ESBD_427930_1749755071524_Combined Drawings.pdf
PDF 6 MB Posted
- Attached to
- TDCJ Ramsey Unit: Renovate Water Tower
- Solicitation number
- 696-FD-25-B049
- Issued by
- Brazoria County, Texas
About this file
These are construction plans for a water tower renovation project for the Texas Department of Criminal Justice (TDCJ) at the Ramsey Unit, located in Brazoria County, Texas. The project involves electrical demolition, site preparation, and comprehensive upgrades to the existing elevated storage tank (EST) Ramsey Unit No. 1, with a specific focus on cathodic protection, electrical infrastructure, and instrumentation improvements. The project is dated March 1, 2023, and was issued for bid with the project number MWR: 01721012.
The documents detail extensive technical specifications for electrical systems, including power panel configurations, heat trace controls, and cathodic protection systems. The renovation includes installing a new electrical rack, replacing existing instrumentation, adding zinc anodes for corrosion protection, and implementing a comprehensive grounding system. The project involves precise electrical work such as conduit installation, wire routing, and integration of new equipment with existing infrastructure at the water tower site. The technical drawings provide detailed schematics for wire routing, anode suspension, and electrical isolation, indicating a comprehensive approach to modernizing the facility's electrical and protective systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEXAS DEPARTMENT OF CRIMINAL JUSTICE
RAMSEY UNIT
RENOVATE WATER TOWER
MWR: 01721012
CONSTRUCTION PLANS FOR
MARCH 1, 2023
ISSUED FOR BID
61026
M = MOTOR CONTACTOR
TR = TIMING RELAY
CR = CONTROL RELAY
ALT = ALTERNATOR
BASIC RELAY SYMBOL-SOME RELAY FUNCTIONS:
MOTOR OR STARTER ENCLOSURE SPACE HEATER
GROUND
CONTACT - NORMALLY CLOSED
CONTACT - NORMALLY OPEN
THERMAL OVERLOAD HEATER - AMBIENT COMPENSATED
CIRCUIT BREAKER - THERMAL MAGNETIC 3 POLE UNLESS
INDICATED OTHERWISE CONTINUOUS AMP TRIP SETTING INDICATED
150A
3 POLE UNLESS INDICATED OTHERWISE.
FUSED SWITCH - SWITCH AND FUSE CURRENT RATING INDICATED.
100A SWITCH - CURRENT RATING INDICATED. 3 POLE UNLESS INDICATED
OTHERWISE
FUSED TERMINAL BLOCK
M
MOTOR, SQUIRREL CAGE INDUCTION-HORSEPOWER
INDICATED ON ONE LINE.
LUMINAIRE, POLE MOUNTED.
GFI = GROUND FAULT INTERRUPTER
CR = CORROSION RESISTANT
WP = WEATHERPROOF
CONVENIENCE RECEPTACLE-DUPLEX UNLESS SPECIFIED OTHERWISE
MOMENTARY PUSHBUTTON NORMALLY CLOSED
MOMENTARY PUSHBUTTON NORMALLY OPEN
POLE 2
POLE 1
OOX
XOO
H A
O SELECTOR SWITCH-MAINTAINED CONTACT. CHART DEFINES OPERATION:
0 = OPEN CONTACT
X = CLOSED CONTACTPOLE
OFF
X
HAND
AUTO
X
POSITION
A A = AMBER
INDICATING LIGHT-PUSH TO TEST (PTT) LETTER INDICATES COLOR.
ELECTRICAL SYMBOLS
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
SWITCHGEAR / MCC SYMBOLS
ELECTRICAL ABBREVIATIONS
TRANSFORMER
THERMOSTAT
ELECTRICAL LEGEND
SSOLR
SOLID STATE OVERLOAD RELAY
MOTOR OVERLOAD, PHASE LOSS,
AND CURRENT UNBALANCE
PROTECTION
G = GREEN
R = RED
Y = YELLOW
B = BLUE
W = WHITE
PTT
AUTO AUTOMATIC
AUX AUXILIARY
CC CONTROL CABLE
CR CONTROL RELAY
CS CONTROL SWITCH
CT CURRENT TRANSFORMER
FLA FULL LOAD AMPERE
FU FUSE
J,JB JUNCTION BOX
KVA KILOVOLT-AMPERE
KILOWATTKW
LS,LMS LIMIT SWITCH
MAGNETIC CONTACTOR COILM
M ELECTRIC MOTOR
N NEUTRAL GROUNDED
CONDUCTOR
OC OVERCURRENT
PH PHASE
VOLTV
XFMR TRANSFORMER
HAND OFF AUTOMATIC SWITCHHOA
ISOLATION SWITCHISW
GREEN INDICATING LIGHTG
M MAIN CONTACTOR AUXILIARY
MIN MINUTES
SEC SECONDS
TR TIMER
EI ELECTRICAL INTERRUPT
FULL VOLTAGE NON-REVERSINGFVNR
CPT CONTROL POWER TRANSFORMER
ETM ELAPSED TIME METER
SA SURGE ARRESTOR
MTS MANUAL TRANSFER SWITCH
RVSS REDUCED VOLTAGE SOFT START
WEATHER PROOFWP
BC BYPASS CONTACTOR
LINE CONTACTORLC
LEVEL FLOAT
RECEPTACLE - 240V., 1ɸ OR 208V., 1ɸ
ATS AUTOMATIC TRANSFER SWITCH
SPD SURGE PROTECTIVE DEVICE
INDICATES FOUNDATION
#2/0 STRANDED BARE TINNED COPPER WIRE, SOFT DRAWN
AS SHOWN ON PLANS
UNDERGROUND ELECTRIC DUCTBANK
EXISTING EQUIPMENT
GROUNDING CONNECTION EXOTHERMIC
OR COMPRESSION
GATE FLEXIBLE GROUNDING STRAP.
TEST WELL WITH GROUND ROD CONNECTION
3/4" X 10' LONG.
GROUND ROD CONNECTION 3/4" X 10' LONG.
ABOVE GRADE TAIL FOR EQUIPMENT CONNECTION. TO BE
LOCATED FOR PROPER EQUIPMENT ENTRANCE.
PENETRATION THRU CONCRETE TO HAVE SCHEDULE 80 PVC
PIPE SEGMENT.
GROUNDING CONNECTION
15LB ZINC ANODE. ZINC ANODES TO BE
SPACED A MINIMUM OF 20' APART.
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
EST No. 1
GST No. 1
AERATOR
PUMP BLDG & CHLORINE ROOM
STORAGE
BLDG
EXISTING GST &
PUMP BUILDING
WATER WELL No. 1
CHAIN LINK FENCE
FM 655
CONTRACTOR
STAGING AREA
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
GENERAL NOTES:
1. CONTRACTOR TO COORDINATE WITH
OWNER FOR ALL DEMOLITION.
2. OWNER RESERVES THE RIGHT TO ALL
EQUIPMENT REMOVED BEFORE
DISPOSAL. CONTRACTOR TO
COORDINATE WITH OWNER PRIOR TO
DISCARDING ANY OF EQUIPMENT.
CONTRACTOR SHALL PROPERLY
DISPOSE OF ALL UNSALVAGEABLE
EQUIPMENT.
3. ALL EXISTING CABLES/CONDUITS NOT
BEING USED SHALL BE REMOVED.
4. ASBESTOS CONTAINING MATERIAL (ACM)
COULD BE PRESENT IN THE ELECTRICAL
DUCTBANKS. CONTRACTOR SHALL HAVE
PERSONNEL QUALIFIED TO IDENTIFY
ACM. IF DISCOVERED, CONTRACTOR
SHALL STOP WORK, NOTIFY OWNER AND
ENGINEER.
X DENOTES THE DETAIL LETTER THAT
IS REFERENCED ON SHEET E-3.
DEMOLITION
LEGEND
E-3 X
E-3 B
E-3 A
SCALE: N.T.S.
GENERAL NOTES:
1. OWNER RESERVES THE RIGHT TO ALL EQUIPMENT REMOVED BEFORE DISPOSAL. CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO DISCARDING ANY OF OWNERS EQUIPMENT. CONTRACTOR SHALL PROPERLY DISPOSE OF ALL UNSALVAGEABLE EQUIPMENT.
2. CONTRACTOR TO DOCUMENT EXISTING POWER PANEL CONNECTIONS AND RECONNECT EQUIPMENT TO EXISTING POWER PANEL CIRCUITS.
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
EXISTING TO OBSTRUCTION LIGHT.
REMOVE CABLE & CONDUIT
DURING TANK REHAB AND
REPLACE WHEN COMPLETE.
CABLE & CONDUIT EXTEND
TO OBSTRUCTION LIGHT AT
TANK BOWL CENTER TOP.
SCALE: N.T.S.
REMOVE PRESSURE GAUGE
DURING TANK REHAB AND
REPLACE WITH NEW
PRESSURE GAUGE WHEN
COMPLETE. HEAT TRACE
PER PLANS &
SPECIFICATIONS WILL BE
PROVIDED FOR GAUGE
CONNECTION TO FILL
COLUMN.
REMOVE PRESSURE
INSTRUMENT INCLUDING
ASSOCIATED CABLE &
CONDUIT DURING TANK
REHAB AND REPLACE WITH
NEW INSTRUMENT PER
SPECIFICATIONS AND NEW
CABLE & CONDUIT WHEN
REHAB IS COMPLETE.
INSTRUMENT WILL BE
LOCATED ON NEW RACK
PER SHEET E-6 AND WILL
REQUIRE HEAT TRACE FOR
WATER LINE CONNECTION
TO TANK.
EST NO. 1
GST NO. 1
AERATOR
PUMP BLDG & CHLORINE ROOM
STORAGE
BLDG
EXISTING GST &
PUMP BUILDING
WATER WELL NO. 1
CHAIN LINK FENCE
FM 655
CONTRACTOR
STAGING AREA
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
#2/0 STRANDED BARE TINNED COPPER WIRE,
SOFT DRAWN AS SHOWN ON PLANS
UNDERGROUND ELECTRIC DUCTBANK
EXISTING EQUIPMENT
GROUNDING CONNECTION EXOTHERMIC
OR COMPRESSION
GATE FLEXIBLE GROUNDING STRAP.
TEST WELL WITH GROUND ROD CONNECTION
3/4" X 10' LONG.
GROUND ROD CONNECTION 3/4" X 10' LONG.
ABOVE GRADE TAIL FOR EQUIPMENT
CONNECTION. TO BE LOCATED FOR PROPER
EQUIPMENT ENTRANCE. PENETRATION
THRU CONCRETE TO HAVE SCHEDULE 80
PVC PIPE SEGMENT.
GROUNDING CONNECTION
NOTES:
1. EXISTING INSTRUMENTATION SUPPORT AND INSTRUMENT TO
BE DEMOLISHED AFTER NEW RACK AND EQUIPMENT IS FULLY
ENERGIZED, TESTED AND OPERATIONAL. CONTRACTOR TO
COORDINATE WITH OWNER FOR DEMOLITION.
2. ALL ABOVE GROUND CONDUIT SHALL BE INSTALLED AS TO
NOT CREATE A TRIPPING HAZARD.
3. PVC COATED RGS CONDUIT SHALL BE PROVIDED IN AREAS
WHERE CONCRETE COMES INTO CONTACT WITH RGS
CONDUIT.
4. SEE SHEET E-5 DETAIL B FOR GROUNDING DETAILS FOR
ELECTRICAL RACK.
5. CONTRACTOR SHALL OBSERVE NEC WORKING SPACE
REQUIREMENTS WHEN LOCATING EQUIPMENT.
6. ALL GROUND GRID CONDUCTORS SHALL BE CONTINUOUS
EXCEPT WHERE SPLICING IS UNAVOIDABLE.
7. GROUND RESISTANCE SHALL MEASURE 5 OHMS OR LESS.
CONTRACTOR TO ADD SUPPLEMENTAL GROUND RODS
WHERE NECESSARY TO ACHIEVE THE RESISTANCE
REQUIRED.
8. UTILITIES NOT SHOWN FOR CLARITY. PLEASE SEE CIVIL
DRAWINGS FOR UTILITIES.
9. GROUND WIRE TO BE INSTALLED NOT LESS THAN 30" DEEP.
CONTRACTOR SHALL DETERMINE LOCATION OF GROUND
WIRE BASED ON UNDERGROUND CONDITIONS. VERIFY THERE
ARE NO UTILITY CONFLICTS PRIOR TO PLACEMENT.
10. ELEVATED STORAGE TANK GROUNDING SHALL BE
ACCOMPLISHED BY USING FOUR (4) 15LB ZINC ANODES. THE
TANK SHALL BE CONNECTED TO THE ANODES USING
INSULATED #2/0 COPPER WIRE. THE SPLICE CONNECTING
THE #2/0 TO THE ANODE SHALL BE ELECTRICALLY INSULATED
FROM THE SOIL USING HEAT SHRINK. COPPER SHALL NOT BE
ALLOWED TO CONTACT THE SOIL.
11. CONTRACTOR SHALL INSTALL DUCTBANK PER SHEET E-5
FROM PUMP BUILDING TO ELEVATED STORAGE TANK
ELECTRICAL RACK. DUCTBANK SHALL INCLUDE THE
FOLLOWING:
6-#10 THWN, 3-#12 GND IN 1" CONDUIT
1-#16 TW/SH/PR IN 2" CONDUIT (RUN TO NEW PULLBOX
IN PUMP BUILDING)
1-SPARE 1" CONDUIT (CAP ON BOTH ENDS)
EST ELECTRICAL
RACK REFER TO
SHEET E-6 AND
NOTE 1.
ADDED DUCTBANK
FOR ELECTRICAL
RACK EQUIPMENT.
15LB ZINC ANODE
COVER
FINISHED GRADE
GROUND TEST WELL ARRANGEMENT
TYPICAL STRUCTURE GROUND DETAILB
TEST LOOP
10-INCH
DIAMETER
DUCTILE IRON
PIPE SPOOL
#2/0 BARE TINNED
COPPER GROUND LOOP
3/4" x 10' GROUND ROD
O.Z. GEDNEY TYPE "ABG"
GROUND CLAMP
TYPICAL LOW VOLTAGE DUCT BANK SECTION
NOTES:
1. PROVIDE 100% CONCRETE ENCASEMENT BOTH HORIZONTALLY AND
VERTICALLY.
2. CONTRACTOR SHALL COORDINATE LOCATION WITH EXISTING AND
NEW UNDERGROUND WATER PIPE, AND ELECTRIC CABLE/CONDUIT.
3. REBAR SHALL BE WIRE TIED TO REBAR STIRRUPS TO PROVIDE
STABILITY DURING CONCRETE POUR.
4. ALL BACKFILL SHALL BE COMPACTED TO 98% OF THE MAXIMUM DRY
DENSITY OR DETERMINED BY TXDOT TEST METHOD TEX-113E
5. REFER TO GEOTECH REPORT AND STRUCTURAL DRAWINGS FOR
BACKFILL MATERIAL TYPE AND BACKFILL MOISTURE CONTENT.
6. REFER TO GEOTECH REPORT AND STRUCTURAL DRAWINGS FOR
EXCAVATION.
7. UNDERGROUND DUCT BANK BENDS 25 DEGREES AND LARGER SHALL
BE PVC-COATED RIGID GALVANIZED STEEL.
8. CONNECT ALL NON CURRENT-CARRYING METAL PART AN ANY
METALLIC RACEWAY GROUNDING BUSHINGS TO GROUND ROD
CONNECTOR WITH #2/0 AWG COPPER CONDUCTOR.
9. IF METAL STRUCTURES ARE NOT FURNISHED WITH PROVISION FOR
BOLTED CONNECTION TO GROUNDING SYSTEM, CONTRACTOR SHALL
PROVIDE WELDED PAD FOR GROUND CONNECTION.
10. CABLES SHALL NOT BE DIRECTLY BOLTED TO STRUCTURES.
11. CLAMPS FOR CONDUIT AND CABLE INSTALLATION. INSTALL CONDUIT
7" MINIMUM FROM LADDER SIDE RAILS.
12. UNISTRUT TO BE POSITIONED WHERE CONDUITS INSTALLED ARE
VISIBLE FROM LADDER FOR INSPECTION PURPOSED.
13. PROVIDE GROUND TEST WELL FOR EST.
TYPICAL DUCT BANK TRANSITION DETAIL
" M
IN
. C
O
VE
R
6" WIDE WARNING TAPE
#3 GRADE 60 REBAR.
TIE AT 3'-0" MAX. SPACING.
3000 PSI CONCRETE AT 28 DAYS.
FINISHED GRADE REFER
#5 GRADE 60 REBAR AT EACH CORNER
2"
2"
6" FLEXIBLE BASE
10"
2" MIN. HMAC (IF REQUIRED)
TO GRADING PAN
CONDUIT
3" MINIMUM
COVER.
TYPICAL ALL
AROUND
COMPACTED MATERIAL BACKFILL
PER GEOTECH REPORT MUST BE
BETWEEN TOP OF CONCRETE AND
WARNING TAPE. SEE NOTE 5.
COMPACTED BACKFILL REFER
TO GEOTECH REPORT
BOTTOM OF TRENCH SHALL BE
COMPACTED FLAT SURFACE FREE OF
LOOSE MATERIAL.
3"
EQUIPMENT PAD
PVC SLEEVE
EQUIPMENT RACK
WALL OR STRUCTURE
FINISH GRADE
3/8" THICK STEEL WELDED TO STRUCTURE
NEMA 2-HOLE BOLTED CONNECTION
#2/0 STRAND SOFT DRAWN BARE COPPER
#2/0 STRAND
SOFT DRAWN
BARE COPPER
RGS NIPPLE
" M
IN
(U N
LE
SS
N O
TE
D
PVC COATED RGS
SCHEDULE 40 PVC COUPLING
CONDUIT BASE SPACER
SCHEDULE 40 PVC
RED CONCRETE
ENCASEMENT SEE
DETAIL C.
THREADED RGS
COUPLING END
FINAL GRADE OR
TOP OF SLABPVC COATED
PVC COATED RGS
COUPLING
SIDE VIEW:
UNISTRUT:
BOLTED TO ANGLE CLIPS WITH STAINLESS
BOLTS/ NUTS AND WASHERS
SEAL WELD AT MAX.
ALLOWABLE SPACING
SIDE VIEW:
UNISTRUT
FRONT VIEW:
CONDUIT
SEAL
WELD
TANK OR
TANK
LEG SIDE
SEE NOTES 12 AND 13.SCALE: N.T.S.A
CONDUIT SUPPORT
SEE NOTES 9-10.
3"
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
C D
SCALE: N.T.S.
SCALE: N.T.S. SCALE: N.T.S.
F
SCALE: N.T.S.
#2/0 BARE TINNED
COPPER GROUND LOOP
CABLE TO GROUND ROD
"CADWELD" MOLD PART No.
GRC-182G WELD METAL No. 90
EXISTING POWER PANEL
125A MAIN BREAKER
1-PHASE, 3-WIRE
TYPE: 125A COPPER BUS
120 / 240V
LOCATED IN EXISTING MCC
LABEL
SMART VALVE RECEPT.
1,900 VA 1,900 VATOTAL: 3,800 VA
BREAKER SIZE
CKT.
CKT.
BREAKER SIZE
LO
AD
LO
AD
POLE
POLE LABEL
1. ALL UNDERGROUND ELECTRIC CONDUIT SHALL BE CONCRETE ENCASED
WITH STEEL REINFORCEMENT.
2. ABOVEGROUND CONDUIT SHALL BE RIGID GALVANIZED STEEL.
3. ALL ENCLOSURES AND DISCONNECTS MUST BE PAD-LOCKABLE.
4. ALL MOUNTING HARDWARE AND STRUT SHALL BE 316 STAINLESS STEEL.
5. RACK STRUTS NEED TO BE 1-1/2" MINIMUM 316 STAINLESS STEEL AND BE
MOUNTED ON 4" GALVANIZED STEEL PIPE. PROVIDE APPROPRIATELY
SIZED CAPS FOR ALL SUPPORT PIPES.
6. THERE SHALL BE 6" MINIMUM SPACING BETWEEN EQUIPMENT MOUNTED
ON THE RACK.
7. ELECTRICAL RACK SHALL HAVE SUPPORT COLUMNS EVERY FIVE FEET.
8. SPARE CONDUITS AS SHOWN ON CABLE AND CONDUIT SCHEDULE SHALL
BE CAPPED 6" ABOVE SLAB OR GRADE WITH PULL STRING BELOW RACK.
9. ALL RECEPTACLES USED ON PROJECT MUST BE WEATHER PROOF GFCI
TYPE.
10. SEPARATE ANALOG SIGNAL CABLE BY PERMANENT BARRIER OR LISTED
DIVIDER FROM OTHER POWER CIRCUITS AS PER NEC ART. 800.133.
11. HEAT TRACE AND INSULATE PRESSURE TRANSMITTER AND PROCESS
PIPING . REFER TO CIVIL SHEETS FOR PIPING INSTALLATION AND
REQUIREMENTS.
12. ALL PANELS AND WIRING GUTTERS TO BE NEMA 4X ALUMINUM UNLESS
NOTED OTHERWISE.
13. ALL INSTRUMENT SIGNAL CABLE (SHIELDED CABLE) SHALL BE
CONTINUOUS WITHOUT SPLICES.
14. PRESSURE TRANSMITTER ENCLOSURE TO BE 24"X24"X10" MIN NEMA 4X
SS HINGED ENCLOSURE WITH BACK PLATE QUARTER TURN QUICK
RELEASE LATCHES AND PAD LOCKING PROVISIONS.
15. REFER TO CP SHEETS FOR CATHODIC PROTECTION CONTROLLER
JUNCTION BOX (CP5 SHEET XX.)
16. ALL CONDUITS FORM EQUIPMENT TO WIRING GUTTER SHALL BE 1"
UNLESS OTHERWISE NOTED.
17. IF NO EXISTING GROUND GRID IS FOUND, THEN CONTRACTOR SHALL AT
NO ADDITIONAL COST FURNISH AND INSTALL ONE GROUND ROD PER
CONNECTION PER SHEET E-5.
18. NEW 20A, 1P BREAKER SHALL BE ADDED TO THE EXISTING POWER
PANEL TO SERVE THE NEW CATHODIC PROTECTION PANEL AT THE NEW
EST ELECTRICAL RACK.
19. NEW 20A, 1P BREAKER SHALL BE ADDED TO THE EXISTING POWER
PANEL TO SERVE THE NEW HEAT TRACE CONTROL PANEL AT THE NEW
EST ELECTRICAL RACK.
20. NEW 20A, 1P BREAKER SHALL BE ADDED TO THE EXISTING POWER
PANEL TO SERVE THE NEW RECEPTACLE AT THE NEW EST ELECTRICAL
RACK.
21. EACH CIRCUIT SHALL HAVE SEPARATE HOT, NEUTRAL, GROUND WIRES.
DO NOT SHARE NEUTRAL GROUND WIRE FROM OTHER CIRCUITS.
22. LOAD VALUES REFLECT ONLY THE ADDED LOAD AS PART OF THIS
PROJECT.
SCALE: N.T.S.
EST ELECTRICAL RACK
A
SEE NOTE 14.
PT
JB
SENSING LINE
FOR
TRANSMITTER.
SEE NOTE 11.
1-2" CONDUIT
TO PUMP
BUILDING
TY
P)
12"
(TYP)
FLEX
CONDUIT
HEAT
TRACE
PANEL
2-1" CONDUITS
TO TANK TOP
FOR ANODE &
CATHODE
WIRES1-1" CONDUIT
SENSING LINE
TAP
ISOLATION
VALVE (TYP)
1" CONDUIT
TO POWER
PANEL IN
PUMP
BUILDING
MCC
THERMOSTAT
DUPLEX GFCI/WP
RECEPTACLE AND
WEATHER PROOF
ENCLOSURE
R
EF
ER
T O
ST
R
U C
TU
R
AL
D
R
AW
IN
G
S
1-5/8" MIN.
316 STAINLESS
STEEL STRUT
(TYPICAL)
2" GALVANIZED
PIPE WITH CAP
(TYPICAL)
HEAT TRACE
JUNCTION BOX
FOR SENSING LINE
PVC SLEEVES
CONNECT TO
EXISTING
GROUND GRID
SEE NOTE 17.
CONNECTION TO
GROUND GRID
#2/0 COPPER
(TYPICAL)
SPARE?SPARE
WELL CONTROL PANEL
1CL2 ROOM RECEPT.
WIRING GUTTER
SEE NOTE 10.
SPARE?
AIR COMPRESSOR
CALIBRATION PORT (TYP.)
1-1" CONDUIT
2-#12 W/#12GND
NEW RTU PANEL
GENERAL NOTES:
AIR CONDITIONER
CATHODIC
PROTECTION
CONTROLLER
JBOX
2727 N. St. Mary's St.
San Antonio, TX 78212 Fax No. 210-658-9805
Tel No. 210-658-7250
ELECTRICAL POWER SYSTEMS
DESIGN AND TESTING
GRUBB ENGINEERING, INC.
TBPE FIRM REGISTRATION NO. 3904
EXTERIOR LIGHTS
1 SPARE?PHOSPHATE PUMP CONTROLS
1INTERIOR LIGHTS
15 CHLORINE ROOM
CONTROL ROOM
CHLORINE BOOSTER PUMP
SPARE?RECEPTACLES
WIR
E
WIR
E
SEE NOTE 21. (TYP.)
- TERMINAL POINT IN HEAT TRACE JUNCTION BOX. DARK SIDE
INDICATES CONNECTIONS INTERNAL TO JUNCTION BOX.
FR
O
M P
O W
ER
P
AN
EL
HTC
VA
C
GFP
HTT HTC
FU
EST PRESSURE
TRANSMITTER
PROCESS PIPING
HTC - HEAT TRACE CONTACTOR
HTT - HEAT TRACE THERMOSTAT
HEAT TRACE
THERMOSTAT
SET AT 40° F
JUMPERED OR SLUGGED FUSE BLOCK
HTC
FU
EST PRESSURE
TRANSMITTER
PROCESS PIPING AT
SENSING LINE TAP
HTC
FU
EST PRESSURE
GAUGE
PROCESS PIPING
CABINET NAMEPLATE
TE
R
M
IN
AL
B
LO
C
K
R
EL
AY
S
AN
D
C O
N
TA
C
TO
R
THERMOSTAT
HEAT TRACE
CABINET
SEE NOTE 11.
28271
20 1
1 SPACESPACE
SPACEEST HEAT TRACE CONTROL PANEL
SPARE?
HEATER NO. 2
HEATER NO. 1
2#10, 1#12 GND 1300 VAEST CATHODIC PROTECTIONSEE NOTE 18.
SEE NOTE 19.
20 EST ELECTRICAL RACK RECEPT.1900 VA SEE NOTE 20.1
600 VA
SEE NOTE 22.
2#10, 1#12 GND
2#10, 1#12 GND
1" SPARE
CONDUIT TO
PUMP
BUILDING
SCALE: N.T.S.
EXISTING 120/240V POWER PANEL
B
SCALE: N.T.S.
EST HEAT TRACE CONTROLS
C SCALE: N.T.S.
HEAT TRACE PANEL
D
15720 Park Row, Suite 500
Houston, TX 77084
Tel. (713) 568-9067, Fax (713) 568-9068
Firm No. F-9154
V&A Project Number: 21-0176
Tel. (713) 568-9067, Fax (713) 568-9068
Tel. (713) 568-9067, Fax (713) 568-9068
Tel. (713) 568-9067, Fax (713) 568-9068
| Sheets and Views |
| 3 SITE PLAN |
File details come from the government source that posted it. Updated .