Exhibit_A.pdf
PDF 2 MB Posted
- Attached to
- 2025-54770 Alta Lake Septic Tanks
- Solicitation number
- 2025-54770
- Issued by
- Adams County, Asotin County, Benton County, Chelan County, Clallam County, Clark County, Columbia County, Cowlitz County, Douglas County, Ferry County, Franklin County, Garfield County, Grant County, Grays Harbor County, Island County, Jefferson County, King County, Kitsap County, Kittitas County, Klickitat County, Lewis County, Lincoln County, Mason County, Okanogan County, Pacific County, Pend Oreille County, Pierce County, San Juan County, Skagit County, Skamania County, Snohomish County, Spokane County, Stevens County, Thurston County, Wahkiakum County, Walla Walla County, Whatcom County, Whitman County, Yakima County, Asotin City, Clarkston City, Clarkston Heights-Vineland CDP, West Clarkston-Highland CDP, Benton City, Chelan City, Chelan Falls CDP, Clallam Bay CDP, Lewisville CDP, Rock Island City, Pacific Beach CDP, Whidbey Island Station CDP, Mercer Island City, Pacific City, Bainbridge Island City, Kingston CDP, Kitsap Lake CDP, Kittitas City, Klickitat CDP, Okanogan City, Anderson Island CDP, Fort Lewis CDP, Fox Island CDP, Herron Island CDP, Ketron Island CDP, North Fort Lewis CDP, Raft Island CDP, Stevenson City, Hat Island CDP, Lake Stevens City, Snohomish City, Spokane City, Spokane Valley City, Puget Island CDP, Garfield Town, Yakima City, Washington
About this file
This is a set of engineering drawings and specifications from the Washington State Parks & Recreation Commission for an on-site sewage system upgrade project at Alta Lake State Park. The project involves installing new septic tanks and upgrading the sewage system, including three 8,000-gallon septic tanks in series, two 6,000-gallon pump tanks in series, and associated piping, pumps, and control systems. The drawings detail the site plans, tank specifications, installation requirements, and system components including a 2.5" PVC force main, drain fields, and comfort station connections. The project location is specifically focused on the Alta Lake South Camp Area and Central Camp Area.
The technical specifications require the system installer to be certified by the Washington State Department of Health and have experience installing at least 3 systems with average design flows of 3,000 gallons per day. The project includes specific testing requirements for water tightness of tanks and pressure testing of sewer lines. Equipment specifications call for Orenco components including PVU120-18-19L pump vault, PF200512 duplex pumps, FM-150 flow meter, V6606A automatic distribution valve, and an SJE Rhombus IFN control panel configured for duplex timed dosing. The project must meet Washington State Department of Health regulations (WAC 246-272B) and requires final inspection and approval from DOH before being placed into service.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ_2025_54770.pdf | ||
| 2025_54770_Amendment #01.docx | DOCX document | |
| WSPRC General Terms and Conditions.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2024 Microsoft Corporation © 2024 TomTom © 2024 Zenrin
BREWSTER
PATROS
METHOW
Source: Esri, Maxar, GeoEye, Earthstar Geographics, CNES/Airbus DS, USDA, USGS, AeroGRID, IGN, and the GIS User Community Powered by Esri Source: Esri, Maxar, GeoEye, Earthstar Geographics, CNES/Airbus DS, USDA, USGS, AeroGRID, IGN, and the GIS User Community Powered by Esri
EXISTING
DRAIN FIELD
NFD RD 2917
COMFORT STA. BLDG #14
EXISTING 2 1/2"
PVC FORCE MAIN
PROPOSED SEPTIC
TANKS LOCATION
ALTA LAKE
SOUTH
CAMP AREA
CENTRAL
CAMP AREA
WEST
CAMP LOOP
ALTA LAKE
STATE PARK
ALTA LAKE STATE PARK
ON-SITE SEWAGE SYSTEM UPGRADE
WASHINGTON STATE PARKS
& RECREATION COMMISSION
APPROVED FOR CONSTRUCTION
Area Manager: JEFF WHEELER date dateREGION MANAGER
CAPITAL PROGRAM MANAGER
MICHAEL LATIMER
MARK O. BROWN, CHAIR
SOPHIA DANENBERG LAURIE CONNELLY
KEN BOUNDS
DIANA DUPUIS, DIRECTOR
ALI RAAD HOLLY WILLIAMS
AEC2303
DOH Approved Stamp
PROJECT TEAM
WASHINGTON STATE PARKS
AND RECREATION
EASTERN HEADQUARTERS OPERATIONS
270 9TH STREET NE, SUITE 200
EAST WENATCHEE, WA 98802
OWNER/CLIENT:
OWNERS REPRESENTATIVE: CHRIS RAMSEY
REGIONAL MAINTENANCE MANAGER
PROJECT COORDINATOR
TEL (509) 699-1844
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
PROJECT TEAM
AS SHOWN
WASHINGTON STATE PARKS
AND RECREATION
EASTERN HEADQUARTERS OPERATIONS
270 9TH STREET NE, SUITE 200
EAST WENATCHEE, WA 98802
10/21/24
EXISTING
DRAIN FIELD
N
FD
R D
COMFORT STA. BLDG #14
EXISTING 2 1/2"
PVC FORCE MAIN
PROPOSED SEPTIC
TANKS LOCATION
ALTA LAKE
SOUTH
CAMP AREA
CENTRAL
CAMP AREA
PARK BOUNDARY
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
OVERALL SITE
PLAN
AS SHOWN
0S1.01
10/21/24
EXISTING DISTRIBUTION GRAVEL BED
(1.2 GPD/SF LOADING)
INTERCEPT EXISTING FORCEMAIN
AND CONNECT TO SEPTIC TANK 1
(3) 8,000 GALLON SEPTIC
TANKS IN SERIES
(INW PRECAST 8000-ST)
0S2.01
(2) 6,000 GALLON PUMP TANKS
IN SERIES. CONNECT TANKS AT
TOP AND BOTTOM
(INW PRECAST 6000-ST)
0S2.01
REPLACE EXISTING ADV AND
RELOCATED IN NEW VAULT
INTERCEPT EXISTING
LATERAL SUPPLY LINES
AND REROUTE TO NEW ADV
0S2.02
1.5" FLOW METER
IN VALVE VAULT
0S2.01
CONTROL PANEL 6
0S2.02
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
DRAINFIELD SITE
PLAN
AS SHOWN
10/21/24
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
GENERAL NOTES
AS SHOWN
1. ALL WORK, WORKMANSHIP AND MATERIALS FOR THIS PROJECT SHALL MEET OR EXCEED THE
PROJECT SPECIFICATIONS, WASHINGTON STATE DEPARTMENT OF HEALTH ENGINEERING DESIGN AND
DEVELOPMENT STANDARDS AND MAY INCLUDE REFERENCES TO THE MOST CURRENT VERSION OF
THE WSDOT STANDARD SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPAL CONSTRUCTION. IF THERE IS A CONFLICT BETWEEN THE SPECIFICATION TYPES, THE MOST RESTRICTIVE REFERENCE
SHALL BE ADHERED TO.
2. ALL GOVERNMENTAL SAFETY REGULATIONS SHALL BE STRICTLY ADHERED TO INCLUDING OSHA, WISHA AND THE WASHINGTON DEPARTMENT OF LABOR AND INDUSTRY.
3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DULY NOTIFY PARKS IN ADVANCE OF THE
COMMENCEMENT OF ANY AUTHORIZED WORK AND TO SCHEDULE REQUIRED INSPECTIONS. ALL
REQUIRED INSPECTION TESTS WILL BE PERFORMED AT THE CONTRACTOR'S EXPENSE.
4. THE CONTRACTOR SHALL PROVIDE A TWO-YEAR WARRANTY ON ALL WORKMANSHIP AND MATERIAL
FOLLOWING ACCEPTANCE OF THE PROJECT BY THE OWNER.
5. THE APPROVAL OF THESE PLANS BY WSDOH OR PARKS DOES NOT RELIEVE THE CONTRACTOR OR DEVELOPER OF THE RESPONSIBILITY TO COMPLY WITH THE REQUIREMENTS OF OTHER GOVERNING
AGENCIES.
6. CAUTION - NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED THAT THE LOCATION OF EXISTING UTILITIES AS
SHOWN ON THESE PLANS IS BASED ON THE PROJECT SURVEY AND OTHER RECORDS OF UTILITIES.
THE INFORMATION IS NOT TO BE RELIED ON AS BEING EXACT OR COMPLETE. THE CONTRACTOR
SHALL CALL 811 48 HOURS PRIOR TO PLANNED EXCAVATIONS.
7. THE DESIGN SHOWN IS BASED UPON THE ENGINEER'S UNDERSTANDING OF THE EXISTING
CONDITIONS. THE EXISTING CONDITIONS SHOWN ON THIS PLAN SHEET ARE BASED UPON COMPILED SURVEY DATA. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING FIELD CONDITIONS PRIOR TO BIDDING THE PROPOSED WORK IMPROVEMENTS. IF CONFLICTS ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE OWNER OR OWNERS REPRESENTATIVE.
8. EXISTING UTILITIES ARE SHOWN FOR REFERENCE ONLY. PRIOR TO CONNECTION TO EXISTING UTILITIES THE CONTRACTOR SHALL VERIFY EXACT LOCATION, DIA, LENGTH, CONDITION, PIPE TYPE, SLOPE AND VERTICAL AND HORIZONTAL ALIGNMENT OF THE EXISTING UTILITY AND PROPOSED POINT OF CONNECTION. THE CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO ENGINEER PRIOR TO
CONSTRUCTION.
9. THE CONTRACTOR SHALL REVIEW AND BECOME FAMILIAR WITH THE STATE PARKS-OBTAINED
PERMITS. THE CONTRACTOR SHALL OBTAIN ALL OTHER FEDERAL, STATE, OR LOCAL DEPARTMENTS
REQUIRED PERMITS AFFECTED BY THE WORK NOT PREVIOUSLY OBTAINED BY STATE PARKS.
10. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE A COPY OF THE APPROVED PLANS, SPECIFICATIONS, AND CONTRACT DOCUMENTS AT THE CONSTRUCTION SITE AT ALL TIMES.
11. THE CONTRACTOR SHALL PROVIDE SLOPE PROTECTION FOR SLOPES OF 5:1 OR GREATER
ACCORDING TO ASSOCIATED GENERAL CONTRACTORS (AGC) STANDARD GUIDELINES AND BEST
MANAGEMENT PRACTICES (BMP'S).
12. THE CONTRACTOR SHALL MAINTAIN EROSION CONTROL FACILITIES IN ACCORDANCE WITH
DEPARTMENT OF ECOLOGY STORMWATER MANUAL.
13. THE CONTRACTOR SHALL SAFELY MAINTAIN TRAFFIC AND CONTINUOUS ACCESS TO PRIVATE AND/OR
PUBLIC PROPERTY.
14. CONSTRUCTION SIGNING AND TRAFFIC CONTROL SHALL BE PER THE CURRENT COPY OF THE MANUAL
OF UNIFORM TRAFFIC CONTROL DEVICES (MUTCD).
15. ALL VEHICLES AND EQUIPMENT SHALL BE KEPT WITHIN THE WORK AREAS ESTABLISHED FOR THAT
WORK SHIFT UNLESS TRAVELING TO OR FROM THE SITE. UNDER NO CIRCUMSTANCES SHALL
VEHICLES OR EQUIPMENT BE PARKED OR STORED OUTSIDE OF THESE AREAS.
16. OTHER CONSTRUCTION PROJECTS MAY OCCUR NEAR THE PROJECT SITE AND MAY BE IN PROGRESS
CONCURRENT WITH THE PROJECT. THE CONTRACTOR SHALL COOPERATE AS NECESSARY AND NOT
INTERFERE OR HINDER THE PROGRESS OR COMPLETION OF WORK BEING PERFORMED BY OTHER
CONTRACTORS.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ALL MATERIALS, LABOR, AND EQUIPMENT NECESSARY TO COMPLETE THE WORK SHOWN ON THESE DRAWINGS AND TO OBTAIN
ACCEPTANCE BY THE PROJECT OWNER.
18. ALL AREAS DISTURBED DURING CONSTRUCTION SHALL BE RESTORED TO THEIR ORIGINAL "PRE
CONSTRUCTION" STATE OR BETTER.
19. DRIVEWAY ACCESS AND UTILITY SERVICE TO EXISTING TRAIL SHALL BE MAINTAINED AT ALL TIMES.
20. THESE NOTES CONTAIN GENERAL INFORMATION AND ARE NOT COMPREHENSIVE. CONTRACTOR
SHALL VERIFY INFORMATION PROVIDED HERE WITH TECHNICAL SPECIFICATIONS AND OTHER
DOCUMENTS AND BRING ANY CONFLICTS TO THE ATTENTION OF WASHINGTON STATE PARKS (OWNER)
BEFORE WORK IS INITIATED.
1. THE BOUNDARIES OF THE GROUND DISTURBANCE LIMITS SHOWN ON THE PLAN SHALL BE CLEARLY FLAGGED BY A CONTINUOUS LENGTH OF SURVEY TAPE (OR FENCING, IF REQUIRED) PRIOR TO ANY CLEARING OR GRADING.
DURING THE CONSTRUCTION PERIOD NO DISTURBANCE BEYOND THE GRADING/CLEARING LIMITS SHALL BE PERMITTED. THE GRADING/CLEARING LIMITS SHALL BE MAINTAINED BY THE CONTRACTOR/TESC SUPERVISOR FOR
THE DURATION OF CONSTRUCTION.
2. TREE PROTECTION FENCING MUST BE IN PLACE PRIOR TO ANY GRADING ACTIVITIES. NO EQUIPMENT IS ALLOWED WITH THE TREE PROTECTION BOUNDARIES. ANY GRADING REQUIRED WITHIN A TREE PROTECTION BOUNDARY
MUST BE DONE WITH HAND EQUIPMENT.
3. THE TESC FACILITIES MUST BE CONSTRUCTED PRIOR TO OR IN CONJUNCTION WITH ALL CLEARING AND GRADING AND/OR ASPHALT/CONCRETE CUTTING SO AS TO ENSURE NO TRANSPORT OF SEDIMENT TO SURFACE WATERS, DRAINAGE SYSTEMS, AND ADJACENT PROPERTIES.
4. ANY AREAS OF EXPOSED SOILS, INCLUDING BUT NOT LIMITED TO ROADWAY EMBANKMENTS, STOCKPILE MATERIAL, AND CUT SLOPES THAT WILL NOT BE DISTURBED FOR TWO DAYS DURING THE WET SEASON OR SEVEN DAYS DURING THE DRY SEASON SHALL BE IMMEDIATELY STABILIZED WITH THE APPROVED TESC METHODS (E.G.
SEEDING, MULCHING, PLASTIC COVERING, NETTING, EROSION BLANKETS ETC.).
5. DURING THE WET SEASON (OCTOBER 1 THROUGH APRIL 30 INCLUSIVE), ALL DISTURBED SOILS SHALL BE STABILIZED WITHIN 48 HOURS AFTER STOP OF WORK. EROSION CONTROL MEASURES SHALL INCLUDE, BUT ARE NOT LIMITED TO, COVERING THE AFFECTED AREA INCLUDING SPOIL PILES WITH PLASTIC SHEETING, STRAW MATTING, JUTE MATTING, STRAW MULCH, OR WOOD CHIPS. SEEDING OF THE DISTURBED AREAS SHALL TAKE
PLACE AS WEATHER PERMITS.
1. THE CONTRACTOR SHALL FOLLOW EROSION CONTROL PRACTICES OUTLINED IN THE WASHINGTON STATE
DEPARTMENT OF ECOLOGY STORMWATER MANAGEMENT MANUAL FOR WESTERN WASHINGTON.
2. EROSION CONTROL MEASURES ARE NOT LIMITED TO THE ITEMS ON THESE PLANS. THE CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION AND MAINTENANCE OF ALL EROSION CONTROL MEASURES. NO SILTATION OF EXISTING OR PROPOSED DRAINAGE FACILITIES SHALL BE ALLOWED. CARE SHALL BE TAKEN TO PREVENT
MIGRATION OF SILTS TO OFF-SITE PROPERTIES.
3. EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO THE BEGINNING OF CONSTRUCTION. THE PROJECT ENGINEER AND THE REVIEWING AGENCY SHALL INSPECT AND APPROVE THE INSTALLATION OF EROSION CONTROL
MEASURES PRIOR TO BEGINNING CONSTRUCTION.
A. INSTALL INLET SEDIMENTATION AS SPECIFIED AT ALL CATCH BASIN LOCATIONS IMMEDIATELY UPON ARRIVAL AT
PROJECT/CONSTRUCTION SITE.
4. ALL EROSION/SEDIMENTATION CONTROL FACILITIES SHALL BE MAINTAINED IN A SATISFACTORY CONDITION UNTIL CONSTRUCTION IS COMPLETE AND THE SITE HAS BEEN STABILIZED. THE CONTRACTOR IS RESPONSIBLE FOR IMPLEMENTATION, MAINTENANCE, REPLACEMENT, AND ADDITIONS TO THE SYSTEM AS REQUIRED BY THE OWNER, ENGINEER.
5. THE CONTRACTOR SHALL MAKE A DAILY SURVEILLANCE OF ALL EROSION CONTROL MEASURES AND MAKE ANY NECESSARY REPAIRS OR ADDITIONS TO THE EROSION CONTROL MEASURES AS REQUIRED. THE CONTRACTOR SHALL PROVIDE ADDITIONAL EROSION CONTROL MEASURES AS DETERMINED NECESSARY BY THE INSPECTOR AND/OR PROJECT ENGINEER. FAILURE TO COMPLY WITH ALL LOCAL AND STATE EROSION CONTROL REQUIREMENTS
MAY RESULT IN CIVIL PENALTIES BEING LEVIED AGAINST THE CONTRACTOR.
6. PRIOR TO CLEARING AND GRADING THE CONTRACTOR SHALL PROTECT TREES TO BE SAVED WITH HIGH VISIBILITY FENCING AT THE ROOT PROTECTION DELINEATION OR OTHERWISE PROTECTED AS DIRECTED BY THE ENGINEER, CITY STAFF, OR OWNERS REPRESENTATIVE. CLEARING AND GRADING LIMITS SHALL BE STAKED IN THE FIELD PRIOR
TO EXCAVATION.
7. ALL STORM DRAINAGE INLETS RECEIVING RUNOFF FROM THE PROJECT DURING CONSTRUCTION SHALL BE PROTECTED SO THAT SEDIMENT-LADEN WATER WILL BE FILTERED BEFORE ENTERING THE CONVEYANCE SYSTEM.
8. ALL OFF-SITE CATCH BASINS IMMEDIATELY ADJACENT TO THE PROPOSED SITE SHALL BE PROTECTED FROM
SILTATION.
9. THE CONSTRUCTION OF TRENCHES (E.G., PIPES, UNDERGROUND UTILITY LINES AND STRUCTURES) SHALL BE
SUBJECT TO THE FOLLOWING CRITERIA:
A. NO MORE THAN 300 FEET OF TRENCH ON A DOWNSLOPE OF MORE THAN FIVE PERCENT SHALL BE OPENED AT ONE
TIME.
B. EXCAVATED MATERIAL SHALL BE PLACED ON THE UPHILL SIDE OF TRENCHES.
10. TRENCH DEWATERING DEVICES SHALL BE DISCHARGED IN A MANNER THAT WILL NOT ADVERSELY AFFECT
STREAMS, DRAINAGE SYSTEMS, OR OFF-SITE PROPERTIES.
11. TRACKING OF SOIL, MUD, OR DEBRIS OFF-SITE IS NOT ALLOWED. SOIL, MUD, OR DEBRIS TRACKED ONTO A PUBLIC ROADWAY, SHALL BE REMOVED BY THE END OF THAT WORKING DAY. TO PREVENT THE TRACKING OF SOIL, MUD, OR DEBRIS ONTO PUBLIC ROADWAYS, SWEEPING OR WASHING OF THE VEHICLE'S TIRES MAY BE REQUIRED PRIOR TO
ENTERING A PUBLIC ROADWAY.
12. DROP-IN CATCH BASIN FILTERS MAY BE USED IN PLACE OF OTHER STANDARD INLET PROTECTION PRACTICES. THIS INLET PROTECTION TECHNOLOGY CAN BE USED IN SITUATIONS WHERE RIGHT-OF-WAY FLOODING WOULD BE
PROBLEMATIC.
13. TO MAINTAIN FUNCTION, THE CONTRACTOR SHALL REMOVE AND CLEAN OR REPLACE FILTERS AFTER EACH STORM EVENT. CONTACT THE JURISDICTION TO DETERMINE ITS ACCEPTANCE OF SPECIFIC FILTER PRODUCTS, PRIOR TO
INSTALLATION.
14. NO MATERIAL SHALL BE STOCKPILED ON PAVEMENT WITHOUT AUTHORIZATION FROM THE PROJECT ENGINEER OR OWNERS REPRESENTATIVE WHICH WILL BE CONDITIONAL ON IMPLEMENTATION OF A PROCEDURE TO PREVENT
SEDIMENT TRANSPORT.
15. ALL TEMPORARY EROSION CONTROL MEASURES SHALL BE REMOVED WITHIN 30 DAYS AFTER FINAL SITE STABILIZATION HAS BEEN ACHIEVED OR AFTER THE MEASURES ARE NO LONGER NEEDED. SEDIMENT COLLECTED IN TRAPS, PONDS, OR SILT FENCE SHALL BE REMOVED AND DISPOSED IN AN APPROVED MANNER OR STABILIZED ON SITE. DISTURBED SOIL AREAS RESULTING FROM SEDIMENT REMOVAL SHALL BE PERMANENTLY STABILIZED WITHIN
SEVEN (7) DAYS.
16. CONTRACTOR SHALL PLACE WADDLES ON THE DOWN SLOPE SIDE OF THE LIMITS OF DISTURBANCE.
17. CONTRACTOR SHALL PLACE FILTER FABRIC DOWN FOR A BARRIER PRIOR TO PLACING EXCAVATION SPOILS
ADJACENT TO TRENCHING TO SEPARATE EXISTING GROUND FROM STOCKPILED MATERIAL.
GENERAL CONSTRUCTION NOTES: GENERAL GRADING NOTES:
GENERAL EROSION CONTROL NOTES:
10/21/24
6"
(MIN.)
6"
(MIN.)
1/2" MIN./1" MAX.
24" ACCESS RISER WITH
LOCKING GAS TIGHT LID
(TYP.)
FINISHED GRADE
(ELEVATION VARIES
FROM 1263' TO 1265')
4"x2"
REDUCER
2" DIA. SCH
40 PVC
FORCE MAIN
DIRECTION
OF FLOW
TRANSITION 2'
OUTSIDE OF
TANK
4" DIA. TURNDOWN
MAX. EFFLUENT LEVEL
10' LIQUID LEVEL
6" TALL x 12"
LONG SLOT
4'-0"
4" DIA. SCH 40 PVC
INTERCONNECT
4" DIA. TURNDOWN
MAX. EFFLUENT LEVEL
10' LIQUID LEVEL
6" TALL x 12"
LONG SLOT
4" DIA. SCH 40 PVC
INTERCONNECT
4" DIA. TURNDOWN
MAX. EFFLUENT LEVEL
10' LIQUID LEVEL
6" TALL x 12"
LONG SLOT
4'-0" 4'-0"
4" DIA. SCH 40 PVC
INTERCONNECT
24" (MAX.)
(3) 8,000 GALLON SEPTIC
TANKS IN SERIES
(INW PRECAST 8000-ST)
OR ENGINEER APPROVED EQUAL
EL. 1263.00
EL. 1262.75
EL. 1262.50
EL. 1250.33
EL. 1250.58
EL. 1250.83
ACTIVATED CARBON
FILTER LID
(TYP.)
4" DIA. SCH 40 PVC
INTERCONNECT
4" DIA. TURNDOWN
6" TALL x 12"
LONG SLOT
8" DIA. SCH 40 PVC
4" DIA. SCH 40 PVC
INTERCONNECT
4" DIA. TURNDOWN
1'-6"
ORENCO BIOTUBE
OR ENGINEER APPROVED EQUAL
6" TALL x 12"
LONG SLOT
FILTER CARTRIDGE
EFFLUENT
PUMP
FLOW INDUCER
LOW LEVEL
ALARM
REDUNDANT OFF
TIMER ON/OFF
HIGH LEVEL
ALARM
DISCHARGE
TO APV
FLEXIBLE HOSE
DISCHARGE
ASSEMBLY
PVC SPLICE BOX
WITH CORD
GRIPS
CONDUIT TO
CONTROL PANEL
30" DIA. ACCESS RISER
WITH LOCKING COVER
20" 22"
60"
24" (MAX.)
(2) 6,000 GALLON PUMP TANKS IN SERIES
(INW PRECAST 6000-ST)
OR ENGINEER APPROVED EQUAL
8"8"8"
LAG TIMER ON/OFF
48"
EL. 1262.50 EL. 1262.50
EL. 1252.83
FINISHED GRADE
(ELEVATION VARIES
FROM 1263' TO 1265')
EL. 1252.83
FLOW METER
(ORENCO FM150 OR
APPROVED EQUAL)
DIRECTION
OF FLOW
UNION
15" (MIN.) 7.5"
(MIN.)
NDS PRO SERIES 13"x24"x15" RECTANGULAR
VALVE BOX (222BCB) WITH COVER
(121BCDMCIFB) OR APPROVED EQUAL
NOTE:
METER TO BE INSTALLED SO THAT IT REMAINS FULL AT ALL TIMES.
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
TANK DETAILS
AS SHOWN
M
AT
C H
LI
N
E (S
EE
B
EL
O
W
(S
EE
A
BO
VE
M
AT
C H
LI
N
E
1 NOT TO SCALE
SEPTIC TANK CHAMBERS 1-3
2 NOT TO SCALE
PUMP TANK CHAMBERS 1-2
3 NOT TO SCALE
1.5" FLOW METER IN VALVE BOX
10/21/24
18"
18"
FINISHED
GRADE
TO PRESSURE DISTRIBUTION
(6 TOTAL, 3 EA. SIDE)
ONE SIDE SHOWN FOR CLARITY
PEA GRAVEL
BELOW VALVE
2" PVC ELL WITH
2" x 1 1/2" REDUCER
(TYP.)
1 1/2" ELL
(TYP.)
2" PVC SCH 40 PIPE
FROM DOSING
CHAMBER
FINISHED GRADE
ELEV: xxx
BASE OF VALVE
ELEV: xxx
(OR HIGHER)
1 1/2" BALLVALVE
2" x 1 1/2" REDUCER
24" DIA. RISER
WITH LOCKING LID
SIX-WAY DISTRIBUTING
VALVE ORENCO ADV6606A
1 1/2" UNION
(TYP.)
FLOAT CORD
SPLICE BOX
GAS AND WATERTIGHT
SPLICE BOX FOR PUMP
CORDS
BALL VALVE
UNION CHECK
VALVES
DOSING TANK
2" DIA.
TRANSPORT LINE
SIX-WAY
DISTRIBUTING
VALVE ASSEMBLY DISCHARGE LATERALS
(6 TOTAL)
2" FLOW METER
IN VALVE BOX
1. TRENCHING SHALL MEET THE REQUIREMENTS OF SECTION
7-10.3(7) OF THE WSDOT SPECIFICATIONS.
2. BEDDING MATERIAL FOR RIGID PIPE SHALL BE CRUSHED,
PARTIALLY CRUSHED, OR NATURALLY OCCURRING
GRANULAR MATERIAL CONFORMING TO THE FOLLOWING
GRADATION:
SIEVE SIZE PERCENT PASSING
1-1/4" SQUARE 100
1/4" SQUARE 30-50
U.S. NO. 40 3-18
U.S. NO. 200 7.0 MAX.
SAND EQUIVALENT 35 MIN.
3. ALL PERCENTAGES ARE BY WEIGHT. NATIVE MATERIAL
SHALL NOT BE USED FOR PIPE BEDDING. GRAVEL BACKFILL
FOR ABOVE BEDDING SHALL BE IN ACCORDANCE WITH
WSDOT STD. SPEC 7-08.3(3)
SEE
NOTE 1
36" MIN. (UNDER DRIVING SURFACE)
1`8" MIN. (UNDER LANDSCAPE)
PIPE BEDDING MATERIAL
(SEE NOTE 2)
6" (MIN.)
4" (MIN.)
UNDISTURBED OR
COMPACTED SUB-GRADE
BACKFILL MATERIAL
(SEE NOTE 2)
TRANSPORT /
RETURN
PIPES
NOTE
BACKFILL MATERIAL SHALL NOT HAVE PARTICLE SIZE GREATER THAN 1"
WITHIN 6" OF THE PIPE OR THE CONTRACTOR HAS THE OPTION TO USE
GRAVEL BACKFILL PIPE ZONE BEDDING CONFORMING TO W.S.D.O.T. 9-03.12 (3).
1.5' (MIN.)
4"
6"
4" (MIN.)
PER DESIGN
METALLIC MARKING TAPE
(TYP.)
SUBGRADE ELEVATION
PVC SCH 40 PIPE
GRAVEL BACKFILL FOR
PIPE ZONE BEDDING PER
W.S.D.O.T. 9-03.12(3), 95%
COMPACTION
BANK RUN GRAVEL FOR
TRENCH BACKFILL
MEETING W.S.D.O.T.
9-03.19, 95%
COMPACTION. 6"
MAXIMUM LIFTS
96"
48"
6"
54"
12" (TYP.)
3" DIA.
GALVANIZED POST
(TYP.)
CONTROL PANEL IN
LOCKABLE STEEL OR
FIBERGLASS NEMA 4X
ENCLOSURE
GALVANIZED UNISTRUT
(TYP.)
3" GALVANIZED CAP
(TYP.)
PARKS
STATE
RECREATION
WASHINGTON
COMMISSION
AND
45843REG I S T E R E D
S
TA
TE
OF WASH I NGTON
PROFESS IONAL E NG I N
EE
R
SO
N J. AJ CO
A
B
J
SON
DETAILS
AS SHOWN
1 NOT TO SCALE
SIX-WAY ADV VALVE
GENERAL PROJECT NOTES
1. SYSTEM INSTALLER SHALL MEET THE FOLLOWING CRITERIA:
1.1. SHALL BE CERTIFIED AS AN INSTALLER OR OTHERWISE
APPROVED BY WSDOH.
1.2. SHALL HAVE DEMONSTRABLE EXPERIENCE OF HAVING
INSTALLED AT LEAST 3 SYSTEMS WITH AVERAGE DESIGN
FLOWS OF AT LEAST 3,000 GALLONS PER DAY.
2. ALL CONSTRUCTION TO MEET THE WASHINGTON STATE
DEPARTMENT OF HEALTH (WAC 246-272B) AND COUNTY
REGULATIONS.
3. SITE PLAN, EXISTING STRUCTURES AND TOPOGRAPHY BY
OTHERS. ADC MAKES NO ASSURANCES AS TO THEIR
ACCURACY.
4. CUTS (EXCAVATIONS) OF GREATER THAN 2FT BUT LESS THAN
5FT IN HEIGHT SHALL NOT BE MADE WITHIN 15FT PLUS THE
HEIGHT OF THE CUT DOWNSLOPE OF THE DRAINFIELD AREAS.
CUTS OF 5FT OR MORE IN HEIGHT SHALL NOT BE MADE WITHIN
50FT DOWNSLOPE OF DRAINFIELD AREAS.
5. FOLLOW MANUFACTURERS' RECOMMENDATIONS FOR
PLACEMENT AND TESTING OF TANKS AND ASSOCIATED
EQUIPMENT.
8. EXCAVATIONS GREATER THAN 48” IN DEPTH SHALL BE SHORED
IN COMPLIANCE WITH RCW 39.04.180, WAC 269-155-657 AND RCW
49.17.
9. CONIFER TREES AND LARGE SHRUBS SHALL BE LEFT INTACT
AND ALL VEGETATIVE PLANTINGS IN THE DRAINFIELD AREA
SHALL BE LIMITED TO SMALL, NATIVE PLANT AND SHRUBS.
10. DURING CONSTRUCTION PRECAUTIONS SHALL BE TAKEN TO
MINIMIZE SOIL DISTURBANCE AND COMPACTION IN THE
DRAINFIELD AREAS. DO NOT DRIVE, PARK, PAVE OVER, OR
REMOVE SOILS IN PRIMARY OR RESERVE DRAINFIELD AREAS.
11. VEGETATION MAY NOT BE REMOVED WITHOUT FIRST OBTAINING
APPROVAL AND GUIDANCE FROM THE DESIGN ENGINEER AND
PROJECT OWNER. DISTURBANCE OF VEGETATION IN THE DRAIN
FIELD SHALL BE MINIMIZED AND ONLY PERFORMED BY THE LOSS
INSTALLER. ROOT SYSTEMS SHALL BE LEFT INTACT TO THE
GREATEST EXTENT POSSIBLE.
12. PRIOR TO ANY SOIL DISTURBING ACTIVITY ON SITE THE
GENERAL CONTRACTOR SHALL STAKE THE CORNERS OF THE
DRAIN FIELDS, PROVIDE BARRIER FENCING AND ENSURE THAT
THE AREA IS NOT DISTURBED THROUGHOUT THE
CONSTRUCTION PHASE.
13. CONTRACTOR SHALL DECOMMISSION THE EXISTING SEPTIC
SYSTEM IN ACCORDANCE WITH COUNTY HEALTH DEPARTMENT.
DECOMMISSIONING PERMITS AND APPLICATIONS SHALL BE
OBTAINED BY THE CONTRACTOR.
ONSITE SYSTEM DESIGN CAPACITY
1. THE SYSTEM IS DESIGNED TO TREAT AND DISPERSE
WASTEWATER GENERATED AT FULL BUILDOUT DURING THE
PEAK SEASON OF JUNE THROUGH SEPTEMBER. SEE
ENGINEERING REPORT FOR BASIS OF OPERATING CAPACITY
AND DESIGN FLOW.
2. THE SYSTEM IS DESIGNED FOR SANITARY WASTEWATER
STRENGTH AND CHARACTERISTICS OF RESIDENTIAL
WASTEWATER. THE LOSS IS DESIGNED FOR AN OPERATING
CAPACITY AS OUTLINED IN THE ENGINEERING REPORT. IT IS THE
OWNER/OPERATOR'S RESPONSIBILITY TO ENSURE THESE LIMITS
ARE NOT EXCEEDED (SEE ENGINEERING REPORT FOR FULL
BASIS OF DESIGN).
TESTING AND INSPECTION REQUIREMENTS
1. INSTALLER SHALL TEST TANKS TO ENSURE THEY ARE WATER
TIGHT AFTER INSTALLATION AND PRIOR TO APPROVAL OF THE
SYSTEM FOR USE.
CONCRETE TANKS: HYDROSTATIC TESTING SHALL BE USED ON
CONCRETE TANKS. INSTALLER SHALL TEST TANKS BY:
1. SEAL THE EMPTY TANK;
2. SEAL ACCESS OPENINGS, RISERS, AND INLET AND
OUTLET PIPES;
3. FILL THE TANK WITH WATER TWO INCHES INTO THE
RISER AND LET STAND FOR TWENTY-FOUR HOURS;
4. ADD WATER TO THE TANK, IF NECESSARY, TO THE
ORIGINAL LEVEL;
5. THE TANK PASSES IF THE WATER LEVEL IS
UNCHANGED AFTER ONE HOUR;
6. THE DESIGN ENGINEER SHALL REJECT TANKS THAT DO
NOT MEET THE WATER TIGHTNESS STANDARD.
2. ALL GRAVITY SEWER LINES AND TRANSPORT PIPE SHALL BE
TESTED FOR TIGHTNESS BY USE OF A LOW PRESSURE AIR TEST
IN ACCORDANCE TO WSDOT STANDARD SPECIFICATIONS.
3. PRESSURE DISTRIBUTION INSPECTION REQUIRES THAT ALL
CONNECTIONS, CHECK VALVES, AND MANIFOLDS BE EXPOSED
OR FLAGGED TO ALLOW DESIGN ENGINEER TO VISUALLY
OBSERVE CONNECTIONS.
4. SYSTEM MAY NOT BE PLACED INTO SERVICE UNTIL WA D.O.H.
HAS COMPLETED FINAL INSPECTION OF SYSTEM, HAS
OBSERVED A FUNCTIONAL TEST OF SYSTEM AND HAS ISSUED
FINAL APPROVAL TO OPERATE. D.O.H. REQUIRES TEN DAYS
NOTICE PRIOR TO FINAL INSPECTION AND TESTING.
2 NOT TO SCALE
DOSE CHAMBER PUMP - TOP VALVE 3 NOT TO SCALE
VALVE LOCATION SCHEMATIC PROFILE
4 NOT TO SCALE
PRESSURE SEWER BEDDING AND BACKFILL
5 NOT TO SCALE
GRAVITY SEWER BEDDING AND BACKFILL
SPECIFICATIONS
1. SEPTIC TANKS - (3) 8,000 GALLON INW PRECAST 8000-ST TANKS AS
CONFIGURED IN PLAN OR APPROVED EQUAL.
2. PUMP TANKS - (2) 6,000 GALLON INW PRECAST 6000-ST TANKS AS
CONFIGURED IN PLAN OR APPROVED EQUAL.
3. PUMP VAULT - ORENCO PVU120-18-19L APPROVED EQUAL.
4. PUMPS - DUPLEX ORENCO PF200512, 0.5HP 240V 1PH APPROVED EQUAL.
5. FLOW METER - ORENCO FM-150 APPROVED EQUAL.
6. AUTOMATIC DISTRIBUTION VALVE - ORENCO V6606A APPROVED EQUAL.
7. CONTROL PANEL - SJE RHOMBUS IFN PANEL CONFIGURED FOR DUPLEX
TIMED DOSING, REDUNDANT OFF, TIMER ON/OFF, OVERRIDE TIMER
ON/OFF, HIGH LEVEL ALARM APPROVED EQUAL.
6 NOT TO SCALE
CONTROL PANEL MOUNTING DETAIL
10/21/24
File details come from the government source that posted it. Updated .