This document is the Attachment B specifications for a state and local invitation for bid (IFB-27-004) issued by the State of Texas for a custom shipping container office to be delivered to the Abilene Tanker Base. The procurement requires one 40-foot high cube IIRC steel shipping container to be converted into a fully finished, watertight, insulated, and climate-controlled aviation operations office. The project is a turnkey conversion that includes structural modifications, insulation, interior finishes, electrical systems, HVAC, lighting, doors, windows, network and data infrastructure, fire-safety equipment, and all other components necessary for a professional office environment. The container must be structurally sound, weathertight, and free from corrosion or damage, with an exterior painted beige and suitable for permanent outdoor installation in West Texas. A minimum five-year warranty on the completed conversion and workmanship is required, along with manufacturer warranties for all installed equipment and components.
The specifications detail comprehensive technical requirements for interior and exterior systems, including closed-cell spray polyurethane foam insulation with finished plywood walls and ceilings painted in Sherwin-Williams Agreeable Gray, commercial-grade epoxy flooring, a properly sized mini-split heat-pump HVAC system with single or dual-zone capability, a complete 100-amp electrical service panel with dedicated circuits, LED lighting throughout with dimming capability, and network infrastructure supporting CAT6 cabling with both interior and exterior wireless access point provisions. The office must accommodate a two-person workstation area, a 10-foot fold-down work table, provisions for two 65-inch televisions, a wall-mounted network/server rack, five exterior LED floodlights, two exterior receptacles, interior lighting with dimming controls, a commercial personnel door with keypad lock, two 4-foot by 4-foot insulated windows, fire extinguisher and illuminated exit sign, and a weatherproof exterior communications entry point for future expansion. All systems must be inspected and tested for full operational capability prior to final acceptance by the end user, with all deficiencies corrected by the vendor before delivery and acceptance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT B
40-FOOT HIGH CUBE CONTAINER OFFICE
SPECIFICATIONS
ABILENE TANKER BASE
MINIMUM TECHNICAL SPECIFICATIONS
1. SCOPE OF WORK
The successful vendor shall furnish and deliver one (1) 40-foot High Cube IIRC steel shipping container converted into a fully finished, watertight, insulated, climate-controlled aviation operations office for use at the Abilene Tanker Base.
The completed unit shall be furnished as a turnkey office and shall include all structural modifications, insulation, interior finishes, electrical systems, HVAC, lighting, doors, windows, network/data infrastructure, fire-safety equipment, and other components identified within this specification.
All materials and workmanship shall be commercial grade and suitable for extended daily use in an aviation operations environment and outdoor installation in West Texas.
See sketch in Attachment C for reference of approximate location of options described. Exact placement of options will be finalized with selected bidder and approved by end user prior to beginning modifications.
2. CONTAINER REQUIREMENTS
The base container shall meet the following minimum requirements:
• Quantity: One (1)
• Size: 40-foot High Cube IIRC
• Construction: Corten/weathering steel
• Container shall be structurally sound, weather-tight, and free from significant corrosion, structural damage, or water intrusion.
• Container shall be suitable for permanent or semi-permanent outdoor installation.
• All modifications to the container shall maintain the structural integrity of the unit.
• Openings cut into the container for doors, windows, HVAC, electrical, or communications equipment shall be properly framed and reinforced as required.
• Exterior color: Painted beige, color to be approved by end user
• Exterior finish shall be suitable for long-term outdoor exposure.
• Minimum five (5) year warranty on the completed office conversion. Vendor shall clearly identify all warranty terms, exclusions, and manufacturer-specific equipment warranties in the bid response.
3. INTERIOR FINISH AND INSULATION
The entire occupied interior shall be professionally finished.
Insulation
Walls and ceiling shall be insulated using closed-cell spray polyurethane foam insulation overlaid with finished smooth, painted plywood specified below.
Insulation shall:
• Provide a continuous thermal barrier to the greatest extent practical.
• Minimize air infiltration and condensation.
• Be suitable for the West Texas climate.
• Be installed behind the finished interior wall and ceiling surfaces.
Vendor shall identify the proposed insulation thickness and resulting R-value in the bid response.
Interior Walls and Ceiling
Walls and ceiling shall be covered with durable, commercial-grade finished plywood material suitable for an office environment, painted Sherwin-Williams Agreeable Gray (SW 7029), or similar color approved by end user.
Interior surfaces shall provide a clean, professional appearance and be capable of supporting normal commercial office use.
Structural blocking shall be installed behind finished wall surfaces wherever required for televisions, fold-down tables, network racks, cabinets, or other wall-mounted equipment.
Flooring
The existing container floor may be retained with any splintering removed and gouges filled to attain an even surface. The entire floor surface shall be professionally coated with commercial/industrial-grade epoxy to provide a durable, long-lasting, and easy-to-clean finished surface suitable for daily office use and heavy foot traffic. Paint is not acceptable as a substitute for the epoxy coating.
4. HVAC SYSTEM
Provide and install a complete mini-split heat-pump HVAC system capable of heating and cooling the entire 40-foot High Cube office. If a single properly sized unit cannot provide adequate and reasonably balanced heating and cooling throughout the space, a two-zone mini-split system with an indoor unit located at each end of the container shall be provided. The HVAC system shall be appropriately sized based upon:
• Interior cubic footage
• Insulation values
• Two 4' × 4' windows
• Exterior personnel door
• West Texas summer temperatures
• Solar loading
• Personnel occupancy
• Computers and office equipment
• Two 65-inch televisions
• Network/server equipment
• Other anticipated internal heat loads
The vendor shall calculate the required HVAC capacity and identify the proposed system manufacturer, model, and BTU capacity in the bid. The HVAC system shall be properly sized for the completed container based on the actual calculated heating and cooling load. The contractor shall account for the container size, insulation, windows, equipment heat load, occupancy, solar exposure, local climate conditions as may be experienced in West Texas, and the efficiency/SEER rating of the proposed equipment.
Proper sizing is critical. An undersized system may not adequately cool the space or control humidity during peak summer conditions in South or West Texas. An oversized system may short-cycle, resulting in poor humidity control, reduced efficiency, and unnecessary wear on the equipment.
The system shall provide both heating and cooling.
A dedicated electrical circuit shall be provided for the HVAC system.
No substitution of the mini-split heat-pump design is permitted.
5. ELECTRICAL SYSTEM
Provide a complete commercial-grade electrical system.
Main Electrical Service
Provide one (1):
• 100-amp outdoor-rated electrical breaker panel.
The panel shall provide sufficient capacity for the installed equipment and reasonable future expansion.
Electrical installation shall comply with applicable National Electrical Code (NEC) requirements and applicable local requirements.
Circuits shall be clearly identified at the electrical panel.
Dedicated Circuits
At minimum, dedicated or appropriately separated circuits shall be provided for:
• HVAC system
• Network/server rack
• Television/display equipment
• Interior general-purpose receptacles
• Exterior receptacles
• Interior lighting
• Exterior/security lighting
6. INTERIOR ELECTRICAL RECEPTACLES
Two-Person Workstation
At the designated two-person workstation, provide:
• One (1) four-gang electrical receptacle arrangement.
• Minimum one (1) CAT6 network connection.
General Office Receptacles
Provide four (4) single-gang duplex 120V receptacle locations along each long interior wall.
Receptacles shall be distributed to provide convenient access throughout the office.
Television Locations
Provide appropriately positioned electrical receptacles behind each television mounting location so that electrical cords can be concealed after installation, in addition to the general receptacles.
Server Rack
Provide dedicated 120V electrical power at the network/server rack location.
7. INTERIOR LIGHTING
Provide commercial-grade 4 feet x 2 feet rectangular LED lighting throughout the entire office.
Lighting shall provide adequate illumination for office, briefing, computer, and aviation operations activities.
Lighting within the primary office/workspace shall be dimmable to allow lighting levels to be reduced for television/display viewing and operational briefings.
Provide:
• LED interior fixtures.
• Wall-mounted dimmer control for the office/workspace lighting.
• Appropriate switches at convenient entrance locations.
8. EXTERIOR ELECTRICAL RECEPTACLES
Provide two (2) exterior 120V receptacle locations.
• One (1) receptacle shall be located on each long exterior side of the container.
• Receptacles shall be outdoor/weather-resistant type.
• Each location shall have a weatherproof in-use cover.
• GFCI protection shall be provided as required by applicable electrical code.
9. EXTERIOR LIGHTING
Provide one (1) exterior LED floodlight near each corner on the long walls and one above the personnel door, for total of five (5) lights, with a switch inside next to the personnel door.
Each floodlight light shall:
• Be outdoor/weather rated.
• Provide adequate illumination of the entrance and immediate surrounding area.
• Be permanently wired into the container electrical system.
• Minimum 120-degree beam angle.
10. PERSONNEL DOOR
Provide one (1) exterior personnel/walk-in door, located on long side approximately 1/3 from front end of container as indicated in drawing.
Minimum requirements:
• 36 inches wide × 79 inches high
• Steel exterior door
• Commercial-grade hinges, hardware, and construction
• Weather stripping/sealing
• Automatic closer
• Commercial keypad combination lock
• Suitable for outdoor commercial use
Door installation shall be structurally reinforced as appropriate and weather tight.
11. WINDOWS
Provide two (2) windows on same long side as personnel door, evenly towards either end as indicated in drawing.
Minimum size:
• 4 feet × 4 feet each
Windows may be fixed or operable.
Windows shall be:
• Commercial grade
• Weather-tight
• Insulated
• Tinted
• UV rated
• Mirror/reflective exterior finish
Window installation shall include proper structural reinforcement, flashing, sealing, and weatherproofing.
Vendor shall identify whether the proposed fixture includes photocell and/or motion-sensing capability.
12. TWO-PERSON WORKSTATION AREA
Provide a designated two-person office/workstation area at the front of the container.
The area shall be configured to accommodate two personnel simultaneously with access to electrical power and network connectivity.
At minimum, provide:
• One (1) four-gang electrical receptacle arrangement.
• One (1) CAT6 network port.
• Appropriate lighting.
• Access to general-purpose electrical receptacles.
13. FOLD-DOWN WORK/BRIEFING TABLE
Provide one (1) approximately 10-foot-long wall-mounted fold-down table/work surface.
The table shall:
• Be ¾-inch cabinet grade plywood covered with laminate or similar approved durable, smooth surface, with no sharp edges, to be used as a functional workspace.
• Be securely attached to the container structure.
• Include appropriate structural blocking behind the finished wall.
• Fold against the wall when not required with retaining device capable of holding the table in stowed (up) position if container is relocated.
• Include appropriate folding support legs that rest on the floor when placed in the operating (down) position, capable of supporting multiple laptops, an office printer, and other office machines. The legs must fold and store securely with the table when it is in stowed (up) position against the wall.
• Be suitable for use as a work, meeting, or aviation briefing surface.
• Shall not be rough plywood or be suspended by chains, ropes, or similar.
14. TELEVISION / DISPLAY WALL
Along the wall containing the 10-foot fold-down table, provide structural provisions for installation of two (2) 65-inch televisions.
The vendor shall provide:
• Structural blocking/reinforcement for both television locations.
• Electrical receptacle behind each television.
• Data/network provisions at or near the television locations.
• Concealed or appropriately routed cabling provisions.
Wall reinforcement shall be sufficient to support each 65-inch television and its associated commercial mounting bracket without relying solely upon the finished interior wall material.
15. NETWORK AND DATA SYSTEM
Provide CAT6 or better structured network cabling throughout the office.
All permanent network cabling shall terminate at the wall-mounted network/server rack.
Provide a minimum of four (4) hardwired network/data ports within the office.
At least:
• One (1) network port shall be located at the two-person workstation.
• Remaining ports shall be positioned at practical locations for office equipment, televisions/displays, or future operational requirements.
All network cabling shall be professionally terminated, labeled, and tested.
16. INTERIOR WIRELESS ACCESS POINT
Provide network cabling for one (1) ceiling-mounted indoor wireless access point.
The cable shall terminate at:
• The designated ceiling access-point location; and
• The network/server rack.
Installation shall support Power over Ethernet (PoE) equipment.
End user will provide and install the wireless access point itself following delivery; infrastructure and cabling shall be provided to support its installation.
17. EXTERIOR WIRELESS ACCESS POINT
Provide one (1) weatherproof exterior network box for installation of an outdoor wireless access point.
The exterior box shall be located near the non-opening (front) end or at a location approved by the end user.
Provide CAT6 or better cabling from this exterior location to the network/server rack.
The installation shall support a PoE-powered outdoor wireless access point.
All penetrations shall be properly sealed and weatherproof.
18. NETWORK/SERVER RACK
Provide and install one (1) small wall-mounted network/server rack.
The rack shall be installed mounted to the wall in the front left corner as shown in Attachment C and shall include:
• Dedicated 120V electrical power.
• Termination point for installed CAT6 cabling.
• Sufficient structural blocking for secure wall mounting.
• Cable-management provisions.
• Space for future network equipment.
• Provision for installation of a UPS.
Rack size shall provide reasonable capacity for future communications and network expansion.
Actual rack installed must be approved by end user.
19. EXTERIOR COMMUNICATIONS ENTRY POINT
Provide a dedicated, weatherproof communications/data entry pass-thru point adjacent to or conveniently located near the network/server rack.
The entry system shall provide the ability to bring additional communications cables into the office without requiring additional holes to be drilled through the container.
The system shall provide spare capacity for future equipment including, but not limited to:
• Network connections
• Starlink/satellite connectivity
• Cellular equipment
• Radio communications equipment
• Security cameras
• Outdoor wireless equipment
• Other communications technology
Exterior penetrations shall utilize commercial-grade weatherproof cable glands, bulkhead fittings, conduit, or equivalent systems.
All unused openings shall be properly sealed.
20. FIRE AND LIFE SAFETY
Provide the following minimum fire/life-safety equipment:
• One (1) 5-pound ABC-rated portable fire extinguisher with mounting hardware.
• Fire extinguisher shall be mounted in an accessible and clearly visible location.
• One (1) illuminated EXIT sign with emergency floodlight installed above personnel door.
• Required emergency or life-safety electrical provisions shall comply with applicable codes.
21. EXTERIOR FINISH
The complete exterior shall be painted beige in a color approved by the end user.
Paint/coating system shall be:
• Suitable for Corten/weathering steel.
• Suitable for continuous outdoor exposure.
• Resistant to UV degradation.
• Appropriate for West Texas environmental conditions.
All areas modified by cutting, welding, drilling, or fabrication shall receive appropriate corrosion protection prior to final coating.
22. WORKMANSHIP
All work shall be performed in a professional and workmanlike manner.
Electrical, HVAC, structural, and other specialty work shall be performed in accordance with applicable codes and manufacturer requirements.
There shall be no exposed sharp edges, unfinished penetrations, unsealed openings, loose wiring, or other unfinished construction.
23. WARRANTY
The vendor shall provide a minimum five (5) year warranty on the completed container office conversion and workmanship, exclusive of user damage.
The vendor shall provide applicable manufacturer warranties for components including, but not limited to:
• HVAC equipment
• Electrical components
• Windows
• Door and keypad lock
• Lighting
• Other installed equipment
The bid response shall clearly identify warranty periods and coverage.
24. FINAL INSPECTION AND ACCEPTANCE
Prior to acceptance, the completed office shall be inspected and all installed systems demonstrated as operational.
At minimum, acceptance shall include verification of:
• HVAC heating and cooling operation.
• Interior LED lighting and dimming operation.
• Exterior lighting.
• All interior and exterior receptacles.
• 100-amp electrical panel and circuit identification.
• Personnel door and keypad lock.
• Windows and weather sealing.
• Network cabling continuity and termination.
• Interior and exterior wireless access-point cabling.
• Server/network rack power.
• Exterior communications entry point.
• Television electrical/data provisions.
• Fire extinguisher and EXIT sign.
• Interior and exterior finishes.
• Water/weather-tight condition of all modifications and penetrations.
Any deficiencies identified during final inspection shall be corrected by the vendor prior to final acceptance.
| 40-FOOT HIGH CUBE CONTAINER OFFICE SPECIFICATIONS |
| ABILENE TANKER BASE |
| MINIMUM TECHNICAL SPECIFICATIONS |
| 1. SCOPE OF WORK |
| 2. CONTAINER REQUIREMENTS |
| 3. INTERIOR FINISH AND INSULATION |
| Insulation |
| Interior Walls and Ceiling |
| Flooring |
| 5. ELECTRICAL SYSTEM |
| Main Electrical Service |
| Dedicated Circuits |
| 6. INTERIOR ELECTRICAL RECEPTACLES |
| Two-Person Workstation |
| General Office Receptacles |
| Television Locations |
| Server Rack |
| 7. INTERIOR LIGHTING |
| 8. EXTERIOR ELECTRICAL RECEPTACLES |
| 9. EXTERIOR LIGHTING |
| 10. PERSONNEL DOOR |
| 11. WINDOWS |
| 12. TWO-PERSON WORKSTATION AREA |
| 13. FOLD-DOWN WORK/BRIEFING TABLE |
| 14. TELEVISION / DISPLAY WALL |
| 15. NETWORK AND DATA SYSTEM |
| 16. INTERIOR WIRELESS ACCESS POINT |
| 17. EXTERIOR WIRELESS ACCESS POINT |
| 18. NETWORK/SERVER RACK |
| 19. EXTERIOR COMMUNICATIONS ENTRY POINT |
| 20. FIRE AND LIFE SAFETY |
| 21. EXTERIOR FINISH |
| 22. WORKMANSHIP |
| 23. WARRANTY |
| 24. FINAL INSPECTION AND ACCEPTANCE |