ESBD_485591_1769709847925_Solicitation Package 601290000033356.pdf

PDF 2 MB Posted

Attached to
Traffic Signal Controllers for Seguin Regional Distribution Center
Solicitation number
601290000033356
Issued by
Grimes County, Texas

About this file

This is an Invitation for Bid (IFB) solicitation issued by the Texas Department of Transportation (TxDOT) for the procurement of traffic signal controllers. The solicitation seeks ten (10) units of fully actuated, solid-state traffic signal controller assemblies conforming to Specification DMS 11170, with NEMA TS/2 Type 1 interface, Size 6 base mount configuration, and 16-position load bay for timer operation without loop detectors. The controllers must be delivered to the Seguin Regional Supply Center located at 2024 HWY 46 North, Seguin, TX 78155-2206. This is classified as an emergency purchase under Texas Government Code 2155.137 and 34 TAC 20.82, and is being advertised as proprietary under Government Code 2155.067. The response due date is February 2, 2026, at 3:00 p.m. central time, with a tentative contract award date of February 13, 2026. The solicitation was posted on January 29, 2026. No bidder's conference or site visits are specified in the documentation. The contract term is not explicitly stated but is subject to standard TxDOT terms and conditions, including termination and renewal provisions.

Pricing for this solicitation is on a firm, fixed-price basis, F.O.B. destination with freight prepaid and included in the quoted unit price. Respondents must be authorized dealers or distributors of the specified products and must provide documentation proving authorization within two days of TxDOT's request. Responses must include complete vendor data, Texas Family Code certifications, and all required documentation; failure to provide these materials will result in non-responsive status. The procurement requires that all materials conform exactly to the detailed specifications outlined in DMS 11170, including NEMA TS 2 standards, comprehensive controller functionality with diamond intersection operation capability, preemption logic, closed-loop system compatibility, and NTCIP compliance. No set-asides, small business preferences, or incumbent contractor information are identified in the solicitation. Funding source and total contract value are not specified in the available documentation.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INSTRUCTIONS TO RESPONDENTS

USE OF NATIONAL INSTITUTE OF GOVERNMENTAL PURCHASING CODE

The Texas Department of Transportation (TxDOT) uses the National Institute of Governmental Purchasing, Inc., (NIGP) code to standardize purchases by conforming to the class, item, and group structure of the code. The NIGP code is used to select vendors for our master vendor file from the Texas Comptroller of Public Accounts (CPA) Centralized Master Bidders List (CMBL).

New suppliers and other vendors wishing to furnish materials, equipment, supplies and services to TxDOT should apply to be on the CMBL to receive bidding opportunities.

Existing TxDOT vendors need only be concerned that the information listed on the CMBL file is correct, and that the applicable NIGP class and item are selected for those you can provide.

CMBL information is available online at: https://comptroller.texas.gov/purchasing/vendor/cmbl/ or by phoning 1-512-463-3459.

Early Payment Program - TxDOT is offering an important program to all respondents that provide prioritized invoice processing and payments (prior to the 30th day after receipt of a correct invoice). The program provides enrolled vendors enhanced benefits from improved invoice processing to priority handling to cash advancement and technology efficiencies.

Respondents offering a cash discount in exchange for TxDOT’s priority invoice processing and early payment agreement should complete and return the attached form entitled “Priority Invoice and Early Payment Program” with the response.

Additional information may be found at the following website: http://www.txdot.gov/business/vendors/epp.html

Revised 20

601290000033356

02/02/2026 3:00 PM

Taylor.Blevins@txdot.gov

Taylor.Blevins@txdot.gov

Taylor.Blevins@txdot.gov Taylor.Blevins@txdot.gov

SHIP TO THE FOLLOWING LOCATION

UNLESS OTHERWISE NOTED

SEE SPECIFIC INSTRUCTIONS FOR

EACH LINE ITEM.

United States

SEE SPECIFIC INSTRUCTIONS FOR

EACH LINE ITEM

1 10.00 EA55081284816

CONTROLLERS, TRAFFIC SIGNAL, NAZTEC,

NEMA TS/2, SIZE 6, BASE MOUNT,16 POS.

FOR TIMER W/O LOOP DETECTORS

SHIP THIS ITEM TO THE FOLLOWING LOCATION

SEGUIN REGIONAL SUPPLY CENTER

2024 HWY 46 NORTH

SEGUIN TX 78155-2206

United States

Must meet Specification DMS 11170

Example: Cubic ITS/Trafficware Part No.

70006-3044E

Respondent must be an official authorized dealer or authorized distributor of the products being solicited.

Respondent will be required to submit documentation and proof that they are an authorized dealer or distributor within 2 days of the request from TxDOT.

Respondent must indicate below the make and model of the item bid.

Make: ________________________

Model: ________________________

Page 1INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

Item Item Quantity Unit Make/ Unit Extended No. Description Model Price Price

IF RESPONDING, FORM MUST BE SIGNED. IF NOT RESPONDING. DO NOT RETURN THIS FORM.

Failure to sign will disqualify response.

Authorized Signature Date

Printed Name

By signing solicitation, respondent certifies that if the Texas address is shown as the address of the respondent, respondent qualifies as a Texas Bidder as defined in 34 T AC Rule 20.306

The following comments apply to the entire Solicitation

1. Description of Goods: This solicitation is to establish a contract for Traffic Signal Controllers for Seguin Regional Distribution Center.

2. Emergency:

This solicitation is for an emergency purchase made under Texas Government Code, §2155.137 and 34 TAC 20.82.

3. Electronic State Business Daily (ESBD): This solicitation is posted on the ESBD.

It is the responsibility of the respondents to check the ESBD for addenda or additional information related to the solicitation. Vendors active on the CMBL at the time the solicitation was posted will receive notifications regarding addenda or additional information related to the solicitation.

http://www.txsmartbuy.com/esbd

4. Proprietary:

This solicitation is being advertised under Texas Government Code, §2155.067.

TxDOT believes the requested items or service are proprietary to one provider and/or specification. Only responses conforming exactly to the specifications or statement of work will be considered in determining award. The issuing office strongly encourages responses from all qualified vendors who may be able to provide the specified items or service.

5. Order of Precedence: In the event of any conflict, terms contained in the document shall prevail in the order as listed below:

5.1. Solicitation No. 601290000033356

5.2. Specification DMS-11170 dated

October 2025

5.3. TxDOT Terms and Conditions, August

5.3.1. Payment will be made in

accordance with Part 4, Para. 4.04 (b)

Page 2INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

Item Item Quantity Unit Make/ Unit Extended No. Description Model Price Price

6. The Vendor shall promptly notify TxDOT of all matters relating to any Federal tax on imported goods that reasonably may be expected to result in either an increase or decrease in the contract price and shall take appropriate action as TxDOT directs

7. Estimated Quantities Quantities are estimates only to be used for the purpose of comparing responses.

The respondent must enter their unit price on Solicitation. Total price will be evaluated by multiplying the unit price for each line by the estimated quantities listed on Solicitation.

TxDOT will order only the amount needed to satisfy operating requirements; no guarantee of any minimum or maximum purchase is made or implied. Total amount ordered must not exceed the aggregate contract amount unless additional funds are allocated, and the total contract amount is increased in accordance with the terms and conditions.

8. Acceptance Inspection:

All items ordered will be subject to acceptance inspection and performance testing upon receipt. Acceptance inspection and performance testing will not take more than thirty working days, weather permitting.

Vendor will be notified within this time frame of any units not delivered in full compliance with the contract specifications. If any units are canceled for nonacceptance, the needed equipment may be purchased elsewhere and vendor may be charged any additional increase in cost and handling.

9. Delivery:

Delivery must be made between 8 AM and 4 PM Monday through Thursday except on regularly observed state or federal holidays, unless prior approval has been obtained from TxDOT.

10. Contact Information:

The individuals listed below are the only authorized TxDOT contacts.

Contacting any other TxDOT personnel regarding this solicitation, may result in the respondent being disqualified.

Page 3INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

Any changes as a result of questions will be made by TxDOT in the form of an addendum to the solicitation; no oral changes will be considered.

For clarification or questions regarding this solicitation, respondents may contact:

Primary Contact: Taylor Blevins, CTCD Phone: 903-737-9293 Email: Taylor.Blevins@txdot.gov

Secondary Contact: Leigh Wilson, CTCD Phone: 903-510-9276 Email: Leigh.Wilson@txdot.gov

11. Vendor Performance: TxDOT will monitor performance on a regular basis.

11.1. TxDOT may consider the following

performance by the vendor as unsatisfactory performance - An unsatisfactory performance determination includes, but is not limited to:

11.1.1. Failure to deliver any portion

of the work product.

11.1.2. Failure to deliver a useable

work product during the term of the contract

11.1.3. Unsatisfactory performance of

any service requirements in the contract

11.2. Exceptional performance

determination includes, but is not limited to:

11.2.1. Deliverables made early upon

TxDOT member request.

11.2.2. Vendor commended for exceptional

customer service

11.2.3. Exceptional service provided

12. Packaging Requirements:

All cardboard boxes must be labeled, listing the manufacturer's name, part number, description, quantity, and box weight.

All cardboard boxes must be suitable in bursting strength to allow for the weight of the contents and to allow for the stacking of the boxes a maximum of four high on a pallet for shipping and storage.

Packaging other than specified herein is acceptable only with the prior written approval of TxDOT’s designated TxDOT

Page 4INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

representative.

13. Response Submission:

13.1. GENERAL FORMAT: The respondent

must submit one signed and dated response to include the documentation required per response paragraph 13.3 to the email address as indicated on the “Instructions to Respondents” page.

13.2. The respondent shall not encrypt

or password protect response or embed documents within the response; each section must be its own separate document.

13.3. RESPONSE: Failure by the

respondent to submit the documentation listed below will result in the response being considered non-responsive. The response submission must be submitted with each section named with the “Section #” and brief description not to exceed 30 total characters as a separate document in the following format:

13.3.1. Section 1 – Signed Invitation

for Bid

13.3.2. Section 2 – Vendor Data Schedule

13.3.3. Section 3 – Texas Family Code

Schedule

13.3.4. Section 4 – Addenda (if

applicable)

14. Vendor Point of Contact:

Name:

Phone:

Email:

15. Vendor Verification of Federal Employer Identification Number:

Vendor to provide current company name:

Vendor to provide federal EIN:

If invoice will be submitted by, and/or payment made to an EIN or company name different from the vendor on the contract, vendor must complete the following to authorize payment:

EIN of company authorized to invoice for vendor:

Name of Invoicing Company:

Page 5INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

EIN of company authorized to receive payment:

Name of company to be paid:

16. Preferences Check below if preference claimed under rule 34TAC 20.306.

Tie-Bid Preferences:

_Supplies, materials or equipment produced in Texas or offered by a Texas bidder.

_Agricultural products produced or grown in Texas.

_Agricultural products and services offered by Texas bidder.

_USA produced supplies, material or equipment.

_Products produced at facilities located on formerly contaminated property _Products and services from economically depressed or blighted areas.

_Goods produced or offered by a Texas bidder that is owned by a service disabled veteran who is a Texas resident.

Source Preferences:

_Products of persons with mental or physical disabilities _Vendors that meet or exceed air quality standards. For contracts to be performed, in whole or in part, in a designated non-attainment area or an affected county, as those terms are defined by Health and Safety Code

386.001 Texas emission reduction plan

_Manufacturer that has a recycle program for computer equipment _Contractor providing foods of higher nutritional value Specification Preferences:

_Point lines made of recycled materials, remanufactured, or environmentally sensitive materials including recycled steel _Energy efficient products _Rubberized asphalt paving materials _Recycled motor oil and lubricants

If the name of your company is not printed on the heading of this solicitation, you must write the full name of company, full name of signer, Page 6INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

mailing address, and respondent's employer identification number (EIN) on the face of the solicitation. To minimize identity theft, every company must have an employer Identification number (EIN), also known as a federal tax identification number, prior to award of a contract.

For information on obtaining your EIN, call 800-829-4933 or visit the following website:

https://www.irs.gov/businesses/small-bus inesses-self-employed/employer-idnumbers

(NOTE: this link will not work if capitalization is used. Type in navigation bar using lower case letters)

17. Calendar of Events Estimated Solicitation Posting Date:

01/29/2026 Response Due Date 02/02/2026, 3:00 p.m.

central time Tentative Date for Contract Award:

02/13/2026

Page 7INVITATION FOR BID 01/29/2026

SOLICITATION NO: 601290000033356

OPENING DATE 03:00 PM Feb 02, 2026 To:

Blank Vendor X Austin TX 78701

VENDOR ID: 9999999999 - 999

Return Sealed Response To:

See Body of Solicitation for Specific Return Instructions

BUYER: Blevins, Taylor

PHONE: 903/427-3561

Shows opening date and number in lower left hand corner of sealed response envelope and show return address of vendor.

Vendor agrees to comply with the solicitation below and at terms and conditions.

F.O.B. destination means vendor retain title to goods until delivered and the price quoted includes all freight charges.

Delivery in _______________________________Days Cash Discount_____________%_________________ Days

QUOTE F.O.B. DESTINATION

DEPARTMENTAL MATERIALS SPECIFICATION

FULLY ACTUATED, SOLID-STATE TRAFFIC SIGNAL

CONTROLLER ASSEMBLY

TRAFFIC SAFETY DIVISION 1 – 40

EFFECTIVE DATE: OCTOBER 2025

REVIEW DATE: OCTOBER 2025

DMS - 11170

FULLY ACTUATED, SOLID-STATE TRAFFIC SIGNAL CONTROLLER

ASSEMBLY

EFFECTIVE DATE: OCTOBER 2025

11170.1. Description. This Specification governs for a shelf-mounted, 16-phase, full-actuated, solid-state controller unit with internal time based coordination (TBC), railroad and fire

(emergency vehicle) preemption (PE), diamond-intersection operation, and closed-loop secondary operation in a traffic signal controller assembly and cabinet assembly.

11170.2. Units of Measurements. The values given in parentheses (if provided) are not standard and may not be exact mathematical conversions. Use each system of units separately.

Combining values from the two systems may result in nonconformance with the standard.

▪ Material Producer List. The Traffic Safety Division (TRF), Traffic Management Section

(TM), maintains the Material Producer List (MPL of all materials and products conforming to the requirements of this specification. Materials and products appearing on the MPL, entitled

“Traffic Signals,” require no further sampling and testing before use, unless deemed necessary by the Project Engineer or TRF TM.

The MPLs associated with this DMS include notations that identify products or materials that are pre-certified to comply with Buy America, Gold Star certification. Submit the Department’s

“Buy America Certification” Form 2812 found on TxDOT.gov for Gold Star certification.

Provide additional form or documentation upon Department request. Submit new form if material or product Buy America compliance status changes. Build America, Buy America

(BABA) compliance status change means anytime the product’s Buy America status as represented on the MPL changes. The Department maintains authority for establishing BABA material classifications (iron or steel, manufactured product, construction material or excluded material).

11170.3. Bidders’ and Suppliers’ Requirements. To be accepted on bids, materials must have approved product codes or designations and be from pre-qualified producers.

The supplier's facilities must be of sufficient size and staffing to allow warranty repairs to the cabinet assembly on a timely basis. Timely return of equipment is no more than 18 calendar days from the date of receipt by the supplier to the return receipt of the equipment at the specified location. This requirement may be met by field service. Failure to meet these requirements may result in rejection of future bids.

Ship the controller cabinet enclosed in cardboard on 4 × 4 in. (100 × 100 mm) runners covered with 0.5-in. (12.5-mm) plywood to facilitate handling. Runners consisting of stacked 2 × 2 in.

(50 × 50 mm) boards are not acceptable.

For ventilation purposes while testing, do not bubble wrap or package cabinet components in boxes when shipping.

CONTROLLER ASSEMBLY

TRAFFIC SAFETY DIVISION 2 – 40

EFFECTIVE DATE: OCTOBER 2025

REVIEW DATE: OCTOBER 2025

Use polypropylene strapping material to secure all cabinet components for shipping. Glass filament tape may be used to secure load switches and flash transfer relays. Other means of securing components are acceptable but require written approval by the TRF Signal Operations

Engineer.

11170.4. Pre-Qualification Procedure.

A. Pre-Qualification Request. Submit a request for evaluation to the Texas Department of

Transportation, Traffic Safety Division, Traffic Engineering Section (TRF-TE), 6230 E.

Stassney Lane, Austin, Texas 78744.

B. Pre-Qualification Sample. Submit one signal controller cabinet assembly with the pre-qualification request.

All materials submitted for pre-qualification tests will be at no cost to the Department.

C. Documentation.

1. Cabinet. Provide each cabinet with the following documentation:

• Three complete, accurate, and fully legible diagrams and one schematic for every electronic device (This must include but not be limited to cabinet-wiring, back panel, detector-panel, power-panel, PE-panel, flasher-circuit, load-switch, card-rack-power-supply, bus-interface-unit, and power-supply diagrams.)

• Complete parts list including names of vendors for parts not identified by universal part numbers such as JEDEC, RETMA, or EIA

• Manufacturer's specifications for cooling fans including the CFM rating of fans

2. Controller Unit. Provide each controller unit with one service manual per unit that includes description of controller unit, description of its operation, and basic maintenance and troubleshooting information.

3. Malfunction Management Unit (MMU). Provide each MMU with one service manual per unit that includes description of MMU unit, description of its operation and basic maintenance, and troubleshooting information

Bidders must be prepared to furnish NEMA certification for the complete cabinet assembly from an independent laboratory.

D. Sampling and Testing. Signal controller cabinet assemblies must meet or exceed the requirements of all applicable National Electrical Manufacturers Association (NEMA), Texas Manual on Uniform Traffic Control Devices (TMUTCD), and Institute of

Transportation Engineers (ITE) Standards and this Specification. In addition to testing of pre-shipment samples, complete testing of signal controller assemblies may be required at any time before acceptance.

Burn-in each controller cabinet assembly for a period of 48 hr. at a temperature of 60°C or for a period of 96 hr. at a temperature of 23°C. Include with or attach a certification to each controller cabinet indicating the dates of the burn-in period, number of hours, burn-in temperature, and results.

TRAFFIC SAFETY DIVISION 3 – 40

The Department may test any controller cabinet assembly under load in a shop environment for a period of at least 120 hr. During this time, the Department will inspect the entire controller cabinet assembly for compliance with the Specifications.

The Department may then perform any or all tests described in NEMA Standard

Publication TS 2 1998 on one or more complete controller cabinet assemblies on a random sample basis. Environmental sampling and testing will be in accordance with

Tex-1170-T. Testing will be performed in the normal operating (i.e., non-flashing) range of 95-135 VAC. All traffic signal cabinet assembly components must operate normally at

95 VAC, just as the unit would operate at 120 VAC.

Provide TRF with closed-loop software, hardware, and cables needed to monitor controller operations during testing.

E. Warranty. All equipment must have no less than 95% of the manufacturer's standard warranty remaining on the date that the contractor submits equipment invoices for payment. The Department will not accept any equipment with less than 95% of its warranty remaining.

The cabinet assembly including all contents must be fully warranted for parts and labor for a minimum of 5 years from the date of acceptance.

Software and firmware updates must be included as part of the warranty.

F. Evaluation. TRF-TE will notify prospective bidders and suppliers after completion of material evaluation.

1. Qualification. If approved for use by the Department, the material will be added to the

MPL. If material is listed on the MPL, no additional submittals are required for that product.

Date of acceptance will be date that TRF approves the controller cabinet assembly.

The traffic signal controllers and cabinets must be identical to the approved pre-qualification sample. Submit any deviations from the approved sample for evaluation and approval before any shipment is accepted for payment.

Deviations from the approved sample after shipment of any parts of the order will be cause for rejection and nonpayment of the remainder of the order. Excessive delays or noncompliance by the vendor at any point in the approval process may be cause for cancellation and nonpayment.

2. Failure. Producers not qualified under this Specification may not furnish materials for

Department projects and must show evidence of correction of all deficiencies before reconsideration for qualification.

If any of the assemblies fail any of the tests, the supplier will be permitted to make one complete repair of the order on a timely basis, as determined by the Department. The supplier must reimburse the Department for any retesting required during acceptance.

The Department will base the cost for each retest, estimated at $1,500 per test, on time and charges.

TRAFFIC SAFETY DIVISION 4 – 40

Minor discrepancies noted in sampling and testing of this item must be corrected within

30 days of written notice of the discrepancies or as stated in the notice. Major discrepancies that in the opinion of the Department will substantially delay receipt and acceptance of the item will be cause for cancellation of the purchase order. Correct any discrepancies found in partial shipments before the delivery of subsequent shipments.

11170.5. Material Requirements.

A. Controller Unit. The controller unit must meet the requirements of NEMA Standards

Publication TS 2-2003 (TS 2), latest edition. Where a difference occurs, these requirements govern. The purchase document must identify either a TS 2 Type 1 interface or TS 2 Type 2 interface. This document specifies the cabinets for TS 2 Type 1 controllers. TS 2 Type 2 controller cabinets must use a cabinet specification identified in the bid document.

Each controller unit must have a unique serial number permanently and neatly displayed on the face of the unit. Affix an additional temporary label, neatly printed or typed, to the controller unit face if the serial number is not on the face of the unit.

Provide a controller unit that is completely solid state and digitally timed. All timing must be referenced to the 60-Hz power line.

The dimensions of the controller unit must not exceed 12.2 in. (305 mm) H, 17.6 in.

(440 mm) W, and 12.2 in. (305 mm) D.

Supply both TS 2 Type 1 and TS 2 Type 2 controllers with Port 1 SDLC and Port 2

RS 232. The TS 2 specification defines the connectors. Provide either a 9 pin RS 232 or

25 pin RS 232 connector for Port 3 for radio communications. When specified in the plans, provide an additional 9 pin FSK connector capable of FSK communications with

FSK modem installed. The controller must have a minimum of one Ethernet port on the front face of the unit.

The controller unit must be built using one or more vertical circuit boards. Requirement exceptions are the power supply, transformers, capacitors, and heat dissipating components.

No circuit cuts will be allowed on circuit boards in any of the equipment supplied. Any wire jumpers included on circuit boards must be in plated through-holes specifically designed to contain them. Jumpers that are tack soldered to circuit traces or are added to correct board layout errors are not acceptable.

Each of the following must be simultaneously displayed during standard NEMA dual-ring operation on the face of the unit:

• Phases in service (one per ring)

• Phases next to be serviced (one per ring)

• Presence of vehicle call (one per phase)

• Presence of pedestrian call (one per phase)

• Reason for green termination (one per ring)

▪ Gap-out

TRAFFIC SAFETY DIVISION 5 – 40

▪ Maximum time-out

▪ Force-off

• Pedestrian service (one per ring)

• Max II in effect (one per ring)

User-programmed entries must be stored and maintained in nonvolatile memory. Battery power is not allowed for this application.

The controller unit must be designed to operate properly with the logic ground isolated from the AC neutral (common).

Provide a high-quality keyboard with a rated lifetime of 1 × 106 operations or keystrokes on the front panel of the controller unit for use programming all user-entered timings and settings. Provide an operator entry that enables and disables the audible sound output

(default must be enabled).

Provide a direct-reading, alphanumeric liquid crystal display (LCD) with back lighting on the front panel of the controller unit. The display must be clearly readable in ambient light—including the cabinet light, full sunlight, or the absence of light—from a distance of 1.0 m at a 45° angle. The display must have an automatic time-out feature approximately 10 minutes after the last keystroke, unless the display has an expected continuous life of 10 years or more, and must have an operating temperature range of -34°C to + 74°C.

The display must be a minimum 40-character × 4-line display. The bidder may be required to supply literature demonstrating that all display requirements of this

Specification are met before the awarding of the bid. (If a LCD contrast adjustment is required for visibility at temperature extremes, then the control must be on the face of the controller unit, adjustable without the use of tools.)

B. Time Clock. The clock must use the 60-Hz power line frequency as time base when power is present. The clock operating voltage range must be 89 to 135 VAC over the temperature range of −34°C to +74°C. A 10-year lithium battery must maintain the time-of-day clock and digital data during a power outage lasting up to 30 days. Lead-acid, nickel-cadmium, or alkaline batteries are not acceptable.

The time base clock must be maintained to within ± 0.005% at 20°C and to within a

± 0.02% over the specified operating temperature range as compared to Coordinated

Universal Time (WWV) standard for a period of 30 days during periods when AC power is not applied.

C. Clock-Calendar Programming. The clock must:

• Be easily set to the year, month, day of month, day of week, hour, minute, and second

• Must store sequences of operations in the form of 255 entries and 15-day plans

The keyboard must provide:

• Automatic daylight-savings time entry

• Capability for the user to program dates for fixed and floating holidays

TRAFFIC SAFETY DIVISION 6 – 40

Special Calendar adjustments for leap years must be automatic.

TRAFFIC SAFETY DIVISION 7 – 40

Table 1

Schedules

Global Time Base Schedule Actuated Traffic Signal

Schedule

Entry Months Dates of Mo Days of Wk. Day Plan Time Base Actions

1 1–12 1–31 1–7 1–15 entry 1 actions

255 " " " " entry 255 actions

1. Structure and Interrelationship of Programs. A day plan must consist of the following, where each action is unique:

Table 2

Structure and Interrelationship of Programs

Hour : Minute Action 1 (time to implement: action to implement)

Hour : Minute Action 10 (time to implement: action to implement)

There must be a minimum of 10 actions per day plan.

There must be a minimum of 15-day plans.

Each action in a day plan must consist of a group of the following objects:

• Pattern, consisting of:

▪ Cycle length

▪ Offset

▪ Split

▪ MUTCD flash (on-off)

▪ Free operation

• Sequence

• Special functions 1–8 (on-off)

• Auxiliary functions 1–3 (on-off)

• Mode of operation (a means of changing operating modes by time of day)

• Max II

• Gap / extension II

• Phase omits

Any or all of these may be selected within a single action.

Transfer into and out of FLASH must be in accordance with the Texas MUTCD. It must be possible to program each phase and overlap to flash either yellow or red via the front panel of the controller unit. This must be accomplished by flashing the load-switch driver outputs simultaneously.

TRAFFIC SAFETY DIVISION 8 – 40

An entry must consist of time period implemented: day plan, months, dates of the month, and days of the week.

A minimum of 255 entries must be programmable.

There must be a copy feature that allows the transfer of entries between day plans.

Other programming schemes that meet the functional intent are acceptable but require approval in writing by the TRF Signal Operations Engineer.

D. TBC. The internal reference sync pulse, from which the local offset is calculated, must resynchronize at midnight, or the resynchronization must be user programmable with a default to midnight. A pulse must be generated whenever the time-of-day clock shows a time that is an exact multiple of the current cycle length after this resynchronization. In case of a power failure, re-sync must be calculated from the programmed re-sync time.

The power failure recovery routine must accommodate the case of a power failure at midnight.

E. Diamond Operation.

1. Program Requirements. Assign phase numbers to traffic movements as shown on the diamond intersection layout in the following figure. Overlap A (OL A) is defined as phases 1+2. Overlap B (OL B) is defined as phases 5+6.

4 3

OL A

2 OL B

Figure 1

Assignment of phase numbers for diamond intersection layout.

There must be six additional user-programmable overlaps. All additional overlaps must be programmable through the keyboard and must function as specified by TS 2.

The controller unit must be programmable for four-phase and three-phase diamond operation as well as for two independent, four-phase rings (separate intersection operation) as shown in the following figure.

TRAFFIC SAFETY DIVISION 9 – 40

4 3 2 1

8 7 6 5

Ring 1

Ring 2

Figure 2

Separate intersection ring structure.

The following modes must be available for each phase and for the intervals identified as special intervals in three-phase and four-phase operation:

• Maximum Recall

• Minimum Recall

• Pedestrian Recall

• Detector Locking and Non-Locking Memory

• Phase Omit

The controller unit must be designed to provide pedestrian phasing with phases two, four, six, and eight.

All timing entries and displays must be available for phases three and seven.

The operation of the controller unit as a four-phase, three-phase, or separate-intersection-operation diamond must be keyboard selectable. This must be overridden while under closed-loop system control or by TBC control.

2. Four-Phase Operation. The controller unit must perform the sequences for four-phase and 6-phase diamond operation defined in Figures 3–8.

The normal four-phase operation sequence must be: 18164525 →→→ . The six-phase operation sequence must be: 181716453525 →→→→→ .

The point at which operation may be switched from four-phase to three-phase operation must be at the clearance interval 2516B or 2518B to the three-phase clearance interval 15.

3. Concurrent Timing Requirements. Refer to Figures 3–6 for the following descriptions:

Intervals 4516B and 4516C must time concurrently with interval 16; however, interval

16 may not terminate green until interval 4516C has timed out.

Intervals 3516B and 3516C must time concurrently with interval 16; however, interval

16 may not terminate green until interval 3516C has timed out.

TRAFFIC SAFETY DIVISION 10 – 40

Intervals 1825B and 1825C must time concurrently with interval 25; however, interval 25 may not terminate green until interval 1825C has timed out.

Intervals 1725B and 1725C must time concurrently with interval 25; however, interval 25 may not terminate green until interval 1725C has timed out.

All left-to-right internal clearance times (intervals 4518B, 4517B, 3518B, 3517B, 2518B, 2517B, and 2516B) must use the same timing settings for minimum green, extension, maximum (max) green, yellow clearance, and red clearance.

All right-to-left internal clearance times (intervals 1845B, 1835B, 1745B, 1735B, 1645B, 1635B, and 1625B) must use the same timing settings for minimum green, extension, max green, yellow clearance, and red clearance.

Separate timing settings for minimum green, extension, max green, yellow clearance, and red clearance must be provided for each of the four external clearance intervals

(1825B, 1725B, 4516B, and 3516B).

Clearance Interval to 16

2516A

2516C 2517C or 2518C

From 25 Clearance Interval to 35 or 45

2535A or 2545A

Clearance Interval to 17 or 18

2517A or 2518A

2516B* 2517B* or 2518B*

* Special Interval

Figure 3

Four-phase operation sequence—clearance intervals from phase 25.

TRAFFIC SAFETY DIVISION 11 – 40

4517C or 4518C 4516C

4517B* or 4518B*

From 45 Clearance Interval to 25 or 35

4525A or 4535A

Clearance Interval to 17 or 18

4517A or 4518A 4516A

Clearance Interval to 16

4516B*

Figure 4

Four-phase operation sequence—clearance intervals from phase 45.

1835B* or 1845B*

1835C or 1845C

From 18 Clearance Interval to 16 or 17

1816A or1817A

Clearance Interval to 35 or 45

1835A or 1845A 1825A

Clearance Interval to 25

1825B*

1825C

Figure 5

Four-phase operation sequence—clearance intervals from phase 18.

TRAFFIC SAFETY DIVISION 12 – 40

From 16

Clearance Interval to 17 or 18

1617A or 1618A

Clearance Interval to 25

1625A

Clearance Interval to 35 or 45

1635A or 1645A

1625B* 1635B* or 1645B*

1625C 1635C or 1645C

Figure 6

Four-phase operation sequence—clearance intervals from phase 16.

1735B* or 1745B*

1735C or 1745C

From 17 Clearance Interval to 16 or 18

1716A or 1718A

Clearance Interval to 35 or 45

1735A or 1745A 1725A

Clearance Interval to 25

1725B*

1725C

Figure 7

Four-phase operation sequence—clearance intervals from phase 17.

TRAFFIC SAFETY DIVISION 13 – 40

3517B* or 3518B*

3517C or 3518C

From 35 Clearance Interval to 25 or 45

3525A or 3545A

Clearance Interval to 17 or 18

3517A or 3518A 3516A

Clearance Interval to 16

3516B*

3516C

Figure 8

Four-phase operation sequence—clearance intervals from phase 35.

4. Diamond Detector Operation. The loop-detector layout for three-phase, four-phase, six-phase, or separate-intersection diamond operation must be as shown in the following figure. The detector operation defined must be automatically loaded when any diamond sequences are selected.

1 1

11 2

8 7

14 13

Figure 9

Loop-detector layout for diamond-intersection operation.

The controller unit software must provide the logic for detector operation described in

Table 3.

TRAFFIC SAFETY DIVISION 14 – 40

Table 3

Detector Operation Requirements

Detector Four- and Three-Phase Requirements

1 In 4-phase operation:

▪ Must call phase 6 if Overlap A is not green and phase 7 is not called.

▪ Must call phase 6 if Overlap A is not green and phase 8 is not called.

▪ Extend intervals 2516B, 2517B, 2518B, 4517B, 4518B, 3517B, and 3518B.

In 3-phase operation:

▪ Must call and extend phase 1 (left turn).

5 In 4-phase operation:

▪ Must call phase 2 if Overlap B is not green and phase 3 is not called.

▪ Must call phase 2 if Overlap B is not green and phase 4 is not called.

▪ Extend Intervals 1625B, 1635B, 1645B, 1735B, 1745B, 1835B, and 1845B.

In 3-phase operation:

▪ Must call and extend phase 5 (left turn).

2, 3, 4, 6, 7, and 8

These setback detectors (or detector sets) belong to the parent phases with the same number

(e.g., detector 2 belongs to phase 2) as shown in Figure 9. These detectors must have a 2-sec.

delay set during red conditions of their parent phase. The detectors are used to extend the parent phase during green.

11, 12, 15, 16, 17, and

These detectors are stop bar detectors and are used to call the associated parent phases shown in

Figure 9. The parent phase green plus a call for that phase plus a 0.2-sec. gap on the detector must disable the detector until the end of green.

9 and 10 In 4-phase operation:

▪ Must extend phase 2 if phase 3 is called

▪ Must extend phase 2 if phase 4 is called

▪ Must call phase 6 if Overlap A is not green and phase 7 is not called

▪ Must call phase 6 if Overlap A is not green and phase 8 is not called

▪ Extend intervals 2516B, 2517B, 2518B, 4517B, 4518B, 3517B, and 3518B

In 3 phase operation:

▪ Must function as a phase-1 calling detector during phase 3 or 4 and as a phase-1 extending detector when a phase 3 or 4 call exists

13 and 14 In 4 phase operation:

▪ Must extend phase 6 if phase 7 is called

▪ Must extend phase 6 if phase 8 is called

▪ Must call phase 2 if Overlap B is not green and phase 3 is not called

▪ Must call phase 2 if Overlap B is not green and phase 4 is not called

▪ Extend Intervals 1625B, 1635B, 1645B, 1735B, 1745B, 1835B, and 1845B

In 3 phase operation:

▪ Must function as a phase-5 calling detector during phase 7 or 8 and as a phase-5 extending detector when a phase 7 or 8 call exists

TRAFFIC SAFETY DIVISION 15 – 40

5. Three-Phase Operation. The controller unit must be keyboard selectable for three-phase diamond operation.

The controller unit must perform the sequences for three-phase diamond operation defined in Figure 10 and in Table 4.

The normal sequence of operation must be 516284 +→+→+ .

The point at which operation may be switched from three-phase to four-phase operation must be through the transition phase sequence to four-phase interval 25 as indicated in

Figure 10.

The controller must be programmable for simultaneous gap operation for phases 4 and

8 in three-phase operation to allow a phase to extend out of a green rest state. When the phase or phases to be serviced next conflict with both phases being serviced, both concurrent phases must reach a green rest state together before they terminate.

Termination of the max timer or application of a force-off must override this feature.

The phases must not be allowed to advance to a green interval beyond the rest state that might override or defeat the simultaneous gap operation.

Transition Phase to

4 Phase Operation

Figure 10

Three-phase diamond operation.

TRAFFIC SAFETY DIVISION 16 – 40

Table 4

Three-Phase Diamond Sequence

From

Interval

IF

Call On

AND

No Call

On

GO TO

Interval

48 2 and 6 ---- 2+6

2 or 6 1 or 5 2+6

1 and 6 2 1+6

2 and 5 6 2+5

5 1 or 2 or 6 4+5

4 and 5 8 4+5 If Min Time of 5 Can be Serviced Before Max Time of

1 2 or 5 or 6 1+8

1 and 8 4 1+8 If Min Time of 1 Can be Serviced Before Max Time of

1 and 5 2 or 6 1+5

45 8 ---- 4+8 if 4+8 Was Not Serviced Immediately Before 4+5

8 1 or 2 or 6 4+8

2 and 6 8 2+6

6 8 or 1 2+6

2 8 or 6 2+5

1 and 6 8 or 2 1+6

1 8 or 2 or 6 1+5

18 4 ---- 4+8 if 4+8 Was Not Serviced Immediately Before 1+8

4 5 or 2 or 6 4+8

2 and 6 4 2+6

2 4 or 5 2+6

6 4 or 2 1+6

2 and 5 4 or 6 2+5

5 4 or 2 or 6 1+5

26 (1 and 5) or

4 or 8

2 or 6 1+5

5 6 or 4 or 8 2+5

2 and 5 6 2+5

1 2 or 4 or 8 1+6

1 and 6 2 1+6

25 1 or 8 ---- 1+5

4 1 or 8 4+5

6 1 or 4 or 8 2+6

16 4 or 5 ---- 1+5

8 4 or 5 1+8

TRAFFIC SAFETY DIVISION 17 – 40

From

Interval

IF

Call On

AND

No Call

On

GO TO

Interval

2 4 or 5 or 8 2+6

15 4 and 8 ---- 4+8

4 8 4+5

8 4 1+8

2 and 6 4 or 8 2+6

2 4 or 6 or 8 2+5

6 2 or 4 or 8 1+6

F. Coordination-Control Hierarchy. When the system switch is in the SYSTEM position, the controller unit must be under the control of the master controller or TBC.

In the absence of any on line closed-loop-system control by a master controller, the internal TBC must control the coordinated, free, and flash operation of the intersection when the system switch is in the SYSTEM position.

When a master controller brings the intersection on line, its control must supersede that of the internal time-base coordination.

When the system switch is in the FREE position, the controller unit must operate in a non-coordinated (free) mode.

G. Preemption (PE). The internal preemptor supplied must be easily programmable from the front panel for either railroad- or emergency-vehicle PE sequences.

Phases must be selectable such that a limited signal sequence may be operational during

PE. It must be possible to add phases that are not in the intersection sequence to this special limited sequence without adding external logic.

The intervals shown in Table 5 must be provided as a minimum. Terminology may vary, but the meaning must be clear. Additional unspecified intervals that may lead to confusion must be programmable to zero. If abbreviations are used on the display, they must be defined on the front panel. While in PE, the display must clearly identify the intervals being timed as PE intervals. Yellow and red clearances from the phase timings may be used in place of the clearance intervals shown.

TRAFFIC SAFETY DIVISION 18 – 40

Table 5

PE Timing Interval Definitions

Interval1 Description

0. PE Delay This time must start immediately when the PE command is received. It must not affect the normal operation of the controller unit until the delay time out occurs. This interval may be used for emergency-vehicle (fire-lane) PE delay. If zero time is set, the interval must be omitted.

1. PE Minimum

Duration

The PE sequence must not terminate until the PE input signal is removed and the Minimum Duration time has expired.

2. PE Minimum Green Any vehicle signal that is green at the time this interval becomes active must not terminate unless it has been displayed for at least the time programmed in this interval. If zero time is set, the interval must be omitted.

3. PE Minimum Walk PE Minimum Walk Time (in seconds). A PE-initiated transition must not cause the termination of a

Walk before its display for this period.

4. PE Ped Clearance At the time of PE call, walk-indications must immediately change to Pedestrian Clearance interval.

The Pedestrian Clearance interval must not terminate unless it has been displayed for at least the time programmed in this interval. If zero time is set, the interval must be omitted.

5. PE Track Green Signals programmed as track (or fire-lane) signals must remain green or be changed to green. All other signals must be red. This interval must be optionally programmable to zero during emergency-vehicle PE.

6. PE Dwell Green Minimum Dwell Time (entered in seconds). This parameter controls the minimum timing for the dwell movement. The phases allowed during the dwell interval must be selectable to include all phases that do not cross the track. The dwell interval must not terminate before the completion of

PE-duration time and PE-dwell time, and until the call is no longer present. Each signal must be keyboard-programmable for red, red flash, yellow flash, or green. As an alternative, a limited cycle must be programmable for use with railroad PEs.

7. PE Exit Ped Clear PE Exit Pedestrian Clear Time (in seconds). This parameter controls the pedestrian clear timing for a walk signal transition to the exit phase or phases.

8. PE Exit Yellow This interval must provide a solid yellow clearance for indications that were green or flashing yellow. Red and flashing red displays must display solid red.

9. PE Exit Red

Clearance

This interval must be an all-red clearance in preparation for return to the normal cycle. Return phases must be programmable from the keyboard.

10. PE Max Call This interval is the amount of time that a PE call may remain active and be considered valid. When the PE call has been active for this amount of time, the controller must return to normal operation.

The PE call must be considered invalid until the call is no longer active.

1. 1. All intervals are sequential.

TRAFFIC SAFETY DIVISION 19 – 40

Table 6 shows PE timing interval ranges.

Table 6

PE Timing Interval Ranges

Timing Interval Time

(seconds)

Increments

(seconds)

0. PE Delay (Emergency vehicle PE) 0–999 1

1. PE Minimum Duration 0–999 1

2. PE Minimum Green 1–255 1

3. PE Minimum Walk 1–255 1

4. PE Ped Clearance 1–255 1

5. PE Track Green 1–255 1

6. PE Dwell Green 1–255 1

7. PE Exit Ped Clear 0–255 1

8. PE Exit Yellow 3.0–25.5 0.1

9. PE Exit Red Clearance 0–25.5 0.1

10. PE Max Call 0–999 1

The phases to be serviced following the PE sequence must be front-panel-keyboard programmable.

PE sequences must be selectable using external inputs. PE priority must be assigned with

#1 being the highest. If a higher-priority PE input is received during a PE sequence, the controller unit must immediately transition to the new sequence subject to the constraints of PE Minimum Green and PE Minimum Walk. The transition must take place in a safe manner from any point in the sequence and must meet all Texas MUTCD requirements.

Provisions must be made to clear two conflicting track phases from a single PE input.

This may be provided by two-track clearance phases for a single PE or by combining two

PEs.

PE 1 must be reserved for a priority railroad PE. If more than two PEs are provided, it must be possible to delete the priority override for all but the railroad PE. If a non-priority

PE is activated during another PE cycle, the one in progress must continue through its entire cycle. If the second PE input is still active when the first one is completed, the controller unit must immediately go to all-red flash or initiate the non-priority PE. When all PE inputs are removed, the controller unit must proceed through the normal sequence to Return Red Clearance (interval 9).

Once the controller unit has entered the first timed interval following PE Delay

(interval 1), the sequence must continue to the end, even if the PE call is dropped. If the call returns, the Minimum Preempt Duration (interval 1) the controller unit should reinitiate track green and complete the PE sequence.

The controller unit must be programmable to be in flash or in limited sequence during interval 6. If flash is specified, the phases must flash yellow or red as programmed from the front panel. Flash must be implemented by simultaneously flashing the appropriate

TRAFFIC SAFETY DIVISION 20 – 40

load-switch driver outputs. If limited sequence is selected, all phases must be programmable even if not normally used in the intersection sequence.

In the event of a power interrupt as defined by TS 2, if the PE command is present when power is restored, the controller unit must power up in cabinet flash operation and remain there until the PE command is removed.

Overlap phases must begin and terminate with the parent phases as described in TS 2. If the PE call occurs during yellow or red displays between parent phases, the overlap phase must display a minimum of 3 sec. of yellow and a minimum of 1 sec. of red clearance.

“Don't Walk” must be displayed throughout the PE sequence unless a limited cycle is run.

During a limited cycle (interval 6), the pedestrian heads may be programmed to be dark.

PE routines must have priority over all controller functions.

The controller must be programmable to allow multiple track clearance phases either within a single PE sequence or by…