
10RCS/STA703 VET CENTER Page 4 | 18 Lessor Initials: ________________Date: ______________
Floor. a. Luxury Vinyl Tile/Plank 5mm thickness + 20mil wear layer; continues through hallway corridor.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent wall color; location determined by VA.
c. Wall backing and mounting materials for VA furnished TV installed by Lessor; location determined by VA.
Ceiling. d. Acoustical Ceiling Panels HIGH-NRC/HIGH-CA; standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. e. Direct window access.
f. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.
Door. g. Full-length glass panel. (Qty 2).
Sound Isolation. h. N/A.
Data. i. One (1) data outlet behind TV; 60” from the floor to center of TV.
Electric. j. One (1) per wall duplex outlet.
k. One (1) quadruplex behind the TV; height 60” from the floor to center of TV.
l. Cable TV wall jack behind the TV; height 60” from the floor to center of TV.
Lighting. m. Multilevel Switching, Dimming & Occupancy.
Safety. n. Cameras. Interior cameras to provide unobstructed monitoring of entrances.
o. EXIT signs, luminated with battery backup.
10RCS/STA703 VET CENTER Page 5 | 18 Lessor Initials: ________________Date: ______________
Key Control Access. p. Access-controlled door that utilizes a wireless key fob for entry.
q. HID Contactless Readers for PIV Solutions https://www.alldataresource.com/assets/hid_global/HID-pivCLASS-Contactless-Readers-Datasheet.pdf
Other. r. Corridors are minimum of 5 feet in clear width.
s. Vinyl Corner Guards. Mounted at height 48” from top of vinyl base in hallways.
t. Wall Backing and Mounting Materials to support 60” VA furnished television installed by Lessor; location determined by VA.
u. Universal Thermostat locking clear cover.
v. Drinking Fountain. Wall hung stainless Bottle Filling Station Single ADA Cooler; Maintenance/filter replacement by Lessor.
Picture Examples.
3. RESTROOM (UNISEX)
Floor. a. Porcelain Floor Tile.
Wall. b. Porcelain Wall Tile 4 feet up from the floor, with tile accent strip.
c. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. d. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC; standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. e. N/A.
Door. f. Power Assisted Door for one (1) Unisex/Family Restroom or for both the Women’s and Men’s Restroom accessible from the lobby.
https://www.alldataresource.com/assets/hid_global/HID-pivCLASS-Contactless-Readers-Datasheet.pdf
10RCS/STA703 VET CENTER Page 6 | 18 Lessor Initials: ________________Date: ______________
Sound Isolation. g. STC 45.
Data. h. N/A.
Electric. i. One (1) GFI duplex outlet.
Lighting. j. Occupancy Sensor, 30-minute time delay.
Safety. k. ADA handicap accessibility to include grab bars at commode for one (1) Unisex/Family Restroom or for both the Women’s and Men’s Restroom accessible from the lobby.
l. Nurse call tone-visual system. The notification sounds in corridors with a visual call light above the room.
m. Example. https://www.tektone.com/products/nurse-call-systems/tek-care120/
Key Control Access. w. Access-controlled door that utilizes a wireless key fob for entry.
Other. n. Toilet. Commercial Grade with automatic toilet flushers.
o. Toilet Paper Dispenser. Dual roll
p. Toilet Paper Cover Dispenser. Provided, maintained, and refilled by the Lessor.
q. Paper Towel Dispenser/Waste Receptacle. Recessed Convertible Paper Towel Dispenser/Waste Receptacle.
r. Soap Dispenser. Automated touchless dispenser provided, maintained, and refilled by the Lessor Vanity with sink and structure to hide exposed plumbing.
s. Mirror. Minimum of 24"x 36" over sink
t. Vanity.
u. Coat Hooks. Three (3) coat hooks; location determined by the VA.
v. Baby changing station for one (1) Unisex/Family Restroom or for both the Women’s and Men’s Restroom accessible from the lobby.
w. Exhaust Vent.
5. RECEPTION / PROGRAM
SUPPORT ASSISTANT
Floor. a. Luxury Vinyl Tile 5mm thickness + 20mil wear layer.
https://www.tektone.com/products/nurse-call-systems/tek-care120/
10RCS/STA703 VET CENTER Page 7 | 18 Lessor Initials: ________________Date: ______________
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC, standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. d. Horizontal manual roller shades with solar glare and heat reduction.
e. Glass transaction window to the lobby area.
Door. f. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Sound Isolation. g. STC 45.
Data. h. Two (2) data outlets next to quad Electrical outlets at program support assistant.
i. Two (2) data outlets at counter height at reception counter.
Electric. j. Two (2) quad outlets next to duplex Data outlets.
k. Two (2) duplex outlets at counter height at reception counter.
Lighting. l. Multilevel Switching, Dimming & Occupancy.
Safety. m. Duress Alarm. Duress Alarm Wireless transmitter device.
n. Video Intercom. System to allow VA staff to view, communicate, and open the door remotely before allowing access to space.
- Compact intercom - Exterior Entrance (Qty 1)
- Compact intercom - Master Station (Qty 2); specific location determined by VA.
Key Control Access. o. Access-controlled door that utilizes a wireless key fob for entry.
10RCS/STA703 VET CENTER Page 8 | 18 Lessor Initials: ________________Date: ______________
Other. p. Countertop. Solid Surface Quartz Countertop utilizing concealed mounting brackets.
q. Reception area is contiguous with the Program Support Assistant, examples below.
6. OFFICE Quantity: Refer to the Exhibit – Space Requirements; the requirements for each room.
Floor. a. Carpet Tile.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC, standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. d. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.
Door. e. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Sound Isolation. f. STC 45.
Data. g. Two (2) data outlets next to quad Electrical outlets.
Electric. h. Two (2) quad outlets next to duplex Data outlets.
i. Two (2) duplex outlets on the opposite walls.
j. Typical office layout diagram with data and electric placement.
10RCS/STA703 VET CENTER Page 9 | 18 Lessor Initials: ________________Date: ______________
Lighting. k. Multilevel Switching, Dimming & Occupancy.
Safety. l. Duress Alarm. Wireless transmitter device.
Key Control Access. m. Access-controlled door that utilizes a wireless key fob for entry.
Other. n. Coat Hooks. Three (3) coat hooks; location determined by the VA.
Picture Examples.
7. GROUP THERAPY ROOM Qty: Three (3) Group Rooms - requirements for each room.
Floor. a. Carpet Tile.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC, standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. d. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.
Door. e. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Sound Isolation. f. STC 45.
Data. g. Four (4) data outlets; one on each wall.
Electric. h. Four (4) duplex outlets; one on each wall, next to data outlets.
i. Wall backing and mounting materials for VA furnished TV installed by Lessor; location determined by VA.
j. One (1) quadruplex behind the TV; height 60” from the floor to center of TV.
k. Cable TV wall jack behind the TV; height 60” from the floor to center of TV.
Lighting. l. Multilevel Switching, Dimming & Occupancy.
10RCS/STA703 VET CENTER Page 10 | 18 Lessor Initials: ________________Date: ______________
Safety. m. Duress Alarm. Hardwired transmitter device with protective clear cover.
Key Control Access. x. Access-controlled door that utilizes a wireless key fob for entry.
Other. n. Coat Hooks: Three (3) coat hooks; location determined by the VA.
8. KITCHEN BREAK ROOM
Floor. a. Luxury Vinyl Tile 5mm thickness + 20mil wear layer.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC, standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. d. N/A.
Door. e. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Sound Isolation. f. N/A.
Data. g. N/A.
Electric. h. One (1) duplex GFI outlet for the refrigerator
i. Two (2) duplex GFI outlets at counter height; 48” from floor; locations determined by VA.
j. Three (3) duplex outlets, one on each wall, 18” from floor.
Lighting. x. Occupancy Sensor, 30-minute time delay.
Safety. k. Duress Alarm. Hardwired transmitter device.
10RCS/STA703 VET CENTER Page 11 | 18 Lessor Initials: ________________Date: ______________
Key Control Access. y. Access-controlled door that utilizes a wireless key fob for entry.
Other. l. Coat Hooks. Three (3) coat hooks; location determined by the VA.
m. Cabinets. Upper and lower kitchen cabinets.
n. Countertop. Minimum 10’ feet solid surface Quartz countertop.
a. Sink. Double compartment stainless sink. Provided by Lessor.
o. Garbage Disposal. Provided by Lessor.
b. Refrigerator. Refrigerator in Fingerprint Resistant Stainless, 25 cu. Ft. capacity minimum with ice maker, provided by Lessor.
c. Microwave. Countertop Microwave in Fingerprint Resistant Stainless, 1.6 cu. Ft. capacity-1000 Watts minimum, provided by Lessor.
d. Dishwasher. Fingerprint Resistant Stainless, provided by the Lessor.
9. HOUSEKEEPING
Floor. a. Sealed concrete floor.
Wall. b. Paint all rooms/spaces with primer, two finish coats.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC; standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Door. e. Solid Core Wood Door.
Data. g. N/A.
Electric. h. One (1) GFCI outlet.
Lighting. i. Occupancy Sensor.
10RCS/STA703 VET CENTER Page 12 | 18 Lessor Initials: ________________Date: ______________
Safety. j. N/A.
Key Control Access. z. Access-controlled door that utilizes a wireless key fob for entry.
Other. k. Shelving. Adjustable wire shelving on two walls.
l. Sink. Mop Sink.
10. SUPPLY ROOM
Floor. a. Luxury Vinyl Tile (LVT) 5mm thickness + 20mil wear layer.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC, standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Door. e. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Data. g. Two (2) data outlets, next to quadraplex electrical outlets.
Electric. h. Two (2) quadraplex outlets, next to data outlets. Two (2) duplex outlets at counter height, 48” from the floor.
Lighting. i. Occupancy Sensor.
Safety. j. N/A.
Key Control Access. k. Access-controlled door that utilizes a wireless key fob for entry.
Other. l. Cabinets. Casework cabinetry and counter provided by VA furniture vendor.
m. Lessor provided and installed independent network switch and IP address to support the Cable television, Business High Speed Internet Wi-Fi Router, and Security Alarm Control Panel; final location determined by VA.
10RCS/STA703 VET CENTER Page 13 | 18 Lessor Initials: ________________Date: ______________
10. STORAGE ROOM
Floor. a. Luxury Vinyl Tile (LVT) 5mm thickness + 20mil wear layer.
Wall. b. Paint all rooms/spaces with primer, two finish coats, and accent walls color; location determined by VA.
Ceiling. c. Acoustical Ceiling Tile panels HIGH-NRC/HIGH-CAC; standard size 24’ x24” x 1” with laminated or sealed face and sealed edges.
Window. d. No Windows.
Door. e. Solid Core Wood Door with sound proofing jamb seal, threshold seal, and soft closing door feature.
Sound Isolation. f. N/A.
Data. g. Two (2) data outlets; locations determined by VA.
Electric. h. Four (4) duplex outlets, one per wall next to data outlets.
Lighting. i. Occupancy Sensor.
Safety. j. N/A.
Key Control Access. k. Access-controlled door that utilizes a wireless key fob for entry.
Other. l. Telecommunication Enclosure (TE) to be in located this space.
11. TELECOMMUNICATIONS
Telecommunication Enclosure
(TE).
a. Telecommunication Enclosure (TE).
Refer to SOW ASR-D Design Guide for Telecommunications Enclosure PG-18-12 Appendix G.
https://dvagov.sharepoint.com/sites/VHAVetCentered/RCSNSS/RCS%20CAM/PREAWARD%20CAM%20DOCUMENTS/SOW%20-%20Statement%20of%20Work%20samples/a.%09Telecommunication%20Enclosure%20(TE).%20%20Refer%20to%20SOW%20ASR-D%20Design%20for%20Telecommunications%20Enclosure%20PG-18-12%20Appendix%20G.
10RCS/STA703 VET CENTER Page 14 | 18 Lessor Initials: ________________Date: ______________
Telecommunication Data Outlets, Connected to VA
Network
a. Standard Data Outlets: Each data outlet device location will have four (4) Work Area Outlet (WAO) Standard Density design cable runs that terminate on the high-density rack mounted patch panel in the Telecommunications Room.
b. Wall Mounted Phones: Any jacks for wall mounted phones should have 1 data cable to support VoIP, and be on a 1 port metal plate, and accommodate RJ45. Cabling must be installed according to BISCI standards.
c. All permanent link cabling from the Telecommunications Room to the outlet require continuous runs with no splices and be less than 295’.
d. Patch Panels, jacks, and cables require CAT 6A and shall be tested and certified; test results provided to VA COR.
e. Provide flush/surface mounted single-gang outlet boxes with four-port base plates and applicable wall device faceplates.
f. Provide and install all cable runs throughout the space and terminate in the Telecommunications Enclosure.
g. VA naming and labeling conventions in section 5.1.5, Information Transport Systems Equipment and Component Labeling, of the Infrastructure Standard for Telecommunications Spaces.
h. Attached labels at the patch panel and wall plate; easily visible and printed, hand-written labels are prohibited.
12. FINISHES
Color Board a. The Lessor shall provide physical samples for VA final approval; VA will provide a digital Color Board.
RCS CAM. INSTRUCTIONS. Color Board Finishes
13. SOUND ISOLATION
Sound Transmission Class
(STC)
a. STC 45 in Restrooms, Offices, and Group Rooms.
b. Sound Acoustic Field Study. Lessor to conduct a Sound Acoustic Field Study to assure the acoustic requirements met the Vet Center specific requirements.
Examples which may help achieve a sound resistant enclosure; these are not the requirements:
https://www.cfm.va.gov/til/telecom.asp https://www.cfm.va.gov/til/telecom.asp https://dvagov.sharepoint.com/:w:/r/sites/VHAVetCentered/RCSNSS/RCS%20CAM/_layouts/15/Doc.aspx?sourcedoc=%7B4678AD0F-3AD8-4FB0-84F8-42FA149AED2C%7D&file=INSTRUCTIONS.%20%20Color%20Board%20Finishes.docx&action=default&mobileredirect=true
10RCS/STA703 VET CENTER Page 15 | 18 Lessor Initials: ________________Date: ______________
- Install sound and noise-blocking wall construction between rooms and in the ceiling.
- Door Thickness 2 ¼”-2 ¾”
- Sound Dampening Cores, Soundproof door jamb and threshold seal
- Rockwool Sound insulation
- Acoustical Ceiling Insulation 3 ½”
- Acoustic Ceiling Panel Tiles
- Walls Floor to Deck
- Walls 12-18” above ceiling
- 5/8” Metal Studs 20-24” spacing
- QuietRock Drywall
14. SOUND MASKING SYSTEM
a. Provide and install a sound masking system using a series of loudspeakers installed in a grid-like pattern in the ceiling.
b. System zones to control volume and frequency in the lobby, corridors, and group rooms; control system location determined by VA.
c. Example Brand Name Equal. Cambridge Qt X 300/300D control module is a compact three-zone networkable controller suitable for installations of up to 36,000 square feet (3,345 m2). Each zone can be independently adjusted for masking with two auxiliary audio inputs to allow for distribution of audio from paging controllers and/or (background) music players; controls up to three zones of Qt standard or active Qt Emitters.
15. SIGNAGE
Exterior Signage a. Refer to Exhibit SOW ASR-B RCS Exterior Signage Guide for specifications and requirements associated with the exterior signage.
b. Preferred Option is luminated dusk to dawn Vet Center logo on building, above the entrance.
c. VA approval required prior to fabrication and installation
d. Signage shall be legible from main serving road.
e. Signage shall comply with local municipality codes, maximum size in accordance with local building code.
https://cambridgesound.com/products/qt-x300/ https://cambridgesound.com/products/qt-emitters/
10RCS/STA703 VET CENTER Page 16 | 18 Lessor Initials: ________________Date: ______________
Main Entry Door f. Refer to Exhibit SOW ASR-B RCS Exterior Signage Guide for specifications and requirements associated with the entry door decal signage.
Interior Signage g. Refer to Exhibit SOW ASR-B RCS Interior Signage Guide for specifications and requirements associated with ADA compliant interior signage.
16. SECURITY
Facility Security Level
(FSL) II.
a. Refer to Facility Security Level (FSL) requirements exhibit included in the lease for all shell and tenant improvements requirements.
b. Lessor to design, provide equipment, install, maintain, and complete software updates.
c. No public access to the offices will be allowed.
d. Security System Monitoring and Maintenance provided by the Lessor and paid through the annual rent.
e. Security system tested quarterly by the Lessor; a copy of the report sent to VA.
10RCS/STA703 VET CENTER Page 17 | 18 Lessor Initials: ________________Date: ______________
VIDEO SURVEILLANCE SYSTEM
(VSS).
f. Lessor to design, provide equipment, install, complete software updates and provide preventive maintenance for all security systems.
g. Provide independent network switch and IP address to support the system; location determined by VA (Supply/Storage Room).
h. Single cabinet, stand-alone browser-based system.
i. System reports to a master station with monitor; location determined in coordination with the VA.
j. System supports the entry control system, 30-day time-lapse video recording.
k. System testing is required prior to occupancy.
l. Cameras (exterior) installed to provide unobstructed coverage of pedestrian entrances and exits.
m. Cameras (interior) installed in the waiting/lobby, the main corridors, and telecommunications room entrance.
ACCESS CONTROL. n. Video Intercom. System to allow VA staff to view, communicate, and open the door remotely before allowing access to space.
- Compact intercom - Exterior Entrance (Qty 1)
- Compact intercom - Master Station (Qty 2); location determined by VA.
INTRUSION DETECTION
SYSTEM (IDS).
o. Locally sounding audible alarm throughout space activate upon illegal/unauthorized entry.
p. Remote visual and audio annunciators located within the facility which ensures 24-hour monitoring.
q. Alarm system keypad to arm/disarm IDS at interior employee entrance/exit; location determined by VA.
r. Alarm sensors on all exterior doors and windows, and telecommunication room door.
s. Motion sensors cover the lobby, main corridors, and telecommunication room.
t. Employee access code updates coordinated with Lessor as required for the duration of lease term.
DURESS ALARM. u. Lessor to design, provide equipment, install, maintain, and complete software updates for the Duress Alarm system.
v. Interface with the Intrusion Detection System.
w. System reports to master station. Master station displays the transmitter device location upon call notification; location determined by VA.
x. Each transmitter device is individually zoned.
y. Hardwired duress alarm installed in each restroom and group room.
z. Wireless duress alarm installed at reception desk and in each office.
aa. When activated, a notification sounds through the hallways/corridors, and the central monitoring center is alerted.
bb. Duress Alarm System alerts the alarm company, which then contacts the Vet Center to determine the required course of action.
NURSE CALL. cc. Nurse call tone-visual system. The notification sounds in corridors and at master station
dd. Dome visual call light above the room.
ee. Pull-cord stations.
10RCS/STA703 VET CENTER Page 18 | 18 Lessor Initials: ________________Date: ______________
Vet Center External Signage Guide
AUGUST 2025
The U.S. Department of Veterans Affairs (VA) Veterans Health Administration (VHA) Readjustment Counseling Service (RCS) created this Vet Center Exterior Signage Guide to provide guidance on all exterior signage related to the Vet Center brand. This guide shall serve as the official directive and final authority for all Vet Center signage standards until a revised version is issued and released.
All exterior sign applications must comply with these standards without exception. Alteration of Vet Center logo colors or design is prohibited unless otherwise stated in the following documentation. All signs must be in accordance with the local code and landlord specifications.
NOTE: VA will approve all signage design schematics prior to fabrication and installation.
Variation shall not exist outside these design specifications without prior authorization. Sign vendor or lessor shall contact the Contracting Officers Representative (COR) for review and approval of any modifications through VA’s Readjustment Counseling Service Communications Office.
Purpose
| Purpose | 1 |
| Vet Center Exterior Signage Requirements | 4 |
| Exterior Signage: Preferred Application | 6 |
| Channel Letters on Raceway | 6 |
| Channel Letters on Raceway Specifications | 7 |
| Exterior Signage: Secondary Applications | 8 |
| Lightbox and Multi-Tenant Signs | 8 |
| Single Tenant Monument and Pylon Signs | 10 |
| Restrictive Tenant Panel Sign | 12 |
No Building, Monument, or Pylon Signage Exterior Panel Sign 14
Door Decal Signage 16
Table of Contents
Vet Center Exterior Signage Guide
1. Install time and design/specifications must be included in bid quote but be listed as separate line items.
2. This service order and installation shall be coordinated with Contracting Officers Representative (COR).
3. The installation shall occur and be completed Monday-Friday between the hours of 8:00 AM-4:30 PM.
4. Deliveries must be scheduled through the COR before installation.
5. Confirmation from vendor shall be sent via email to COR who will inspect that all products are installed 100%. Upon completion of inspection, the COR will email the Contracting Officer authorizing that products have been received complete and that payment can be released.
6. Any damage to the Vet Center facility incurred through the installation process must be repaired within 30 days at the vendor’s expense.
GENERAL REQUIREMENTS
• Lessor shall provide samples for the VA to review and approve prior to fabrication.
• Lessor shall provide Vet Center logo Exterior Signage on the Building Exterior as well as Door Decal signage.
• Lessor shall provide Vet Center logo Exterior Signage on Marquee.
• Lessor shall provide Vet Center logo Exterior Signage, Monument sign.
• Lessor shall develop, provide, deliver, stage/move, and install the new exterior sign.
• Lessor shall provide all the equipment, cabling, labor, materials, and sign.
• Signage shall be legible from main serving road.
• Signage shall comply with local municipality’s codes and specifications.
SIZE: Maximum size in accordance with local building code.
EXTERIOR SIGNAGE REVIEW
C h an n el L et te rs o n R ac ew ay
PREFERRED EXTERIOR SIGNAGE APPLICATION:
CHANNEL LETTERS ON A RACEWAY
Every effort shall be made to construct channel letters on a raceway, as this is the preferred application. In all cases where the channel letters on raceway sign is constructed for a building exterior, the exterior sign should be raceway mounted, with the raceway color matching the face of the building. The power connectors for the logo’s star and red stripe shall be remote mounted with external power links.
LIGHTING: In the case where illuminated signage is not permitted by ordinance, ½” thick stud-mounted acrylic letters shall be used.
Channel Letters on a Raceway Signs
CHANNEL LETTERS ON A RACEWAY
COLOR SPECIFICATIONS FOR CHANNEL LETTERS ON A RACEWAY SIGN
Colors are to be pigmented Translucent Vinyl over White Acrylic Faces with a minimum of 3/8th of an inch white reveal around each colored area. Trim cap and returns shall be white. White LED Illumination. Raceway mounted channel letters with raceway to match building. Each letter should be one piece, with vinyl and white space used to simulate the stencil effect.
BUILD SPECIFICATIONS FOR CHANNEL LETTERS ON A RACEWAY SIGN
MATERIAL SPECIFICATONS FOR CHANNEL LETTERS ON A RACEWAY SIGN
STRIPE AND STAR
8” Deep Cans Remote Mounted wire to main text with connectors
White Trim Cap & White Returns
VET CENTER
5” Deep Cans
White LED Lamps
POWER
CONNECTOR:
Painted to match building facade
ATTACHMENTS:
All attachments to be appropriate to exterior wall construction
RACEWAY:
Raceway 3” x 8” painted to match building facade
Low Voltage Power Supply
Internal Power Connection
Typical Wall Construction
EXTERIOR WALLCHANNEL LETTERS
CHANNEL LETTER
FACES:
Channel letter faces should have a minimum 3/8th of an inch white reveal around the colored overlays.
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.
L ig h tb ox a n d
M u lt i-T en an t
SECONDARY EXTERIOR SIGNAGE APPLICATION:
LIGHTBOX AND MULTI-TENANT DESIGN
In the case where the preferred application of the channel letters on a raceway sign is not possible, the secondary application choice is a lightbox and multi-tenant design. Where a lightbox sign is the only choice available, the logo design shall appear as shown in the color specifications for lightbox and multi-tenant design.
LIGHTING: Determined by existing signage.
Lightbox and Multi-Tenant Design Signs
LIGHTBOX AND MULTI-TENANT SIGN
COLOR SPECIFICATIONS FOR LIGHTBOX AND MULTI-TENANT SIGN
BUILD SPECIFICATIONS FOR LIGHTBOX AND MULTI-TENANT SIGN
Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.
MATERIAL SPECIFICATONS FOR LIGHTBOX AND MULTI-TENANT SIGN
PREFERRED DESIGN - NEW SIGNS
Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale.
Logo maximized to fit allowable lightbox width.
Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.
ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.
Logo maximized to fit allowable lightbox height.
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.
Si n gl e
T en an t
M on u m en t an d
P yl on
SECONDARY EXTERIOR SIGNAGE APPLICATION:
SINGLE TENANT MONUMENT AND PYLON SIGNS
In the case where the preferred application of the channel letters on a raceway sign is not possible, another secondary application choice is a single tenant monument or pylon sign design. The logo design shall appear as shown in the color specifications. If the sign face is wide and short, the vendor shall maximize the size of the logo leaving an appropriate amount of white space around the logo as indicated in the build specifications guidance.
LIGHTING: Determined by existing signage.
Single Tenant Monument and Pylon Signs
SINGLE TENANT MONUMENT AND PYLON SIGN
COLOR SPECIFICATIONS FOR SINGLE TENANT MONUMENT AND PYLON SIGN
Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.
BUILD SPECIFICATIONS FOR SINGLE TENANT MONUMENT AND PYLON SIGN
MATERIALS FOR SINGLE TENANT MONUMENT AND PYLON SIGN
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
PREFERRED DESIGN - NEW SIGNS
Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale.
Logo maximized to fit allowable lightbox width.
Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.
ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.
Logo maximized to fit allowable lightbox height.
NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.
R es tr ic ti ve
T en an t
P an el
RESTRICTIVE TENANT PANEL SIGNS
In the case where the preferred application of the channel letters on a raceway sign is not possible, a secondary application choice is a restrictive tenant panel sign. When there is nothing but a solid, non-illuminated panel to use (common in office complexes, with multi-tenant panels) the words “Vet Center” shall be used in the appropriate color and font for that sign. Wherever possible, the logo shall be shown. When the logo cannot be used, the words “Vet Center” shall be used.
LIGHTING: Determined by existing signage.
Restrictive Tenant Panel Signs
VET CENTER
RESTRICTIVE TENANT PANEL SIGN
COLOR SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN
BUILD SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN
The materials should match the existing signage, and can range from cut vinyl lettering to routed/engraved tenant panels.
MATERIAL SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.
PREFERRED DESIGN - NEW SIGNS
Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale. When possible, follow the guidelines for logo spacing within the restricitve tenant panel.
Logo maximized to fit allowable lightbox width.
Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.
ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.
Logo maximized to fit allowable lightbox height.
E tr an ce P an el
S ig
EXTERIOR POSTED PANEL SIGN
Where there is no ability to place a channel lettering on raceway sign, monument sign, or pylon sign, thus restricting you to a sign by the entrance door, an exterior posted panel sign shall be used. If space is not available by the entrance door, a non-illuminated post and panel sign shall be constructed outside of the building, near the main entrance. All exterior Vet Center signage within a facililty, i.e. medical building, must comply with regulations set forth by the Americans with Disabilities Act (ADA) and include braille, as required.
LIGHTING: Determined by signage placement.
Suite 1A
Exterior Posted Panel Sign - Entrance Door or Nearby
EXTERIOR POSTED PANEL SIGN - ENTRANCE
DOOR OR NEARBY
COLOR SPECIFICATIONS FOR ENTRANCE PANEL SIGN
Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.
MATERIAL SPECIFICATIONS FOR ENTRANCE PANEL SIGN
BUILD SPECIFICATIONS FOR ENTRANCE PANEL SIGN
ACCEPTABLE SIGN DESIGN
12”w x 8” h
A 2” d x 12” h x 36” w aluminum post and panel with internal 2” square posts is required. The sign base shall be no less than 24” above grade. (This is not to be confused with a directional sign.)
19” w x 6” h
36”
36”
12”
Suite 1A
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.
DOOR DECAL SIGNAGE
The Lessor shall provide signage on the main entrance door. The door decal shall be printed on a clear background. A white poster-like background for the door decal display is unacceptable. The Vet Center Call Center number shall be shown as the numeric 1-877-927-8387 only. Avoid use of the “WAR-VETS” phonewords.
A full-color Vet Center logo shall be used with an accompanying “Connection.
Camaraderie. Community.” slogan in white. Alterations to this brand shall not be made. If other building notices are needed, such as an automatic door symbol, spacing accommodations can be made. For the Veterans Crisis Line, refer to the build specifications and use “Dial 988” instead of “Call 1-800-273-8255.”
Accompanying font: Zilla Slab preferred; Rockwell is an approved alternative.
Door Decal Signage
D oo r D ec al
S ig n ag e
NOTE: (Above left) Spacing accomodations for automatic door symbol may be made. (Below) The door decal shall be printed on a clear background. A white poster-like background or a white stroke around the lettering is unacceptable.
DOOR DECAL SIGNAGE
COLOR SPECIFICATIONS FOR DOOR DECAL SIGNAGE
Digitally printed on clear vinyl application shall be used. The colors must match the color specifications of the logos.
BUILD SPECIFICATIONS FOR DOOR DECAL SIGNAGE
MATERIAL SPECIFICATIONS FOR DOOR DECAL SIGNAGE
[Vet Center Slogan Logo]
[Vet Center or Vet Center Outstation Name]
Greatest Vet Center Outstation [Vet Center Address] 123 Lane, Greatest City, VA 12345
[Core Hours] Open Monday-Friday 8:00 A.M. - 4:30 P.M.
Ask about additional hours to meet your needs
[Vet Center Office Phone Number] (012) 345-6789 [Vet Center website] www.va.gov/Hilo-Vet-Center
After Hours
Vet Center Call Center 1-877-927-8387
Veterans Crisis Line
Dial 988 and Press 1 to receive confidential support 24 hours a day.
[VA Seal]
RED- PANTONE 1797C
CMYK: 13 94 83 3
DARK BLUE- PANTONE 647C
CMYK: 91 63 20 4
LIGHT BLUE- PANTONE 7461C
CMYK: 96 42 6 0
NOTE: The black background is for visual reference only. An additional white stroke around the letters of the Vet Center slogan logo should not be added for the purposes of the door decal. This differs from other designs used for prominent exterior signage.
Vet Center Internal Signage Guide
JANUARY 2025
VA Signage Design Manual Section 2.3 Mandatory VA Policy & Directive Signage Guidelines https://www.cfm.va.gov/til/dManual/dmSignage.pdf
Sheet Title:
Sheet No.:
VC - 01.01
SIGNAGE TYPE A1
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
5. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
6. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
SIDE VIEW
COUNSELOR
116 1
9 1/2"
3/4
2 1 /2"
1/4
4 3 /4"
3/4
9" 1/8"
1/8"
7 3/4"
3/4" 8" 3/4"
7 1 /2"
COUNSELOR
3"
5'
- 0
Sheet No.:
Sheet Title:
VC - 01.01
SIGNAGE TYPE A1
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
3" = 1'-0"
SIGN TYPE A1
1/4" = 1'-0"
INSTALLATION DETAIL - TYPE A1
SIDE VIEW
COUNSELOR
116 1
9 1/2"
3/4
2 1 /2"
1/4
4 3 /4"
3/4
9" 1/8"
1/8"
7 3/4"
3/4" 8" 3/4"
7 1 /2"
COUNSELOR
3"
5'
- 0
Sheet No.:
Sheet Title:
VC - 01.01
SIGNAGE TYPE A1
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
3" = 1'-0"
SIGN TYPE A1
1/4" = 1'-0"
INSTALLATION DETAIL - TYPE A1
SIGNAGE TYPE A2
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
5. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
6. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
8. TYPE: LETERS SET INTO 1/8”
ACRYLIC SLIDE PANEL
COLOR: BLACK TEXT /
BRUSHED NICKEL PANEL
TEXT: 5/8” HELVETICA
SIDE VIEW
1/8"
1/8"
FAMILY
COUNSELING
IN USE
3/4
1 1 /2"
4 3 /4"
1/4
2 1 /2"
3/4
1/
2"
9"
7 3/4" 3/4" 8" 3/4"
9 1/2"
FAMILY
3"
5'
- 0
COUSELING
IN USE
Sheet No.:
Sheet Title:
VC - 01.02
SIGNAGE TYPE A2
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
8. TYPE: ACRYLIC LETTERS SET
INTO 1/8" ACRYLIC SLIDE
PANEL
COLOR: BLACK TEXT /
BRUSHED NICKEL PANEL
TEXT: 5/8" HELVETICA
3" = 1'-0"
SIGN TYPE A2
1/4" = 1'-0"
INSTALLATION DETAIL - TYPE A2
SIDE VIEW
1/8"
1/8"
FAMILY
COUNSELING
IN USE
3/4
1 1 /2"
4 3 /4"
1/4
2 1 /2"
3/4
1/
2"
9"
7 3/4" 3/4" 8" 3/4"
9 1/2"
FAMILY
3"
5'
- 0
COUSELING
IN USE
Sheet No.:
Sheet Title:
VC - 01.02
SIGNAGE TYPE A2
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
8. TYPE: ACRYLIC LETTERS SET
INTO 1/8" ACRYLIC SLIDE
PANEL
COLOR: BLACK TEXT /
BRUSHED NICKEL PANEL
TEXT: 5/8" HELVETICA
3" = 1'-0"
SIGN TYPE A2
1/4" = 1'-0"
INSTALLATION DETAIL - TYPE A2
VC - 01.02
SIGNAGE TYPE A OVERALL
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
5. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
6. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
DRAWINGS STAGE.
VESTIBULE
LOBBY
RECEPTION
EDUCATION /
RESOURCES
FAMILY
COUNSELING
PROGRAM
SUPPORT
ASSISTANT
GROUP
ROOM 1
GROUP
ROOM 2
MAIL / COPY
Sheet No.:
Sheet Title:
VC - 01.03
SIGNAGE TYPE A
OVERALL
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
DRAWINGS STAGE.
VC - 01.03
SIGNAGE TYPE A OVERALL
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
5. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
6. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
DRAWINGS STAGE.
SUPPLY
OIT
TELECOM
STORAGE
DIRECTOR
OUTREACH
SPECIALIST
COUNSELOR
COUNSELOR
COUNSELOR
COUNSELOR
Sheet No.:
Sheet Title:
VC - 01.04
SIGNAGE TYPE A
OVERALL
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
VC - 01.04
SIGNAGE TYPE A OVERALL
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
5. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
6. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
DRAWINGS STAGE.
OFFICE
OFFICE
BREAKROOM
HOUSEKEEPING
MECH / ELEC
Sheet No.:
Sheet Title:
VC - 01.05
SIGNAGE TYPE A
OVERALL
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
4. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
5. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
6. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
7. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
LESSOR SHALL VERIFY ALL SIGN
TYPES AND LOCATIONS WITH VA
DIRECTOR AT DESIGN INTENT
VC - 01.05
SIGNAGE TYPE B
1. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 1” HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILE
COLOR: BLACK
3. TYPE: 1/8” ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50% TRANSPARENT
4. TYPE: 1/16” RAISED ACRYLIC
PICTOGRAMS
COLOR: BLACK
5. TYPE: 1/16” BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
6. TYPE: 1/16” RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8” HELVETICA
7. TYPE: 1/8” ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
8. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND TO
WALL INSTALLATION
BABY CHANGING PICTOGRAM
ONLY TO BE PROVIDED AT
ROOMS ONE IS PROVIDED.
RESTROOM
SIDE VIEW
3/4
7 3 /4"
1/4
2 1 /2"
3/4
1'
- 0
9 1/2"
1/8"
1/8"
3/4" 8" 3/4"
1/
2"
7 3/4"
MEN
B1
WOMEN
B2
RESTROOM
5'
- 0
3"
Sheet No.:
Sheet Title:
VC - 02.01
SIGNAGE TYPE B
3" = 1'-0"
SIGN TYPE B
1/4" = 1'-0"
INSTALLATION DETAIL -TYPE B
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
4. TYPE: 1/16" RAISED ACRYLIC
PICTOGRAMS
COLOR: BLACK
5. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
6. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
7. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
8. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
RESTROOM
SIDE VIEW
3/4
7 3 /4"
1/4
2 1 /2"
3/4
1'
- 0
9 1/2"
1/8"
1/8"
3/4" 8" 3/4"
1/
2"
7 3/4"
MEN
B1
WOMEN
B2
RESTROOM
5'
- 0
3"
Sheet No.:
Sheet Title:
VC - 02.01
SIGNAGE TYPE B
3" = 1'-0"
SIGN TYPE B
1/4" = 1'-0"
INSTALLATION DETAIL -TYPE B
1. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 1" HELVETICA
2. TYPE: GRADE 2 RAISED
BRAILLE
COLOR: BLACK
3. TYPE: 1/8" ACRYLIC PANEL
COLOR: FROSTED W/ WHITE
BACK, 50 TRANSPARENT
4. TYPE: 1/16" RAISED ACRYLIC
PICTOGRAMS
COLOR: BLACK
5. TYPE: 1/16" BRUSHED METAL
FACE ACCENT BAR, SET
INTO CLEAR PANEL
COLOR: BRUSHED NICKEL
6. TYPE: 1/16" RAISED ACRYLIC
COLOR: BLACK
TEXT: 5/8" HELVETICA
7. TYPE: 1/8" ACRYLIC PANEL W/
BRUSHED METAL FACE
COLOR: BRUSHED NICKEL
8. DOUBLE SIDED FOAM TAPE
BETWEEN PANELS AND
TO WALL INSTALLATION
RESTROOM
SIDE VIEW
3/4
7 3 /4"
1/4
2 1 /2"
3/4
1'
- 0
9…
This is the start of the file's text. The full file is on GovTribe.