ESBD_File_353717_HHS0014504 Solicitation Addendum Drawing 2.pdf

PDF 113 KB Posted

Attached to
HHS0014504 Reverse Osmosis Control Panel
Solicitation number
HHS0014504
Issued by
Travis County, Austin City, Texas

About this file

The document is a technical drawing and specification for a Reverse Osmosis (RO) system and is related to the HHS0014504 state and local contract opportunity in Texas. The RO system is a 3-stage, 4-high configuration that includes a stainless steel structural frame, a NEMA 4X hydraulic panel, a 480V/3Ph/60Hz electrical system, and various components such as an inlet filter housing, RO booster pump, valves, and piping. The contract opportunity is for the Department of State Health Services (DSHS) to design, program, and install a replacement control panel for the RO/Deionization Water Purification system. The jurisdictions involved are Travis County and the City of Austin.

The drawing and specification provide detailed technical information about the RO system's dimensions, materials, capacities, and other features. Pricing, funding sources, and other commercial terms are not included in this document, which appears to be focused on the technical requirements and specifications of the RO system.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

C

B

A

8 7 6 5 4 3 2 1

STANDARD STAINLESS STEEL FEATURES AND SPECIFICATIONS

1. Structural Frame

2. Structural Frame Finish

304SS Structural Tubing, ASTM A554 Buff Finish

-------- 48" -------+---------------------- 148"

---------------------i------ 48" ---------1•-1

3. Cantrel Panel

4. Hydraulic Panel

304SS, NEMA 4X

304SS Plate, ASTM A240, Buff Finish

304SS, 150# RF, ASTM A182

CLEARANCE REQ'D

FOR ELEMENT REMOVAL

TP 1

...----i

ELECTRICAL

480 V / 3PH / 60 HZ

(SEE CHART FOR FLA)

RO HOUSING, FRP(TYP)

RATED 300 PSI

DISCONNECT 1STARTER

PANEL �181

CONTROL

PANEL

NEMA 4X

304 S5

74•

ANCHOR BOLTS

Pl Pl

HYDRAULIC

PANEL

c:::D:J c:::D:J

RECIRC WASTE

V/>J..VE V/>J..VE

PLAN VIEW

TP

INLET

FILTER

HOUSING

'-----------11------------�prz> sv

RO

PUMP

�----------- 83"'---------------

NOTES:

1. MODEL XL-3L-4H SHOWN.

2. ALL PUMP MOTORS ARE 480 VAC / 3 PH / 60 HZ.

3. INLET FLANGES ARE 150# RF 304 SS

4. PRODUCT AND WASTE FLANGES ARE 150# RF SCH80 PVC.

5. SY= SAMPLE VALVE 1/4" PVC.

6. Pl= PRESSURE GAUGE

7. RO FRAME MUST BE LEVELED AND ANCHORED PROPERLY BEFORE OPERATING.

8. HMI= ALLEN-BRADLEY COLOR TOUCH SCREEN CONTROL.

9. DO NOT SCALE DRAWING.

10. ALL DIMENSIONS ±2".

7 6

ELEVATION VIEW

CLEARANCE REQ'D

FOR ELEMENT REMOVAL

32"

ANCHOR BOLTS

1 /2",0'HOLE FOR 3/8".0 AB

(4) PLACES

ALL STAINLESS STEEL STRUCTURAL

FRAME-304 SS

WELD TYPE: GTAW (TIG)

ER 308/308L FILLER

RO MODEL

XL-3L-4H

TP101

INLET

2"

5. Inlet Flange

6. Inlet Piping

7. Filter Housing

8. RO Booster Pump

9. Booster Pump Motor

10. Pump Control Valve

11. Waste Control Valve

304SS, SCH10, ASTM A182

304SS, Multi-Cartridge Type, 100 PSI 316SS, Grundfos Model CRN

480VAC/3PH/60HZ, TEFC

316SS, Needle Valve 316SS, Needle Valve

12. Recirculatian Control Valve 316SS, Needle Valve

13. High Pressure Piping

14. Victaulic Clamps

15. Pipe Clamps

16. Air Bleed Valves

17. Pressure Gauges

18. Bolting Hardware

19. Inlet Valve

TP102 TP103 TP104

WASTE PRODUCT Cleaning

Connection

1" 2· 1.5" VIC

6 "77"

316SS Tubing x .065" Wall, ASTM A269 316SS, 600 PSI Rated 304SS w/Polypropylene Insert 316SS Needle Valve 316SS, 2.5" Dial, Liquid Filled

304SS, ANSI 818.2.1

316SS 2" Diaphragm Type

RO HOUSING PUMP FULL LOAD

FEED PORTS HP AMPS@

480V

2" VIC 15 21

SHIPPING

WT. (lbs)

PUMP

CONTROL

VALVE

------- 41"--------1

RIGHT SIDE VIEW

TITLE:

XL RO SERIES

™ REVERSE OSMOSIS

MODEL XL-3L-4H

_. COMPANY: CUSTOMER /I:

(,,� _CROSSLINK ULTRA PURE & INDUSTRIAL

Nanul'adullng DRAWN BY: APPROVED BY: DRAWING

ENGINEERED SYSTEMS TEP CEN 7-45GA_R(O)

DATE: 9/12/07 DATE: 9/12/07

GLENWOOD, ILLINOIS

Tel: 708-756-2417 Fax: 708-754-9897 www.crosslink-manufacturing.com

# OF SHEETS: SHEET #:

1 1 OF 1

REV:

R(O)

D

C

B

A