ARMY & AIR FORCE EXCHANGE SERVICE
P.O.BOX 660202
Dallas, Texas 75266-0202 214-312-2011
Dear Sir or Madam, The Army & Air Force Exchange Service is currently in the process of reviewing its Data Center Maintenance located at the Exchange’s Headquarters and Stoneridge locations in Dallas, TX.
The Exchange is looking to improve efficiencies by obtaining one provider that can perform all duties required to maintain the Exchange Headquarters and Stoneridge Data Centers.
Currently this Request for Information (RFI) covers:
Headquarters and Stoneridge Data Center Requirements
Mechanic Room Requirements
General Yard Requirements
The Exchange is a joint non-appropriated fund instrumentality of the Department of Defense (DoD) and provides quality merchandise and services to active duty, Guard and Reserve members, military retirees and their families at competitively low prices. The Exchange is now in its 118th year. Shopping the Exchange offers an average overall savings of 25 percent compared to shopping the competition. The Exchange returned $203 million to the military services in 2011. Shoppers can enjoy Exchange benefits in many ways, with the greatest value being the Exchange pledge "We go where you go," serving troops worldwide.
The Exchange is responsible for more than 3,700 facilities worldwide in more than 30 countries, 50 states and five U.S. territories. The Exchange operates 157 main stores, 182 Military Clothing facilities, over 1,000 specialty stores (gas stations, bookstores, Class Six, etc.) and more than 120 theaters. Plus the Exchange has more than 2,100 fast food restaurants, such as Taco Bell, Burger King and Subway. Concession operations overseen by the Exchange add nearly 6,000 more activities.
The desired requirements and current equipment information are outlined in attachment 1.
Your responses may be used to further evaluate and/or refine our requirement.
If you are interested in this potential upcoming procurement, please provide:
1. Responses to the desired requirements and how you meet these.
2. Please provide a brief summary of your company including:
a. How long you have been providing this service(s)?
b. A white paper describing your company and service(s).
c. List of major customers using this service(s).
3. Is your company interested in receiving our Request for Proposal (RFP) should we issue one for this effort? If so, please provide contact information for your company.
4. Does your company have a GSA Schedule or any other type of Government Wide Acquisition Contracts (GWAC) Contract?
Again, this is a Request for Information only. The Exchange is not seeking a firm price quote.
However, the Exchange does want to understand how the industry prices these solutions.
Please provide budgetary numbers with your response. Do not include a price quote. In the event the Exchange solicits, price quotes will be requested at that time.
Responses to this RFI are required by close of business 18 February 2014 via email to:
olsonje@aafes.com. The solicitation will be issued only to those companies that respond to this request.
Regards, Jennifer Olson Contracting Officer Technology Goods & Services Procurement Division Army & Air Force Exchange Service
214-312-4857 / DSN 967-4857
olsonje@aafes.com Visit our online store! www.shopmyexchange.com mailto:olsonje@aafes.com mailto:olsonje@aafes.com http://www.shopmyexchange.com/
Frequency Qty Manufacturer Type Model
Semi-Annual PM 6 MGE MGE 750 KVA UPS MGE EPS 6000 / 750 KVA
Semi- Annual PM 2 MGE MGE UPS Static Switch Continuous Duty Static Switch
Quarterly 1,920 UPS Power Batteries VRLA HX 800 Batteries 6 volt batteries
Annual 1 Russelectric Utility and Generator Control Panels Russelectric
Annual 2 Square D Switchgear III Powerzone Switchgear
Recertify every 3 Years 13 Circuit Breakers in Russelec panels Receritfy to NETA & Pearl Standards AKR & AKRT
Quarterly 3 Cummins Generator Set 1250 DFLC
As Needed 3 Fuel Delivery 1250 DFLC
Annual PM 26 MGE Power Distribution Units (12) Stand-Alone, (14) attached to STS's
Annual PM 5 MGE / Cyberex Digital Static Switch DSTS-FR-30400-2-6-2-5CB35 (600A)
Annual PM 2 MGE / Cyberex Digital Static Switch DSTS-FR-30400-2-6-2-5CB35 (400A)
Annual 1 None Electrostatic cleaning of DC floor & perforated tiles 30,000 sf
Every 3 years 1 None Vacuuming under data center floor 30,000 sf
Annual 2 Pioneer Gas Monitor RKI Gas Monitoring System RKI
Annual 1 Veeder Root UST Monitoring System TLS-350
Quarterly 30 ELU Batteries VRLA Batteries 12 volt batteries
Annual 3 Current Technology SF80 Suppression Filter System SF80
Annual Mat Ground Testing In Data Center and Mech. Room
Annual ARC Flash Protection Rating Switchgear
Annual Thermal Imaging 1 Square D MSB 'Dirty' Circuit Board Panel Square D
Annual Thermal Imaging 1 Square D MSB 'Clean' Circuit Board Panel Square D
Annual Thermal Imaging 2 Square D Switchgear III Powerzone Switchgear
Annual Thermal Imaging multiple Square D Disconnect boxes for PDU's & CRAC's Square D
Annual Thermal Imaging 26 MGE Power Distribution Units MGE
Annual Thermal Imaging 7 Cyberex Static Switches Cyberex
Annual Thermal Imaging 2 Russelectric TVSS - Surge Suppressor Russelectric
Annual Thermal Imaging 6 Russelectric Utility and Generator Control Panels Russelectric
Quarterly PM 1 Kohler Generator 350-REOZVC
As Needed 1 Fuel Delivery 350-REOZVC
Quarterly PM 1 MGE Comet MGE Comet UPS System MGE Comet
Quarterly PM 36 UPS Batteries (in MGE Comet) Stoneridge UPS 6 volt
Annual Professional assessment on equipment placement, obtain samples of data center temps, receive an as-is CFD model of under-floor airflow and pressure, and a professional report on problems and recommendations.
HEADQUARTERS
STONERIDGE
Request for Information (RFI)
Attachment 1
File details come from the government source that posted it. Updated .