ESBD_File_351081_251859-24-01-plans.pdf
PDF 10 MB Posted
- Solicitation number
- 251859-24-01
- Issued by
- Hardeman County, Texas
About this file
This document is an ESBD (Electronic State Business Daily) file related to a Request for Contractor (RFC) for Equipment Sheds, Childress District, Project ID #251859-24-01, issued by the Texas Department of Transportation (TxDOT) for a project located in Quanah, Texas. The project involves the construction of equipment sheds, with an estimated cost of $386,000.00 and a bid guarantee/bid bond of $8,000.00. The pre-bid meeting and mandatory site visit are scheduled for February 29, 2024, and the bid submission deadline is April 3, 2024, at 1:00 PM CT. The contract documents are divided into six packages, with the first package containing the required proposal documents. Starting September 1, 2023, all bids must be submitted through the Bonfire platform. Pre-qualification of contractors is waived, but there are specific requirements outlined in the Uniform General Conditions. The use of Historically Underutilized Businesses (HUBs) is mandated if the project estimate or contractor's estimate is greater than or equal to $100,000, and a HUB Subcontracting Plan (HSP) is required with the proposal package.
The contract award will be made to the successful bidder, and the Texas Department of Transportation has the right to reject any and all proposals. Conditional bids will not be considered, and all bids will be publicly opened, with only the successful bids read. The Texas Department of Transportation will strictly adhere to applicable State Laws prohibiting discriminatory practices in the bidding and awarding process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COLLINGSWORTH COUNTY, TX
Support Services Division / Facilities Planning & Management
COPYRIGHT 2024 TEXAS DEPARTMENT OF TRANSPORTATION
6230 E. Stassney Lane
Austin, Texas 78744-3147 c
VICINITY MAP
INDEX OF DRAWINGS
PROJECT:
Project Manager:
ELECTRICAL:
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s Q u a n a h
M
N T
D
S G
N
C
A D
E
L E
C
C
O V
E R
S
H E
E T d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
Q U
A N
A H
M
N T
W
E L L I N
G T
O
E
Q U
I P
M E
T
S
O
R A
G
E
D
I N
S T
A L L A
T I O
N
P R
O J E
C
U M
B E
R
MULTI-SITE PEMB SHED - LTG INSTALLATION
PROJECT
LOCATION
NORTH
THIS PROJECT INCLUDES THE INSTALLATION OF A PRE-ENGINEERED METAL BUILDING ALONG WITH THE LIGHTING AND POWER REQUIRED FOR THE
BUILDING.
SCOPE OF WORK:
ELECTRICAL
E1.01 ELECTRICAL SITE PLAN - QUANAH
E1.02 ELECTRICAL SITE PLAN - WELLINGTON
E2.01 ELECTRICAL FLOOR PLAN - QUANAH
E2.02 ELECTRICAL FLOOR PLAN - WELLINGTON
E3.01 ELECTRICAL ONE-LINE DIAGRAM & SCHEDULES - QUANAH
E3.02 ELECTRICAL ONE-LINE DIAGRAM & SCHEDULES - WELLINGTON
E5.01 ELECTRICAL DETAILS
GENERAL NOTES
1. WORK SHALL CONFORM TO THE CONSTRUCTION DOCUMENTS & ALL
APPLICABLE BUILDING CODES (INCLUDING FEDERAL & STATE CODES,
ORDINANCES, REGULATIONS, ETC.) CONSTRUCTION DOCUMENTS
INCLUDE CIVIL, LANDSCAPE, ARCHITECTURAL, STRUCTURAL, MEP
DRAWINGS & SPECIFICATIONS PLUS ANY ADDENDA TO THE
AFOREMENTIONED.
2. CONSTRUCTION DOCUMENTS ARE INTENDED TO INCLUDE ITEMS
NECESSARY TO CONVEY DESIGN INTENT OF THE WORK.
MANUFACTURERS' INSTRUCTIONS SHALL BE CONSIDERED AS PART OF
THE SPECIFICATIONS WHETHER INCLUDED OR NOT IN THE
SPECIFICATION MANUAL ..
3. PERIODIC SITE VISITS BY OWNER'S REPRESENTATIVE SHALL NOT BE
CONSTRUED AS SUPERVISION OF MEANS, METHODS, TECHNIQUES,
SEQUENCES OR PROCEDURES FOR CONSTRUCTION, NOR IMPLY
RESPONSIBILITY FOR PROVIDING A SAFE PLACE FOR PERFORMANCE
OF WORK BY CONTRACTOR OR CONTRACTOR'S EMPLOYEES, OR
EMPLOYEES OF SUPPLIERS, OR FOR ACCESS, VISITS, USE, WORK,
TRAVEL, OR OCCUPANCY BY ANY PERSON.
4. CONTRACTOR SHALL:
- VERIFY DIMENSIONS & FIELD CONDITIONS BEFORE PROCEEDING.
- NOTIFY ARCHITECT OF FIELD CONDITIONS REQUIRING DEVIATIONS
FROM CONSTRUCTION DOCUMENTS BEFORE THE CONSTRUCTION
OF ANY MODIFICATION.
- PROVIDE ADEQUATE BRACING & SHORING AS NECESSARY UNTIL
PERMANENT SUPPORTS & STIFFENERS ARE INSTALLED.
- IMMEDIATELY REPAIR OR REPLACE DAMAGED OR DEFECTIVE
WORK TO THE APPROVAL OF (AND AT NO ADDITIONAL COST TO)
THE OWNER
- NOTIFY ARCHITECT & APPROPRIATE INSPECTORS AT CRITICAL
CONSTRUCTION MILESTONES IN ORDER TO OBTAIN NECESSARY
APPROVALS & INSPECTIONS PRIOR TO COMMENCEMENT OF
SUBSEQUENT WORK.
- TAKE REASONABLE PRECAUTIONS FOR THE SAFETY OF, AND
PROVIDE REASONABLE PROTECTION TO PREVENT DAMAGE,
INJURY OR LOSS TO:
a) EMPLOYEES & ALL OTHER AFFECTED PERSONS
b) ALL WORK, MATERIALS & EQUIPMENT
c) OTHER PROPERTY AT SITE OR ADJACENT THERETO.
- UPON COMPLETION OF THE WORK, REMOVE MATERIALS, TOOLS &
EQUIPMENT AND LEAVE SITE IN A CONDITION ACCEPTABLE TO
OWNER.
5. RESTORE CIRCUITS, UTILIZATION EQUIPMENT AND SYSTEMS AFFECTED BY SELECTIVE
DEMOLITION TO THE CONDITION NOTED IN THE PRE-WORK SURVEY REPORT.
ELECTRICAL CIRCUITS WITH A PORTION OF THE LOAD REMOVED SHALL HAVE THE
REMOVED LOADS ASSOCIATED CIRCUITRY TERMINATED IN SUCH A MANNER THAT THE
REMAINING LOAD REMAINS FULLY OPERATIONAL.
6. EQUIPMENT, RECEPTACLES, LIGHTS AND TELEPHONE OUTLETS SCHEDULED FOR
DEMOLITION SHALL HAVE THEIR ASSOCIATED CIRCUITRY REMOVED. ASSOCIATED
CIRCUITRY IS DEFINED AS ALL WIRE, CONDUIT, J-BOXES, DEVICE BOXES, WIRING
DEVICES, COVER PLATES, PROTECTIVE DEVICES, PANELS, ETC. ASSOCIATED WITH THE
ITEM SCHEDULED FOR REMOVAL. CONDUIT FOR ITEMS SCHEDULED FOR REMOVAL AND
IN INACCESSIBLE AREAS SHALL BE EMPTIED AND SEALED OR OTHERWISE TERMINATED
IN A SAFE MANNER ACCEPTABLE TO THE OWNER.
7. DAMAGED AREAS CAUSED BY REMOVAL OF ANY OF THE ABOVE ITEMS AND WHICH ARE
NOT CONCEALED BY NEW CONSTRUCTION SHALL BE REPAIRED TO MATCH ADJACENT
SURFACES. OPENINGS CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE
RATED WALLS SHALL BE FIRE STOPPED.
8. REMOVE ABANDONED CONDUIT TO POINT OF CONCEALMENT BEHIND INACCESSIBLE
SURFACES. ENTIRELY REMOVE ABANDONED WIRING.
9. PROVIDE BLANK COVERS AND PLATES AT UNUSED OPENINGS IN BOXES, RACEWAYS,
AUXILIARY GUTTERS, CABINETS, EQUIPMENT CASES AND HOUSINGS SHALL BE CLOSED
TO AFFORD PROTECTION SUBSTANTIALLY EQUIVALENT TO THE EQUIPMENT ENCLOSURE.
10. IF A CONDUIT RUN IS EXPOSED OR A SURFACE RACEWAY LEFT WITHOUT A MOUNTING
SURFACE DUE TO THE REMOVAL OF A PARTITION, THE RACEWAY SHALL BE REROUTED
AS ACCEPTABLE TO THE OWNER/ARCHITECT.
11. PROTECT ELECTRICAL EQUIPMENT, OUTLETS, DEVICES THAT ARE SCHEDULED TO BE
RELOCATED. REPAIR, RESTORE OR REPLACE ITEMS DAMAGED WHEN REMOVED TO THE
APPROVAL OF THE OWNER. NOTIFY OWNER/ARCHITECT/ENGINEER OF ANY ELECTRICAL
EQUIPMENT, OUTLETS AND/OR DEVICES WHICH ARE SCHEDULED TO BE RE-USED THAT
ARE FOUND TO BE UNUSABLE.
12. ASPHALT PAVEMENT WILL BE FURNISHED AND INSTALLED BY THE IN-HOUSE CREW ON
ANY AND ALL TRENCHING WORK CREATED BY THE CONTRACTOR FOR THE CONDUIT
INSTALLATION. CONTRACTOR TO PROVIDE BACK FILL WITH SAND AND EXISTING
MATERIAL ONLY AND COMPACT IN PLACE TO LEVEL UP FOR ANY TRENCHES CREATED
DURING CONSTRUCTION. THIS WILL ELIMINATE ANY ASPHALT WORK ON TRENCHING
DONE FOR UNDERGROUND CONDUIT INSTALLATION.
BUILDING SUMMARY :
EQUIPMENT SHED: 5,760 SQFT.
TOTAL SCOPE: 5,760 SQFT.
SITE # 259866, 259871
BUILDING # 258101, 258183
405 LOOP ROAD (FM 2568), QUANAH, TX 79252
16215 FM 338, WELLINGTON, TX 79095
CHILDRESS DISTRICT (25)
PROJECT NUMBER: 25-1859-24-01
BUILDING CODES :
INTERNATIONAL ENERGY CONSERVATION CODE IECC - 2018
INTERNATIONAL MECHANICAL CODE IMC - 2021
NATIONAL ELECTRIC CODE NEC - 2023
NATIONAL FIRE CODE NFPA 1 - 2021
NATIONAL LIFE SAFETY CODE NFPA 101 - 2021
TxDOT STANDARD SPECS FOR CONSTRUCTION..................HIGHWAYS, STREETS AND BRIDGES - 2014
MICHAEL WASHINGTON, P.E.
Texas Department of Transportation
Support Services Division
Facilities Planning & Management Section
6230 E Stassney Lane, Austin, TX 78744
Phone: (512) 426-0623
E-mail: Michael.Washington@TxDOT.gov
HARDEMEN COUNTY, TX
PROJECT
LOCATION
DAVID CHAPA
(806) 543-1561
David.Chapa@TxDOT.gov
AutoCAD SHX Text 2.0
AutoCAD SHX Text 4.8
AutoCAD SHX Text 2.0
AutoCAD SHX Text 1.9
AutoCAD SHX Text 1.9
AutoCAD SHX Text 2.0
AutoCAD SHX Text 1.0
AutoCAD SHX Text 1.9
AutoCAD SHX Text 4.4
AutoCAD SHX Text
POP 3,413
AutoCAD SHX Text
QUANAH
AutoCAD SHX Text
MUNICIPAL
AutoCAD SHX Text
AIRPORT
AutoCAD SHX Text 3.1
AutoCAD SHX Text 1.1
AutoCAD SHX Text
QUANAH
AutoCAD SHX Text Spring
AutoCAD SHX Text 2.2
AutoCAD SHX Text 1.3
AutoCAD SHX Text 1.7
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.2
AutoCAD SHX Text 1.6
AutoCAD SHX Text 2.0.
AutoCAD SHX Text 1.1
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
MERCER
AutoCAD SHX Text
GREEN
AutoCAD SHX Text
DUBOSE
AutoCAD SHX Text
EARLE
AutoCAD SHX Text
SHAW
AutoCAD SHX Text
SIMPSON
AutoCAD SHX Text
GOLDSTON
AutoCAD SHX Text
COMBS
AutoCAD SHX Text
HUGHES
AutoCAD SHX Text
EDDY
AutoCAD SHX Text
CAIN
AutoCAD SHX Text
ELEVENTH
AutoCAD SHX Text
TWELFTH
AutoCAD SHX Text
THIRTEENTH
AutoCAD SHX Text
FOURTEENTH
AutoCAD SHX Text
FIFTEENTH
AutoCAD SHX Text
SIXTEENTH
AutoCAD SHX Text
KING
AutoCAD SHX Text
ELBERT
AutoCAD SHX Text
STARR
AutoCAD SHX Text McCLELLAND
AutoCAD SHX Text
GOOD
AutoCAD SHX Text
GRANGER
AutoCAD SHX Text
LOUISE
AutoCAD SHX Text
DODGE
AutoCAD SHX Text
MORGAN
AutoCAD SHX Text
MEEK
AutoCAD SHX Text
DUNCAN
AutoCAD SHX Text
TENTH
AutoCAD SHX Text
NINTH
AutoCAD SHX Text
EIGHTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
SIXTH
AutoCAD SHX Text
FIFTH
AutoCAD SHX Text
FOURTH
AutoCAD SHX Text
THIRD
AutoCAD SHX Text
SECOND
AutoCAD SHX Text
NELSON
AutoCAD SHX Text
LORD
AutoCAD SHX Text
BUGBE
AutoCAD SHX Text
PATTERSON
AutoCAD SHX Text
NEWCOMB
AutoCAD SHX Text
CURTIS
AutoCAD SHX Text
LANHAM
AutoCAD SHX Text
BROWINING
AutoCAD SHX Text
ALVORD
AutoCAD SHX Text
MAY
AutoCAD SHX Text
FLOYD
AutoCAD SHX Text
JONES
AutoCAD SHX Text
SETZLER
AutoCAD SHX Text
TIMMONS
AutoCAD SHX Text
FROST
AutoCAD SHX Text
JAMES
AutoCAD SHX Text
BEVERLY
AutoCAD SHX Text
HAHN
AutoCAD SHX Text
FLYNT
AutoCAD SHX Text
WIGLEY
AutoCAD SHX Text
GILES
AutoCAD SHX Text
FLORA
AutoCAD SHX Text
BLACK
AutoCAD SHX Text
HOUSTON
AutoCAD SHX Text 0.8
AutoCAD SHX Text Park
AutoCAD SHX Text Memorial
AutoCAD SHX Text Park
AutoCAD SHX Text Cemetery
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.0
AutoCAD SHX Text 2.0
AutoCAD SHX Text 2.4
AutoCAD SHX Text 2.0
AutoCAD SHX Text
POP 3,043
AutoCAD SHX Text
MARIAN
AutoCAD SHX Text
AIRPARK
AutoCAD SHX Text 3.0
AutoCAD SHX Text
WELLINGTON
AutoCAD SHX Text Creek
AutoCAD SHX Text House
AutoCAD SHX Text Log
AutoCAD SHX Text Creek
AutoCAD SHX Text 1.0
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text 1.0.
AutoCAD SHX Text
FIRST
AutoCAD SHX Text
SECOND
AutoCAD SHX Text
THIRD
AutoCAD SHX Text
FOURTH
AutoCAD SHX Text
FIFTEENTH
AutoCAD SHX Text
FOURTEENTH
AutoCAD SHX Text
THIRTEENTH
AutoCAD SHX Text
ELEVENTH
AutoCAD SHX Text
TENTH
AutoCAD SHX Text
NINTH
AutoCAD SHX Text
EIGHTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
FIFTH
AutoCAD SHX Text
SIXTEENTH
AutoCAD SHX Text
SEVENTEENTH
AutoCAD SHX Text
HOUSTON
AutoCAD SHX Text
GALVESTON
AutoCAD SHX Text
FORT WORTH
AutoCAD SHX Text
ENNIS
AutoCAD SHX Text
DALLAS
AutoCAD SHX Text
CORSICANA
AutoCAD SHX Text
BELTON
AutoCAD SHX Text
ARLINGTON
AutoCAD SHX Text
EAST
AutoCAD SHX Text
WEST
AutoCAD SHX Text
AMARILLO
AutoCAD SHX Text
BOWIE
AutoCAD SHX Text
CHILDRESS
AutoCAD SHX Text
DALHART
AutoCAD SHX Text
ELPASO
AutoCAD SHX Text
FLOYDADA
AutoCAD SHX Text
GRAHAN
AutoCAD SHX Text
HASKELL
AutoCAD SHX Text 1.0
AutoCAD SHX Text
SIXTH
AutoCAD SHX Text 1.1
AutoCAD SHX Text
TWELFTH
AutoCAD SHX Text Ellison
AutoCAD SHX Text Pk
AutoCAD SHX Text Memorial
AutoCAD SHX Text Gardens
AutoCAD SHX Text Cemetery
AutoCAD SHX Text Rodeo
AutoCAD SHX Text Grounds
AutoCAD SHX Text Fairview
AutoCAD SHX Text Cemetery
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
AutoCAD SHX Text 02-06-24
Amy Stone Reviewer Text , 25-1859-24-03
Amy Stone Reviewer Text , 25-1859-24-03
A
B
C
D
E
F
G
H
J
GENERAL NOTES: (THIS SHEET ONLY)
A. REFER TO COVER SHEET FOR ADDITIONAL GENERAL NOTES.
B. ALL SIGHT LIGHTING TO BE CIRCUITED TO PANEL 'LA1'.
NUMBER NEXT TO FIXTURE DENOTES CIRCUIT ON PANEL.
C. CONDUIT LINES SHOWN ON DRAWING ARE DIAGRAMMATIC.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND CHOOSE
APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT
APPROXIMATE CONDUIT SHOWN ON PLANS IS NOT FEASIBLE,
SONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER.
D. LOCATION OF DEVICES ARE DIAGRAMMATICAL. EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD.
CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONFLICTS
PRIOR TO ROUGH-IN.
E. THE CITY OF QUANAH DESIGN GUIDELINES SHALL GOVERN
MATERIAL AND METHODS USED TO DO THIS WORK.
F. COORDINATE EQUIPMENT REQUIREMENTS WITH CABLE
TELEVISION AND TELEPHONE COMPANIES. COORDINATE
MOUNTING REQUIREMENTS IN FIELD.
G. CONDUITS NEED TO BE INSTALLED AS CLOSE AS POSSIBLE TO
THE BACK OF THE BUILDINGS.
H. CIRCUIT SITE LIGHTING THROUGH LIGHTING CONTROL PANEL.
I. PROVIDE EMPTY CONDUITS WITH PULLSTRING AND ENDCAPS.
J. CONDUITS INSTALLED UNDER VEHICULAR TRAFFIC AREAS
SHALL BE INSTALLED A MINIMUM OF 36" BELOW GRADE AND IN
DUCTBANK WITH FLOWABLE FILL, OTHERWISE INSTALL A
MINIMUM OF 24" BELOW GRADE AND IN DUCTBANK WITH
FLOWABLE FILL.
K. ALL EXTERIOR FLEXIBLE CONDUIT TO BE LIQUID-TIGHT.
L. CONTRACTOR TO PROVIDE IN-GRADE HANDHOLE(S), AS
REQUIRED, TO COMPLY WITH MAXIMUM CONDUIT BENDS AS
NOTED IN THE NEC.
M. REFERENCE ELECTRICAL ONE-LINE DIAGRAM, SHEET E3.01,
FOR ADDITIONAL BUILDING LOAD ANALYSIS INFORMATION.
1. EXISTING OVERHEAD PRIMARY ELECTRIC UTILITY LINE TO REMAIN.
2. EXISTING UTILITY POLE TO REMAIN.
3. EXISTING UTILITY RISER POLE WITH TRANSFORMERS AND SERVICE EQUIPMENT
TO REMAIN.
4. APPROXIMATE LOCATION OF EQUIPMENT SHED.
APPROXIMATE LOCATION OF EXISTING PANEL 'LP2' IN MAINTENANCE BUILDING
KEYED NOTES: (THIS SHEET ONLY)
AWM
E1.01ELECTRICAL SITE PLAN
MLW
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s Q u a n a h
M
N T
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
Q U
A N
U
I P
M E
E
D
L
I G
H T
I N
G
L
O O
P
R
O A
D
F
M
Q
U A
N A
H
T
X
H A
R D
E M
U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-08-2024
60'
SCALE: 1 INCH = 30 FOOT
30'0' 15' 90'
SCALE: 1"=30'-0"
ELECTRICAL SITE PLAN
NORTH
TRUE
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E1.01
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
AutoCAD SHX Text 02-06-24
1 2
B C
D E
F G
H J
GENERAL NOTES: (THIS SHEET ONLY)
A. REFER TO COVER SHEET FOR ADDITIONAL GENERAL NOTES.
B. ALL BUILDING LIGHTING TO BE CIRCUITED TO PANEL 'ES'.
NUMBER NEXT TO FIXTURE DENOTES CIRCUIT ON PANEL.
C. CONDUIT LINES SHOWN ON DRAWING ARE DIAGRAMMATIC.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND CHOOSE
APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT
APPROXIMATE CONDUIT SHOWN ON PLANS IS NOT FEASIBLE,
SONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER.
D. LOCATION OF DEVICES ARE DIAGRAMMATICAL. EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD.
CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONFLICTS
PRIOR TO ROUGH-IN.
E. THE CITY OF WELLINGTON DESIGN GUIDELINES SHALL
GOVERN MATERIAL AND METHODS USED TO DO THIS WORK.
F. COORDINATE EQUIPMENT REQUIREMENTS WITH CABLE
TELEVISION AND TELEPHONE COMPANIES. COORDINATE
MOUNTING REQUIREMENTS IN FIELD.
G. CONDUITS NEED TO BE INSTALLED AS CLOSE AS POSSIBLE TO
THE BACK OF THE BUILDINGS.
H. CIRCUIT SITE LIGHTING THROUGH LIGHTING CONTROL PANEL.
I. PROVIDE EMPTY CONDUITS WITH PULLSTRING AND ENDCAPS.
J. CONDUITS INSTALLED UNDER VEHICULAR TRAFFIC AREAS
SHALL BE INSTALLED A MINIMUM OF 36" BELOW GRADE AND IN
DUCTBANK WITH FLOWABLE FILL, OTHERWISE INSTALL A
MINIMUM OF 24" BELOW GRADE AND IN DUCTBANK WITH
FLOWABLE FILL.
K. ALL EXTERIOR FLEXIBLE CONDUIT TO BE LIQUID-TIGHT.
L. CONTRACTOR TO PROVIDE IN-GRADE HANDHOLE(S), AS
REQUIRED, TO COMPLY WITH MAXIMUM CONDUIT BENDS AS
NOTED IN THE NEC.
M. REFERENCE ELECTRICAL ONE-LINE DIAGRAM, SHEET E3.02,
FOR ADDITIONAL BUILDING LOAD ANALYSIS INFORMATION.
1. EXISTING OVERHEAD PRIMARY ELECTRIC UTILITY LINE TO REMAIN.
2. EXISTING UTILITY POLE TO REMAIN.
3. EXISTING UTILITY RISER POLE WITH TRANSFORMERS AND SERVICE EQUIPMENT
TO REMAIN.
4. APPROXIMATE LOCATION OF EQUIPMENT SHED.
5. APPROXIMATE LOCATION OF EXISTING PANEL 'BP' NEAR BRINE TANK. PROVIDE
FEED TO NEW LOAD CENTER AT EQUIPMENT SHED FOR BUILDING LIGHTING.
PROVIDE A NEW 2-POLE CIRCUIT BREAKER IN PANEL BUSSED SPACE TO POWER
NEW LOAD CENTER AS NOTED ON SCHEDULE, SHEET E3.02.
6. EXISTING UNDERGROUND SECONDARY FEED FROM SERVICE DISCONNECT
FEEDING EXISTING PANEL 'BP' TO REMAIN.
7. NEW UNDERGROUND FEED TO LOAD CENTER IN EQUIPMENT SHED. REFERENCE
ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
NEW POLE MOUNTED FLOOD LIGHT FIXTURE AS INDICATED. PROVIDE A NEW
KEYED NOTES: (THIS SHEET ONLY)
AWM
E1.02ELECTRICAL SITE PLAN
MLW
60'
SCALE: 1 INCH = 30 FOOT
30'0' 15' 90'
SCALE: 1"=30'-0"
ELECTRICAL SITE PLAN
NORTH
TRUE
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E1.02
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s W e l l i n g t o n
A
E M
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
W E
L L
I N
G T
Q U
I P
M E
E
D
L
T G
F
M
W
E L
L I N
G T
O N
T
X
C O
L L
I N
G S
W O
R T
H
C
O U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-06-2024
SCALE: NOT-TO-SCALE
SERVICE ENTRANCE EQUIPMENT
E1.02
SCALE: NOT-TO-SCALE
EXISTING PANEL 'BP'
E1.02
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
AutoCAD SHX Text 02-06-24
Amy Stone
25-1859-24-03
A B
C D
E F
G H
J
Aa Aa
AaAa
Aa Aa
Ab Ab
AbAb
Ac Ac
AcAc
B
B
B
B
B
B
B
B
6 5
6 5
6 5
6 5
6 5
6 5
6 5
5 5
3 3
5 5
5 5
GENERAL NOTES: (THIS SHEET ONLY)
A. REFER TO COVER SHEET FOR ADDITIONAL GENERAL NOTES.
B. ALL BUILDING LIGHTING TO BE CIRCUITED TO EXISTING PANEL
'F'. NUMBER NEXT TO FIXTURE DENOTES CIRCUIT ON PANEL.
C. CONDUIT LINES SHOWN ON DRAWING ARE DIAGRAMMATIC.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND CHOOSE
APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT
APPROXIMATE CONDUIT SHOWN ON PLANS IS NOT FEASIBLE,
SONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER.
D. LOCATION OF DEVICES ARE DIAGRAMMATICAL. EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD.
CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONFLICTS
PRIOR TO ROUGH-IN.
E. THE CITY OF QUANAH DESIGN GUIDELINES SHALL GOVERN
MATERIAL AND METHODS USED TO DO THIS WORK.
F. CONDUITS NEED TO BE INSTALLED AS CLOSE AS POSSIBLE TO
THE BACK OF THE BUILDINGS.
G. CIRCUIT SITE LIGHTING THROUGH LIGHTING CONTROL PANEL.
H. PROVIDE EMPTY CONDUITS WITH PULLSTRING AND ENDCAPS.
I. CONDUITS INSTALLED UNDER VEHICULAR TRAFFIC AREAS
SHALL BE INSTALLED A MINIMUM OF 36" BELOW GRADE AND IN
DUCTBANK WITH FLOWABLE FILL, OTHERWISE INSTALL A
MINIMUM OF 24" BELOW GRADE AND IN DUCTBANK WITH
FLOWABLE FILL.
J. ALL EXTERIOR FLEXIBLE CONDUIT TO BE LIQUID-TIGHT.
K. CONTRACTOR TO PROVIDE IN-GRADE HANDHOLE(S), AS
REQUIRED, TO COMPLY WITH MAXIMUM CONDUIT BENDS AS
NOTED IN THE NEC.
L. REFERENCE ELECTRICAL ONE-LINE DIAGRAM, SHEET E3.01,
FOR ADDITIONAL BUILDING LOAD ANALYSIS INFORMATION.
1. EXISTING OVERHEAD PRIMARY ELECTRIC UTILITY LINE TO REMAIN.
2. EXISTING UTILITY POLE TO REMAIN.
3. EXISTING UTILITY RISER POLE WITH POLE MOUNTED TRANSFORMERS AND
UTILITY METER.
4. EXISTING SERVICE ENTRANCE EQUIPMENT TO REMAIN. REFERENCE ONE-LINE
DIAGRAM, SHEET E4.01, FOR ADDITIONAL INFORMATION.
5. COORDINATE LIGHT FIXTURE MOUNTING WITH LOW EVE.
6. COORDINATE LIGHT FIXTURE MOUNTING WITH HIGH EVE.
7. MOUNT TIMER SWITCH TO COLUMNS. COORDINATE EXACT LOCATION WITH
ARCHITECT AND OWNER PRIOR TO ROUGH-IN.
APPROXIMATE LOCATION OF EXISTING PANEL 'LP2' IN MAINTENANCE BUILDING
KEYED NOTES: (THIS SHEET ONLY)
AWM
E2.01ELECTRICAL FLOOR PLAN
MLW
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s Q u a n a h
M
N T
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
A
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
Q U
A N
U
I P
M E
E
D
L
I G
H T
I N
G
L
O O
P
R
O A
D
F
M
Q
U A
N A
H
T
X
H A
R D
E M
U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-08-2024
16'
SCALE: 1/8 INCH = 1 FOOT
8'0' 4' 24'
SCALE: 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN
NORTH
TRUE
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E2.01
AutoCAD SHX Text A
AutoCAD SHX Text Ta
AutoCAD SHX Text Tb
AutoCAD SHX Text Tc
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
Aa Aa
AaAa
Aa Aa
Ab Ab
AbAb
Ac Ac
AcAc
B
B
B
B
B
B
B
B
6 5
6 5
6 5
6 5
6 5
6 5
6 5
3 3
1 1
3 3
3 3
GENERAL NOTES: (THIS SHEET ONLY)
A. REFER TO COVER SHEET FOR ADDITIONAL GENERAL NOTES.
B. ALL BUILDING LIGHTING TO BE CIRCUITED TO NEW PANEL 'ES'.
NUMBER NEXT TO FIXTURE DENOTES CIRCUIT ON PANEL.
C. CONDUIT LINES SHOWN ON DRAWING ARE DIAGRAMMATIC.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND CHOOSE
APPROPRIATE CONDUIT ROUTING. IN THE EVENT THAT
APPROXIMATE CONDUIT SHOWN ON PLANS IS NOT FEASIBLE,
CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER.
D. LOCATION OF DEVICES ARE DIAGRAMMATICAL. EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD.
CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONFLICTS
PRIOR TO ROUGH-IN.
E. THE CITY OF WELLINGTON DESIGN GUIDELINES SHALL
GOVERN MATERIAL AND METHODS USED TO DO THIS WORK.
F. CONDUITS NEED TO BE INSTALLED AS CLOSE AS POSSIBLE TO
THE BACK OF THE BUILDINGS.
G. CIRCUIT SITE LIGHTING THROUGH LIGHTING CONTROL PANEL.
H. PROVIDE EMPTY CONDUITS WITH PULLSTRING AND ENDCAPS.
I. CONDUITS INSTALLED UNDER VEHICULAR TRAFFIC AREAS
SHALL BE INSTALLED A MINIMUM OF 36" BELOW GRADE AND IN
DUCTBANK WITH FLOWABLE FILL, OTHERWISE INSTALL A
MINIMUM OF 24" BELOW GRADE AND IN DUCTBANK WITH
FLOWABLE FILL.
J. ALL EXTERIOR FLEXIBLE CONDUIT TO BE LIQUID-TIGHT.
K. CONTRACTOR TO PROVIDE IN-GRADE HANDHOLE(S), AS
REQUIRED, TO COMPLY WITH MAXIMUM CONDUIT BENDS AS
NOTED IN THE NEC.
L. REFERENCE ELECTRICAL ONE-LINE DIAGRAM, SHEET E3.02,
FOR ADDITIONAL BUILDING LOAD ANALYSIS INFORMATION.
1. EXISTING OVERHEAD PRIMARY ELECTRIC UTILITY LINE TO REMAIN.
2. EXISTING UTILITY SERVICE RISER POLE WITH SERVICE ENTRANCE EQUIPMENT TO
REMAIN.
3. EXISTING UNDERGROUND SECONDARY FEED TO EXISTING PANEL 'BP' TO REMAIN.
4. EXISTING RACK WITH PANEL 'BP' TO REMAIN. REFERENCE ONE-LINE DIAGRAM,
SHEET E3.02, FOR ADDITIONAL INFORMATION. PROVIDE A NEW 2-POLE CIRCUIT
BREAKER IN PANEL BUSSED SPACE TO FEED LOAD CENTER IN EQUIPMENT SHED.
5. COORDINATE LIGHT FIXTURE MOUNTING WITH LOW EVE.
6. COORDINATE LIGHT FIXTURE MOUNTING WITH HIGH EVE.
7. MOUNT TIMER SWITCH TO COLUMNS. COORDINATE EXACT LOCATION WITH
ARCHITECT AND OWNER PRIOR TO ROUGH-IN.
8. NEW UNDERGROUND FEED TO LOAD CENTER IN EQUIPMENT STORAGE BUILDING.
REFERENCE ONE-LINE DIAGRAM, SHEET E3.02, FOR ADDITIONAL INFORMATION.
9. PROVIDE NEW PANEL 'ES' IN EQUIPMENT BAY. COORDINATE FINAL LOCATION
WITH OWNER PRIOR TO ROUGH-IN. REFERENCE PANEL SCHEDULE, SHEET E3.02,
FOR ADDITIONAL INFORMATION.
NEW POLE MOUNTED FLOOD LIGHT FIXTURE AS INDICATED. PROVIDE A NEW
KEYED NOTES: (THIS SHEET ONLY)
AWM
E2.02ELECTRICAL FLOOR PLAN
MLW
SCALE: 1/8" = 1'-0"
ELECTRICAL FLOOR PLAN
NORTH
TRUE
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E2.02
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s W e l l i n g t o n
A
E M
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
W E
L L I N
G T
Q U
I P
M E
E
D
L T
G
F
M
W
E L L I N
G T
O N
T
X
C O
L L I N
G S
W O
R T
H
C
O U
N T
Y
C H
I L D
R E
D
I S
T R
I C
T
02-06-2024
16'
SCALE: 1/8 INCH = 1 FOOT
8'0' 4' 24'
AutoCAD SHX Text Ta
AutoCAD SHX Text Tb
AutoCAD SHX Text Tc
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
AutoCAD SHX Text 02-06-24
Amy Stone
EQUIP SHED
1. EXISTING UTILITY RISER POLE WITH POLE MOUNTED TRANSFORMERS TO REMAIN.
2. EXISTING UTILITY SERVICE METER TO REMAIN.
3. EXISTING 60A CIRCUIT BREAKER IN NEMA 3R ENCLOSURE.
4. EXISTING PANEL 'F' TO REMAIN.
5. EXISTING GROUNDING SYSTEM TO REMAIN. VERIFY COMPLIANCE WITH 2023 NEC
GROUNDING REQUIREMENTS.
6. PROVIDE NEW UNDERGROUND FEED FOR POWER TO EQUIPMENT SHED LIGHTING.
7. LIGHTING TO BE MOUNTED IN EQUIPMENT SHED. REFERENCE ELECTRICAL FLOOR
PLAN, SHEET E2.01, FOR LOCATIONS AND ADDITIONAL INFORMATION.
8. CONTRACTOR TO VERIFY BREAKERS FEEDING EXISTING SITE RECEPTACLES TO
REMAIN. IF BREAKER SHOWN FOR LIGHTING IS CIRCUITED TO USED BREAKER.
CONTRACTOR TO PROVIDE NEW 20A BREAKER IN BUSSED SPACE FOR POWER
CONNECTION.
9. PROVIDE NEW 120/240V, 1PH, 200kA, TYPE 2 SURGE PROTECTION DEVICE WITH
INTEGRAL DISCONNECTING MEANS, NOISE FILTER AND CONTINUOUS &
RESETTABLE SURGE COUNTER. ACT COMMUNICATIONS 455 FAMILY OR TXDOT
APPROVED EQUAL. REFER TO SPECIFICATION SECTION 26 43 13.
10. PROVIDE RECEPTACLE WITH NEW WHILE-IN-USE COVER.
KEYED NOTES: (THIS SHEET ONLY)
GENERAL NOTES: (THIS SHEET ONLY)
A. REFERENCE PANEL SCHEDULES, THIS SHEET, FOR PANEL
SCHEDULES SHOWN ON PLAN.
B. CONTRACTOR TO VERIFY BRANCH CIRCUIT FEEDER USE AND
PROVIDE REQUIRED QUANTITY OF BREAKERS FOR BRANCH
CIRCUITS TO RE-FED FROM NEW DISTRIBUTION PANELBOARDS.
C. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO
MAINTAIN A SAFE WORK ENVIRONMENT AND IN ACCORDANCE WITH
APPLICABLE SAFETY RULES AND PROCEDURES WITHIN NEC, NECA
AND OSHA REQUIREMENTS.
D. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS
MATERIALS SURVEYS FROM THE OWNER'S REPRESENTATIVE.
OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE STATUS
OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE
HAZARDOUS MATERIAL SURVEY. NOTIFY THE OWNER'S
REPRESENTATIVE IF ANY HAZARDOUS MATERIALS ARE SUSPECTED
OR OBSERVED DURING THE COURSE OF EXECUTING THIS
CONTRACT.
E. SURVEY AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR
PARTIAL DEMOLITION PRIOR TO ANY WORK BEING PERFORMED.
SUBMIT REPORT OF THE PRE-WORK SURVEY DETAILING ANY
UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD
WORKING ORDER IN ADVANCE OF ANY DEMOLITION WORK AND
REVIEW WITH THE OWNER'S REPRESENTATIVE.
F. RESTORE CIRCUITS, UTILIZATION EQUIPMENT AND SYSTEMS
AFFECTED BY SELECTIVE DEMOLITION TO THE CONDITION NOTED IN
THE PRE-WORK SURVEY REPORT. ELECTRICAL CIRCUITS WITH A
PORTION OF THE LOAD REMOVED SHALL HAVE THE REMOVED LOADS
ASSOCIATED CIRCUITRY TERMINATED IN SUCH A MANNER THAT THE
REMAINING LOAD REMAINS FULLY OPERATIONAL.
G. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED
MATERIAL. REQUEST THAT THE OWNER PROVIDE DIRECTION ON
DISPOSITION OF SALVAGED MATERIAL FIVE(5) WORKING DAYS PRIOR
TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL
SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE
DELIVERED BY THE CONTRACTOR TO A LOCATION AS DIRECTED.
REMOVE AND DISPOSE ANY SALVAGED MATERIAL NO RETAINED BY
THE OWNER.
H. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF
PANELS, TRANSFORMERS, DISCONNECTS, ETC. TO BE REMOVED.
VERIFY LOCATION AND QUANTITY OF ITEMS TO BE REMOVED. NO
ALLOWANCE WILL BE MADE BECAUSE OF CONTRATOR'S
UNFAMILIARITY WITH THE DETAILS.
I. DAMAGED AREAS CAUSED BY REMOVAL OF ANY OF THE ABOVE
ITEMS AND WHICH ARE NOT CONCEALED BY NEW CONSTRUCTION
SHALL BE REPAIRED TO MATCH ADJACENT SURFACES. OPENINGS
CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED
WALLS SHALL BE FIRE STOPPED.
PROVIDE MINIMUM SCHEDULE 40PVC FOR UNDERGROUND
AWM
E3.01ELECTRICAL ONE-LINE DIAGRAM
MLW
SCALE: NOT-TO-SCALE
ELECTRICAL ONE-LINE DIAGRAM
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E3.01
SCALE: NOT-TO-SCALE
SERVICE EQUIPMENT PHOTO
E3.01
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s Q u a n a h
M
N T
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
Q U
A N
U
I P
M E
E
D
L
I G
H T
I N
G
L
O O
P
R
O A
D
F
M
Q
U A
N A
H
T
X
H A
R D
E M
U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-08-2024
AutoCAD SHX Text
WIRE SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
3#4, 1 #10GND, IN 1-1/2"C
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
EQUIP SHED
1. EXISTING UTILITY RISER POLE WITH OVERHEAD SERVICE FEED TO REMAIN.
2. EXISTING UTILITY SERVICE METER TO REMAIN.
3. EXISTING SERVICE ENTRANCE DISCONNECT TO REMAIN.
4. EXISTING RACK MOUNTED PANEL 'BP' TO REMAIN.
5. EXISTING GROUNDING SYSTEM TO REMAIN. VERIFY COMPLIANCE WITH 2023 NEC
GROUNDING REQUIREMENTS.
6. PROVIDE NEW UNDERGROUND FEED FOR POWER TO PANEL 'ES' AT EQUIPMENT
SHED.
7. LIGHTING TO BE MOUNTED IN EQUIPMENT SHED. REFERENCE ELECTRICAL FLOOR
PLAN, SHEET E2.02, FOR LOCATIONS AND ADDITIONAL INFORMATION.
8. PROVIDE NEW 120/240V, 1PH, 200kA, TYPE 2 SURGE PROTECTION DEVICE WITH
INTEGRAL DISCONNECTING MEANS, NOISE FILTER AND CONTINUOUS &
RESETTABLE SURGE COUNTER. ACT COMMUNICATIONS 455 FAMILY OR TXDOT
APPROVED EQUAL. REFER TO SPECIFICATION SECTION 26 43 13.
KEYED NOTES: (THIS SHEET ONLY)
GENERAL NOTES: (THIS SHEET ONLY)
A. REFERENCE PANEL SCHEDULES, THIS SHEET, FOR PANEL
SCHEDULES SHOWN ON PLAN.
B. CONTRACTOR TO VERIFY BRANCH CIRCUIT FEEDER USE AND
PROVIDE REQUIRED QUANTITY OF BREAKERS FOR BRANCH
CIRCUITS TO RE-FED FROM NEW DISTRIBUTION PANELBOARDS.
C. CONDUCT ALL DEMOLITION WORK IN SUCH A MANNER AS TO
MAINTAIN A SAFE WORK ENVIRONMENT AND IN ACCORDANCE WITH
APPLICABLE SAFETY RULES AND PROCEDURES WITHIN NEC, NECA
AND OSHA REQUIREMENTS.
D. CONTRACTOR SHALL REQUEST AND REVIEW ANY HAZARDOUS
MATERIALS SURVEYS FROM THE OWNER'S REPRESENTATIVE.
OBSERVE RECOMMENDED PRECAUTIONS AND VERIFY THE STATUS
OF ANY REMEDIAL WORK RECOMMENDED OR NOTED WITHIN THE
HAZARDOUS MATERIAL SURVEY. NOTIFY THE OWNER'S
REPRESENTATIVE IF ANY HAZARDOUS MATERIALS ARE SUSPECTED
OR OBSERVED DURING THE COURSE OF EXECUTING THIS
CONTRACT.
E. SURVEY AREAS OF THE FACILITY SCHEDULED FOR RENOVATION OR
PARTIAL DEMOLITION PRIOR TO ANY WORK BEING PERFORMED.
SUBMIT REPORT OF THE PRE-WORK SURVEY DETAILING ANY
UTILIZATION EQUIPMENT OR SYSTEMS THAT ARE NOT IN GOOD
WORKING ORDER IN ADVANCE OF ANY DEMOLITION WORK AND
REVIEW WITH THE OWNER'S REPRESENTATIVE.
F. RESTORE CIRCUITS, UTILIZATION EQUIPMENT AND SYSTEMS
AFFECTED BY SELECTIVE DEMOLITION TO THE CONDITION NOTED IN
THE PRE-WORK SURVEY REPORT. ELECTRICAL CIRCUITS WITH A
PORTION OF THE LOAD REMOVED SHALL HAVE THE REMOVED LOADS
ASSOCIATED CIRCUITRY TERMINATED IN SUCH A MANNER THAT THE
REMAINING LOAD REMAINS FULLY OPERATIONAL.
G. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR SALVAGED
MATERIAL. REQUEST THAT THE OWNER PROVIDE DIRECTION ON
DISPOSITION OF SALVAGED MATERIAL FIVE(5) WORKING DAYS PRIOR
TO REMOVAL. IF SO DIRECTED BY THE OWNER, SALVAGED MATERIAL
SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE
DELIVERED BY THE CONTRACTOR TO A LOCATION AS DIRECTED.
REMOVE AND DISPOSE ANY SALVAGED MATERIAL NO RETAINED BY
THE OWNER.
H. DRAWINGS INDICATE APPROXIMATE LOCATION AND QUANTITY OF
PANELS, TRANSFORMERS, DISCONNECTS, ETC. TO BE REMOVED.
VERIFY LOCATION AND QUANTITY OF ITEMS TO BE REMOVED. NO
ALLOWANCE WILL BE MADE BECAUSE OF CONTRATOR'S
UNFAMILIARITY WITH THE DETAILS.
I. DAMAGED AREAS CAUSED BY REMOVAL OF ANY OF THE ABOVE
ITEMS AND WHICH ARE NOT CONCEALED BY NEW CONSTRUCTION
SHALL BE REPAIRED TO MATCH ADJACENT SURFACES. OPENINGS
CREATED BY THE REMOVAL OF THESE ITEMS THROUGH FIRE RATED
WALLS SHALL BE FIRE STOPPED.
PROVIDE MINIMUM SCHEDULE 40PVC FOR UNDERGROUND
AWM
E3.02ELECTRICAL ONE-LINE DIAGRAM
MLW
SCALE: NOT-TO-SCALE
ELECTRICAL ONE-LINE DIAGRAM
NOTE:
THIS FACILITY MUST REMAIN IN OPERATION DURING NORMAL BUSINESS HOURS.
ALL WORK REQUIRING POWER OUTAGES SHALL BE ACCOMPLISHED BETWEEN
6PM AND 5AM DURING WEEKDAYS, ON WEEKENDS, SATURDAY, SUNDAY AND
HOLIDAYS. PREPARATORY WORK NOT REQUIRING A POWER OUTAGE SUCH AS
CONDUIT INSTALLATION, NEW PANELBOARDS, PULLING OF CONDUCTORS, ETC.
MAY BE PERFORMED DURING NORMAL BUSINESS HOURS PROVIDED THE
CONTRACTOR DOES NOT DISRUPT NORMAL BUSINESS OPERATIONS.
E3.02
SCALE: NOT-TO-SCALE
SERVICE ENTRANCE EQUIPMENT
E3.02
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s W e l l i n g t o n
A
E M
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
W E
L L
I N
G T
Q U
I P
M E
E
D
L
T G
F
M
W
E L
L I N
G T
O N
T
X
C O
L L
I N
G S
W O
R T
H
C
O U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-06-2024
SCALE: NOT-TO-SCALE
EXISTING PANEL 'BP'
E3.02
AutoCAD SHX Text
WIRE SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
3#4, 1 #10GND, IN 1-1/2"C
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
AutoCAD SHX Text 02-06-24
Amy Stone
SCALE: NOT-TO-SCALE
CONDUIT HANGER DETAIL
E5.01
SCALE: NOT-TO-SCALE
BOX MOUNTING DETAIL
E5.01
SCALE: NOT-TO-SCALE
PANELBOARD SURFACE MTG. DETAIL
E5.01
SCALE: NOT-TO-SCALE
CONDUIT SUPPORT DETAIL
E5.01
SCALE: NOT-TO-SCALE
MULTIPLE CONDUIT SUPPORT DETAIL
E5.04
ELECTRICAL DEVICE IDENTIFICATION
SCALE: NONE
KEYED NOTES:
PROVIDE LABELS FOR LIGHT SWITCH AND RECEPTACLE COVER PLATES
INDICATING THE PANELVOARD AND THE SUPPLY BRANCH CIRCUIT NUMBER.
ALL LABELS SHALL BE TYPED. TEXT SHALL BE THERMAL SET, 12 OR 14
POINT PLAIN OR BLOCK STYLE FONT. ALL ENGRAVED INFORMATION SHALL
HAVE A BLACK FINISH.
COVER
PLATE FOR
RECEPTACLE
OR LIGHT
SWITCH
1NHA-3
1NLA-6
NH01-23
TEST
RESET
ADDITIONAL DEVICES TO BE LABELD:
(RE: KEYED NOTE 1)
PROVIDE LABELS FOR THE FOLLOWING ADDITIONAL DEVICES:
TOGGLE TYPE LOAD DISCONNECT SWITCHES FOR
DIRECT CONNECTED LOADS.
OUTLET BOXES FOR DIRECT CONNECTED LOADS
OUTLET BOXES FOR DIRECT CONNECT LOADS WHICH
DO NOT REQUIRE LOCAL DISCONNECTS.
M
I N
D3"
YELLOW WARNING TAPE WITHIN
12" OF TOP OF TRENCH
GRANULAR PIPE EMBEDMENT ("SAND")
AS DEFINED BY ASTM C-33.
PIPING AS SPECIFIED DIAMETER
PER PLAN (NOTE: PIPING BURIED IN
THE SAME TRENCH SHALL BE 4"
APART MINIMUM).
EXCAVATED MATERIAL COMPACTED
TO AT LEAST EXISTING DENSITY, OR
96% PROCTOR, WHICHEVER IS GREATER.
3"
SLOPE TRENCH WALLS OR SHORING AS
REQUIRED PER SPECIFICATIONS. SHORING
SHALL BE USED WHERE NECESSARY TO
STAY WITHIN CLEARING LIMITS.
MOUND
EXISTING GRADE
SCALE: NOT-TO-SCALE
BOX MOUNTING DETAIL
E5.01
SCALE: NOT-TO-SCALE
CONDUIT SUPPORT DETAIL
E5.01
SCALE: NOT-TO-SCALE
SURFACE FIXTURE MOUNTING DETAIL
E5.01
SCALE: NOT-TO-SCALE
WALL MOUNTED CONDUIT DETAIL
E5.01
SCALE: NOT-TO-SCALE
TYPICAL DEVICE LABELING DETAIL
E5.01
SCALE: NOT-TO-SCALE
ELECTRICAL UNPAVED AREAS - TYPICAL
E5.01
AM
E5.01ELECTRICAL DETAILS
MLW
Texas of Transportation Department
R
COPYRIGHT 2024
c
C A
D F
I L E
U
P r o j e c t s C h i l d r e s s Q u a n a h
M
N T
D
S G
N
C
A D
E
L E
C E d w g
P l o t t e d
T u e
F e b
P
M
B y
M
W A
S H
I N
CHECKED BY:
P R
O J E
DRAWN BY:
ISSUED:
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
REVISIONS:
Q U
A N
U
I P
M E
E
D
L
I G
H T
I N
G
L O
P
R
A
D
F
M
Q
U A
N A
H
T
X
H A
R D
E M
U
N T
Y
C H
I L
D R
E S
S
D
I S
T R
I C
T
02-08-2024
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text
%%UGENERAL NOTES (DETAIL NO. 2 ONLY)
AutoCAD SHX Text
METAL MOUNTING
AutoCAD SHX Text
PRE-FORMED SHEET
AutoCAD SHX Text
PROVIDE SUPPORT BRACKET SIMILAR TO AND EQUAL IN STRENGHT TO THE
AutoCAD SHX Text
NOT INCLUDED IN OTHER DETAILS. IF DEPTH OF BOX EXCEEDS 2-1/2",
AutoCAD SHX Text
THIS DETAIL TO BE USED FOR ALL OUTLET AND DEVICE BOX INSTALLATIONS
AutoCAD SHX Text
ONE SPECIFIED.
AutoCAD SHX Text
CONDUITS SHALL BE SUPPORTED PER NEC 358.30(A).
AutoCAD SHX Text
SCREWS
AutoCAD SHX Text
SELF TAPPING
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
OUTLET BOX(ES)
AutoCAD SHX Text
SIZE AS
AutoCAD SHX Text
BRACKET
AutoCAD SHX Text
STUD
AutoCAD SHX Text
METAL
AutoCAD SHX Text
%%UGENERAL NOTES (DETAIL NO. 1 ONLY)
AutoCAD SHX Text
1-1/2" SQ. 12 GA. MIN.
AutoCAD SHX Text
PROVIDE NUT, LOCKNUT AND CUT ROD 1" FROM
AutoCAD SHX Text
LOCKNUT, PROVIDE CAPNUT ON END OF ROD.
AutoCAD SHX Text
CONTRACTOR MAY USE A CONDUIT SUSPENSION SYSTEM
AutoCAD SHX Text
EQUIVALENT TO THAT WHICH IS DETAILED, HAVING THE
AutoCAD SHX Text
FEATURES SHOWN AND APPROVED IN ADVANCED BY THE
AutoCAD SHX Text
PROVIDED A SAMPLE SUPPORT SYSTEM TO KEEP ON JOB
AutoCAD SHX Text
SITE FOR CONSTRUCTION GUIDE PURPOSES.
AutoCAD SHX Text
CONDUIT SUSPENSION SYSTEM SHALL BE INDEPENDENT
AutoCAD SHX Text
OF ANY OTHER SUSPENSION SYSTEM.
AutoCAD SHX Text 4.
AutoCAD SHX Text 3.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
RESIDENT ENGINEER.
AutoCAD SHX Text
36" MAX
AutoCAD SHX Text
SINGLE BOLT CHANNEL
AutoCAD SHX Text
CONDUIT STRAPS
AutoCAD SHX Text
SEE DETAIL BELOW
AutoCAD SHX Text
NOTE 4
AutoCAD SHX Text
1/2" THREADED GALV.
AutoCAD SHX Text
GALV. STEEL CHANNEL
AutoCAD SHX Text
STEEL RODS
AutoCAD SHX Text
36" MAX
AutoCAD SHX Text
WITH SINGLE BOLT
AutoCAD SHX Text
PIPE STRAPS
AutoCAD SHX Text
SINGLE CONDUIT
AutoCAD SHX Text 1-1/2" x 3/4" - 14 GA.
AutoCAD SHX Text
GALV. STEEL CHANNEL
AutoCAD SHX Text
SURFACE MOUNTED
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
36" MAX
AutoCAD SHX Text
PIPE STRAP, EACH CONDUIT
AutoCAD SHX Text
8'-0" O.C. MAXIMUM
AutoCAD SHX Text
12 GA. 1-1/2" SQ (MIN) STEEL CHANNEL
AutoCAD SHX Text
OF STEEL CHANNEL
AutoCAD SHX Text
SIZE ON BOTTOM
AutoCAD SHX Text
0'-1" MAXIMUM
AutoCAD SHX Text
1/2" GALV.
AutoCAD SHX Text
ROD MIN.
AutoCAD SHX Text
LOCK NUT
AutoCAD SHX Text
AT EACH SUPPORT
AutoCAD SHX Text
SINGLE BOLT CHANNEL
AutoCAD SHX Text
INSERTS
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
STEEL CHANNEL
AutoCAD SHX Text
ELECTRO GALVENIZED
AutoCAD SHX Text
1 1/2"X3/4" 12 GAGE MIN
AutoCAD SHX Text
SECURE TO FLOOR
AutoCAD SHX Text
EIGHT 1/4" STEEL
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
ANGLE
AutoCAD SHX Text
CONNECTORS
AutoCAD SHX Text
SLAB OR JOISTS
AutoCAD SHX Text
SECURE TO CEILING
AutoCAD SHX Text
%%UGENERAL NOTES (DETAIL NO. 5 ONLY)
AutoCAD SHX Text 1.
AutoCAD SHX Text
SECURE TO WALL WITH PLATED BOLTS USING METHODS
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
WALL
AutoCAD SHX Text
WITH SPRING
AutoCAD SHX Text
CLAMPING NUT
AutoCAD SHX Text
SELF-HOLDING
AutoCAD SHX Text
(CONDUIT SYSTEMS)
AutoCAD SHX Text
DESCRIBED IN SPECIFICATION SECTION 16111.
AutoCAD SHX Text
12 GUAGE 1-1/2" SQ
AutoCAD SHX Text
STEEL BRACKET
AutoCAD SHX Text
(MIN) GALVANIZED
AutoCAD SHX Text
12 GAGE 1-1/2"
AutoCAD SHX Text
SQ (MIN) GALVANIZED
AutoCAD SHX Text
STEEL CHANNEL.
AutoCAD SHX Text
CLAMPS
AutoCAD SHX Text
(NOTE #1)
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text 2.
AutoCAD SHX Text
%%UGENERAL NOTES (DETAIL NO. 7 ONLY)
AutoCAD SHX Text 1.
AutoCAD SHX Text
OR OUTLETS ARE SHOWN ONLY ON ONE SIDE OF WALL OR PARTITION.
AutoCAD SHX Text WALL OR PARTITION. %%uDO NOT USE%%u WHERE SWITCHES, RECEPTACLES
AutoCAD SHX Text
OUTLETS ARE SHOWN IN THE SAME LOCATION ON BOTH SIDES OF A
AutoCAD SHX Text
THIS DETAIL TO BE USED ONLY WHERE SWITCHES, RECEPTACLES OR
AutoCAD SHX Text
BOX MOUNTING
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
SIZE AS REQUIRED
AutoCAD SHX Text
OUTLET BOX
AutoCAD SHX Text
BOTH ENDS
AutoCAD SHX Text
CLIP AT
AutoCAD SHX Text
RETAINER
AutoCAD SHX Text
BAR
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
HANGER ASSEMBLY
AutoCAD SHX Text
OFFSET BAR
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
CLIP
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
BAR
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
CLIP
AutoCAD SHX Text
STUD
AutoCAD SHX Text
METAL
AutoCAD SHX Text
20" MAX.
AutoCAD SHX Text
CONDUITS SHALL BE SUPPORTED PER NEC 358.30(A).
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UKEYED NOTES: (DETAIL NO. 3 ONLY)
AutoCAD SHX Text
#12 GAGUE GALV.
AutoCAD SHX Text
T-BAR CLIP ON STUD
AutoCAD SHX Text
INDEPENDENT FROM CEILING SUPPORT WIRES.
AutoCAD SHX Text
FIXTURE SUPPORT WIRES SHALL BE IN ADDITION TO AND
AutoCAD SHX Text
FOR SURFACE MOUNTING OF LIGHT FIXTURES BELOW SUSPENDED
AutoCAD SHX Text
T-BAR CEILINGS.
AutoCAD SHX Text
LIGHT FIXTURE MOUNTING
AutoCAD SHX Text
T-BAR MAIN RUNNER
AutoCAD SHX Text
TOP OF LIGHT FIXTURE
AutoCAD SHX Text
CLG. TILE
AutoCAD SHX Text
HOUSING
AutoCAD SHX Text
CLIP
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
SUPPORT WIRE.
AutoCAD SHX Text
(MODIFIED)
AutoCAD SHX Text 1.
AutoCAD SHX Text
%%UGENERAL NOTES (DETAIL NO. 4 ONLY)
AutoCAD SHX Text
(CONDUIT SYSTEMS)
AutoCAD SHX Text
DESCRIBED IN SPECIFICATION SECTION 16111.
AutoCAD SHX Text
SECURE TO WALL WITH PLATED BOLTS USING METHODS
AutoCAD SHX Text
STEEL CHANNEL.
AutoCAD SHX Text
SQ (MIN) GALVANIZED
AutoCAD SHX Text
12 GAGE 1-1/2"
AutoCAD SHX Text
CONDUIT CLAMPS
AutoCAD SHX Text
NOTE 1
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text
MICHAEL WASHINGTON
AutoCAD SHX Text 111774
DocuSign Envelope ID: 43EE17BB-DC0C-4B72-A132-663EC8777B74
3/20/2019
Amy Stone
NO WORK COMPLETED AT THIS LOCATION
DocuSign Envelope ID: 237C13FA-71C2-4931-8666-8C659502F6FF
Amy Stone
SLAB ON GRADE INSTALLED AT WELLINGTON. NO PEMB FRAMING MEMBERS ERECTED.
Amy Stone
Amy Stone
Amy Stone
| 25-1859-24-01 COVER_SHEET |
| Sheets and Views |
| Layout1 |
| E1.01 |
| Sheets and Views |
| E1.01 |
| E1.02 |
| Sheets and Views |
| E1.01 |
| E2.01 |
| Sheets and Views |
| E2.01 |
| E2.02 |
| Sheets and Views |
| E2.01 |
| E3.01 |
| Sheets and Views |
| E3.01 |
| E3.02 |
| Sheets and Views |
| E3.01 |
| E5.01 |
| Sheets and Views |
| E5.01 |
File details come from the government source that posted it. Updated .