ESBD_405629_1743119062341_Drawing.pdf
PDF 14 MB Posted
- Attached to
- Stiles Unit Bldg 8 - Install HVAC
- Solicitation number
- 696-FD-25-P014
- Issued by
- Texas
About this file
This is a comprehensive set of construction documents for an HVAC installation project for the Texas Department of Criminal Justice (TDCJ) at the Stiles Unit in Beaumont, Texas. The project involves installing new HVAC systems in eight buildings, including replacing air handling units (AHUs), chillers, pumps, and associated mechanical, electrical, and plumbing infrastructure. The project is identified with MWR #04923007 and is dated November 8, 2024, with Jacobs Engineering Group serving as the engineering firm. The documents include detailed architectural, structural, mechanical, electrical, and plumbing plans, schedules, and specifications for the renovation.
The project involves significant equipment upgrades, including three new air handling units (AHU-1, AHU-2, AHU-3), two chillers (CH-1, CH-2), a chilled water pump skid, and associated support systems. The total project appears to involve approximately 13,500 CFM per AHU, with chillers rated at 100 tons each. The installation will include variable frequency drives (VFDs), control systems, electrical infrastructure, and required modifications to existing building systems. The documents suggest a comprehensive approach to system replacement, including demolition of existing equipment, new piping and ductwork, electrical connections, and integration with existing building infrastructure at the Stiles Unit correctional facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FO
T A
X S
E
TA T
T H
E S
E
Texas Engineering Registration F−2966
Date:
Revision:
Description:
ENGINEER:OWNER:
08−NOV−2024
ISSUED−FOR−PROPOSAL
- ISSUED FOR PROPOSAL -
- NOVEMBER 08, 2024 -
TEXAS DEPARTMENT OF CRIMINAL JUSTICE
STILES UNIT - BEAUMONT, TX
INSTALL HVAC - 8 BLDG
MWR# 04923007
JACOBS ENGINEERING GROUP INC.
1999 BRYAN STREET, SUITE 3500
DALLAS, TEXAS 75201
CONTACT:
THOMAS KEITH MAYER, P.E.
PHONE: 214.583.8598
TEXAS DEPT. OF CRIMINAL JUSTICE
STILES UNIT - BEAUMONT, TX
CONTACT:
TIM KIERSZ, P.E.
PHONE: 936.437.7272
CIVIL
C-001
CIVIL OVERALL SITE PLAN W/ LAYDOWN AREA
CIVIL DETAILS
C-002 C-003
GENERAL CIVIL LEGEND 3
T D C J
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
IS
S
U E
D F
O R
D A
T E
D A
T E
P R
O
JE
C T
N A
M E
IN
S T
A
LL
H V
A C
B
LD
G
M W
R
E N
G
IN
E E
R
JA
C
O B
S F
-2
D A
T E
/0 8/
U N
IT
S T
IL
E
S
D R
A W
N B
Y
D
R E
IL
LY
S C
A
LE
A
S S
H O
W N
Texas Engineering Registration F-2966
IS
S
U E
D F
O R
P R
O P
O S
A L
/0
8/
SHEET OF
11/08/2024
G-001
DRAWING
INDEX
2 52
STILES UNIT
BEAUMONT, TEXAS
JEFFERSON COUNTY
UNIT LOCATION
29.9932'N 094.0503'W
MECHANICAL
32 M-001 MECHANICAL GENERAL NOTES AND ABBREVIATIONS
33 MD110 OVERALL MECHANICAL DEMO PLAN
34 M-110 OVERALL MECHANICAL PLAN
35 M-301 SECTIONS
36 M-401 3D VIEWS
37 M-501 DETAILS
38 M-502 DETAILS
39 M-503 DETAILS
40 M-504 DETAILS
41 M-601 SCHEDULES
42 M-602 SCHEDULES
43 M-701 CHILLED WATER FLOW DIAGRAM
44 M-800 MECHANICAL CONTROLS SYMBOLS AND ABBREVIATIONS
45 M-801 CONTROL DIAGRAMS
46 M-802 CONTROL DIAGRAMS
47 M-803 CONTROL DIAGRAMS
48 M-804 CONTROL DIAGRAMS
PLUMBING
49 P-001 PLUMBING ABBREVIATIONS, LEGENDS, AND NOTES
50 PD110 OVERALL PLUMBING DEMO PLAN
51 P-110 OVERALL PLUMBING PLAN
52 P-601 PLUMBING SCHEDULES
STRUCTURAL
6 S-001 ABBREVIATIONS, SYMBOLS AND LEGEND
7 S-002 GENERAL NOTES
8 S-003 GENERAL NOTES
9 S-010 STATEMENT OF SPECIAL INSPECTIONS
10 S-100 LEVEL 1 - FOUNDATION PLAN - OVERALL
11 S-101 LEVEL 3 - FRAMING PLAN - OVERALL
12 S-102 ROOF FRAMING PLAN - OVERALL
13 S-103 ENLARGED FOUNDATION PLAN
14 S-104 ENLARGED PLANS
15 S-105 ENLARGED PLANS
16 S-300 TYPICAL CONCRETE DETAILS
17 S-301 TYPICAL CONCRETE & STEEL DETAILS
ELECTRICAL
18 E-001 ABBREVIATIONS, GENERAL NOTES, & SYMBOLS
19 ED102 DEMOLITION POWER PLAN - BUILDING 8 - LEVEL 3
20 E-010 PARTIAL SITE PLAN
21 E-101 POWER/ GROUNDING PLAN - EXT. HVAC SYSTEM
22 E-102 POWER PLAN - BUILDING 8 - LEVEL 1
23 E-103 POWER PLAN - BUILDING 8 - LEVEL 3
24 E-104 POWER PLAN - BUILDING 8 - ROOF
25 E-301 ELEVATIONS
26 E-501 DETAILS
27 E-502 DETAILS
28 E-503 DETAILS
29 E-601 SINGLE LINE DIAGRAM
30 E-602 PANEL SCHEDULE
31 E-603 PANEL SCHEDULE
GENERAL
1 G-000 TDCJ COVER
2 G-001 DRAWING INDEX
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
IS
SU
ED
F
O R
D
AT
E
D
AT
E
PR
O
JE
C
T N
AM
E:
IN
ST
AL
L
H
VA
C
BL
D G
M W
R
: 0
EN
G
IN
EE
R : J
AC
O
BS
F
-2
D
AT
E:
1/
/2
U N
IT
: S
TI
LE
S
D R
AW
N
B Y:
A . M
O R
AL
ES
SC
AL
E:
N
/A
Texas Engineering Registration F-2966 SHEET OF
T D C J
CIVIL
GENERAL
LEGEND
IS
SU
ED
F
O R
P R
O
PO
SA
L
/0
8/
C-001 3 52
GENERAL NOTE:
1. THIS IS A STANDARD LEGEND SHEET.
THEREFORE, NOT ALL OF THE INFORMATION
SHOWN MAY BE USED ON THIS PROJECT.
DISCLAIMER:
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE TYPE AND
QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR MANUFACTURER NAMES SHALL BE
INTERPRETED TO INCLUDE THE LANGUAGE “OR A/E APPROVED EQUAL”. ANY BRAND OR
MANUFACTURER MEETING SPECIFICATIONS WILL BE CONSIDERED, IRRESPECTIVE OF THE LANGUAGE “OR A/E APPROVED EQUAL” APPEARING IN CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
SOURCE OF TOPOGRAPHY SHOWN ON THE CIVIL PLANS ARE BASE MAPS PROVIDED BY JACOBS SERVICES.
ADDITIONAL MAPPING HAS BEEN ADDED FROM AS-BUILT DATA. EXISTING CONDITIONS MAY VARY FROM THOSE SHOWN ON THESE PLANS. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND ADJUST WORK PLAN ACCORDINGLY PRIOR TO
BEGINNING CONSTRUCTION.
EXISTING TOPOGRAPHY, STRUCTURES, AND SITE FEATURES ARE SHOWN SCREENED AND/OR LIGHT-LINED.
NEW FINISH GRADE, STRUCTURES, AND SITE FEATURES ARE SHOWN HEAVY-LINED.
HORIZONTAL DATUM: BEARINGS ARE BASED ON THE TEXAS STATE PLANE COORDINATE SYSTEM, CENTRAL ZONE (NAD 83). ALL DISTANCES SHOWN HEREON ARE SURFACE DISTANCES AND MAY BE BROUGHT TO GRID BY APPLYING THE FOLLOWING SCALE
FACTOR: 1.00017
VERTICAL DATUM: NAVD 88.
MAINTAIN, RELOCATE, OR REPLACE EXISTING SURVEY MONUMENTS, CONTROL POINTS, AND STAKES WHICH ARE DISTURBED OR DESTROYED. PERFORM THE WORK TO PRODUCE THE SAME LEVEL OF ACCURACY AS THE ORIGINAL
MONUMENT(S) IN A TIMELY MANNER, AND AT THE CONTRACTOR'S EXPENSE.
STAGING AREA SHALL BE FOR CONTRACTOR'S EMPLOYEE PARKING, CONTRACTOR'S TRAILERS AND
ON-SITE STORAGE OF MATERIALS.
PROVIDE TEMPORARY FENCING AS NECESSARY TO MAINTAIN SECURITY AT ALL TIMES.
SLOPE UNIFORMLY BETWEEN CONTOURS.
ALL DISTURBED AREAS SHALL BE RESTORED PER SPECIFICATION 32 90 00.
CONTRACTOR SHALL BE RESPONSIBLE FOR IMPLEMENTING AND MAINTAINING EROSION CONTROL DEVICES DURING
CONSTRUCTION.
CONTRACTOR SHALL TAKE ALL OTHER MEASURES TO POSITIVELY PRECLUDE EROSION MATERIALS FROM LEAVING
THE SITE. CONTRACTOR TO SUBMIT EROSION CONTROL PLAN.
EXISTING UNDERGROUND UTILITIES OBTAINED FROM AS-BUILTS AND FROM FIELD SURVEY.
CONTRACTOR SHALL FIELD VERIFY DEPTH AND LOCATION PRIOR TO EXCAVATION.
PROTECT ALL EXISTING UTILITIES DURING CONSTRUCTION.
FOR PIPING IDENTIFICATION, SEE DRAWING M-110.
EXISTING UTILITIES AND EQUIPMENT ARE SHOWN SCREENED AND/OR LIGHT-LINED.
NEW EQUIPMENT ARE SHOWN HEAVY-LINED.
UNLESS OTHERWISE SHOWN ALL PIPING SHALL HAVE A MINIMUM OF 4' COVER.
FOR TRENCHING AND BACKFILL, SEE .
MINIMUM ALLOWABLE CLEARANCE BETWEEN PIPES AT CROSSINGS SHALL BE 3" .
CONTROLLED DENSITY FILL SUPPORT IS REQUIRED AS SHOWN ON.
EQUIPMENT PAD ENCLOSURE FENCING, AS SHOWN ON .
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
GENERAL SITE NOTES:
C-003
C-003
C-003
PROJECT COORDINATION
1. FOR POWER AND OTHER UTILITY INTERCONNECTION AND COORDINATION, CONTACT OWNER’S STILES UNIT MAINTENANCE
SUPERVISOR.
2. WORK SEQUENCING/CONSTRAINTS
a. CONTRACTOR WILL NOT BE ALLOWED TO PERFORM WORK IN AREAS OUTSIDE THE VISIBILITY LIMITS OF A SINGLE SECURITY ESCORT. CONTRACTOR SHALL NOT SCHEDULE WORK THAT REQUIRES ITS CREWS TO BE IN TWO OR MORE PLACES THAT
CANNOT BE VISUALLY MONITORED AT THE SAME TIME BY A SINGLE SECURITY ESCORT.
b. CONTINUOUS OPERATION OF OWNER’S FACILITIES IS OF CRITICAL IMPORTANCE. SCHEDULE AND CONDUCT ACTIVITIES TO ENABLE EXISTING FACILITIES TO OPERATE CONTINUOUSLY, UNLESS OTHERWISE SPECIFIED. DO NOT PROCEED WITH WORK AFFECTING A FACILITY’S OPERATION WITHOUT OBTAINING OWNER’S PA AND ENGINEER’S ADVANCE APPROVAL OF THE NEED
FOR AND DURATION OF SUCH WORK.
3. AFTER EFFECTIVE DATE OF THE AGREEMENT AND BEFORE WORK AT SITE IS STARTED, AND AGAIN UPON ISSUANCE OF START UP, TAKE A MINIMUM OF 40 PHOTOGRAPHS OF SITE AND PROPERTY ADJACENT TO PERIMETER OF SITE.
CIVIL LEGEND
SPOT ELEVATION
CONTOUR LINE
DRAINAGEWAY OR DITCH
157.7
SIGN
MANHOLE
POST OR GUARD POST
UTILITY POLE
CENTER LINE, BUILDING, ROAD, ETC.
STRUCTURE, BUILDING OR FACILITY
LOCATION POINT - COORDINATES
N 1000.00 E 1000.00
LIGHT POLE
GUY ANCHOR
TREE
BRUSH/TREE LINE
FIRE HYDRANT
STRUCTURE, BUILDING OR FACILITYOR
ASPHALT CONCRETE PAVEMENT
GRAVEL SURFACING
OR
DEMOLITION
GUARD RAIL
WIRE FENCE
CHAIN LINK FENCE
CULVERT
CATCH BASIN OR INLET
ELECTRICAL MANHOLE
ELECTRIC HANDHOLE
BENCH MARK
PROPERTY LINE
STAGING OR WORK AREA LIMITS
AGGREGATE BASE COURSE PAVING
CURB
CURB AND GUTTER
SINGLE SWING GATE
DOUBLE SWING GATE
SLIDING GATE
ARCHITECTURAL FENCE
PROPOSEDEXISTING
H
E
BM
WATER LINEW
CONCRETE
11/08/2024
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS
W
W
W
W
17'
5'
5'
10'
N:13940582.52 E:3534167.41
N:13940610.45 E:3534204.12
N:13940561.27 E:3534178.57
N:13940565.26 E:3534199.07
N:13940555.96 E:3534181.36
N:13940525.00 E:3534109.52
N:13940546.25 E:3534098.36
6' 5'
62.5'
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS
CHAIN LINK
FENCE
CONCRETE
EQUIPMENT PAD, SEE
STRUCTURAL PLANS.
TOP OF PAD = 21.00
FG = 20.00, TYP.
IS
SU
ED
F
O R
P R
O
PO
SA
L
/0
8/
C-002 4 52
LIMITS OF
CONSTRUCTION
TEMPORARY
GENERATOR
LOCATION
ACCESS GATE
C-003
C-003
WATER SUPPLY LINE TO
5' FROM BUILDING, SEE
PLUMBING PLANS
C-003
NORTH FACILITY
ENTRANCE
LAYDOWN AREA
1 OVERALL SITE PLAN
1" = 20'
2 CONTRACTOR LAYDOWN AREA
1" = 40'
NOTES:
1. MAINTAIN REQUIRED CLEARANCES FROM DOMESTIC WATERLINE.
CIVIL
OVERALL
SITE PLAN
W/ LAYDOWN
AREA
MAINTENANCE
PARKING AREA
TCI TO PROVIDE
FENCING AND GATE
CONTRACTOR TO FIELD
LOCATE DOMESTIC WATER
LINE CONNECTION TO
EXISTING PROVISION
CONTRACTOR TO
FIELD LOCATE
DOMESTIC WATER
LINE CONNECTION
TO PUMP SKID
10 20 4051520
SCALE: 1" = 20'
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
IS
SU
ED
F
O R
D
AT
E
D
AT
E
GRAPHIC SCALE
NORTH
PLAN
PR
O
JE
C
T N
AM
E:
IN
ST
AL
L
H
VA
C
BL
D G
M W
R
: 0
EN
G
IN
EE
R : J
AC
O
BS
F
-2
D
AT
E:
1/
/2
U N
IT
: S
TI
LE
S
D R
AW
N
B Y:
A . M
O R
AL
ES
SC
AL
E:
A
S
SH
O W
N
KEYPLAN
NOTE:
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE TYPE
AND QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR MANUFACTURER NAMES
SHALL BE INTERPRETED TO INCLUDE THE LANGUAGE “OR A/E APPROVED EQUAL ”. ANY
BRAND OR MANUFACTURER MEETING SPECIFICATIONS WILL BE CONSIDERED,
IRRESPECTIVE OF THE LANGUAGE “OR A/E APPROVED EQUAL ” APPEARING IN
CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
Texas Engineering Registration F-2966 SHEET OF
T D C J
CHAIN LINK
FENCE 108 LF CHAIN LINK
FENCE 35 LF
CHAIN LINK
FENCE 5 LF
CHAIN LINK
FENCE 77 LF
CHAIN LINK
FENCE 9 LF
CHAIN LINK
FENCE 29 LF
STEP, SEE STRUCTURAL
SHEET S-301/DETAIL 7
STEP, SEE STRUCTURAL
SHEET S-301/DETAIL 7
11/08/2024
NORTH
TRUE
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
IS
SU
ED
F
O R
D
AT
E
D
AT
E
PR
O
JE
C
T N
AM
E:
IN
ST
AL
L
H
VA
C
BL
D G
M W
R
: 0
EN
G
IN
EE
R : J
AC
O
BS
F
-2
D
AT
E:
1/
/2
U N
IT
: S
TI
LE
S
D R
AW
N
B Y:
A . M
O R
AL
ES
SC
AL
E:
N
/A
Texas Engineering Registration F-2966 SHEET OF
T D C J
DETAILS
CIVIL
1 20' ACCESS GATE
NTS
20'
DOUBLE-HUNG SWING
GATE WITH TRAVELING
TAUT BARBED WIRE (12 - 1/2 GA.)
3/8" GALV. THREADED ROD
WITH GALV, TURNBUCKLE
GATE SUPPORT
POST 4" GALV. SCH. 40
2" GALV. PIPE GATE FRAME
METAL BANDS -
2" JAMIESON #210103 XHT-3
OR APPROVED EQUAL
1/4" x 3/4" GALV. TENSION BAR (TYP)
1-3/8" DROP ROD ASSEMBLY
WITH PADLOCK -
(PADLOCK FURNISHED BY TDCJ)
NOTE:
HEAVY DUTY HINGES WELDED
TO FRAME POSTS AND GATE
FRAMES - USE 180° HINGE
JAMIESON #138093 180-93
OR APPROVED EQUAL
9 GA. CHAIN
LINK FABRIC
IS
SU
ED
F
O R
P R
O
PO
SA
L
/0
8/
8' -0
'-0
" TENSION BAR BANDS
12" C-C TYP
END RAIL CLAMP
C-003 5 52
DISCLAIMER:
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE TYPE AND
QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR MANUFACTURER NAMES SHALL BE
INTERPRETED TO INCLUDE THE LANGUAGE “OR A/E APPROVED EQUAL”. ANY BRAND OR
MANUFACTURER MEETING SPECIFICATIONS WILL BE CONSIDERED, IRRESPECTIVE OF THE LANGUAGE “OR A/E APPROVED EQUAL” APPEARING IN CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
MIN WIDTH
PIPE ZONE
DEPTH OF COVER MIN 48"
(REFER TO PLUMBING DWGS)
TRENCH
BACKFILL
ABOVE
PIPE ZONE
NEW SURFACING,
OR SURFACE
RESTORATION,
SEE PLANS
12" MIN
PIPE OUTSIDE
DIAMETER
PIPE BEDDING
MATERIAL
TRENCH
STABILIZATION
WHERE REQD
MARKING TAPE AS
SPECIFIED
CONDUIT (REFER TO ELECTRICAL
DWGS FOR QUANTITY AND
PLACEMENT OF CONDUITS)
12" MIN
9" 9"
1.
2.
3.
4.
12" TYP
CLSM SUPPORT IS REQUIRED:
12" TYP
NOTES:
PLAN SECTION
WHEN BOTH PIPELINES ARE NEW AND CLEARANCE BETWEEN THEM IS LESS THAN 12".
WHEN A NEW PIPELINE IS CROSSING OVER AN EXISTING PIPELINE AND THE
CLEARANCE BETWEEN THEM IS LESS THAN 12".
AT ALL PIPE CROSSINGS WHERE A NEW PIPELINE IS CROSSING UNDER AN
EXISTING PIPELINE.
REFER TO SPECIFICATION SECTION 31 22 00 FOR CLSM REQUIREMENTS.
CLSM
MINIMUM ALLOWABLE
CLEARANCE IS 3"
CONTROLLED
LOW-STRENGTH
MATERIAL (CLSM)
2 CHAIN LINK FENCE
NTS 3 TYPICAL TRENCH
NTS
4 TRENCH PIPE CROSSING
NTS
NEW 4" GALV.
CORNER GATE POST
PROVIDE POST CAP (TYP)
11/08/2024
SLOPE
SPAN
STRUCTURAL LEGEND
CAST-IN-PLACE
CONCRETE
THE FOLLOWING SYMBOLS ARE USED TO REPRESENT THE MATERIALS SHOWN ON
THE STRUCTURAL DRAWINGS. REFER TO SPECIFICATIONS AND GENERAL NOTES
FOR MATERIAL QUALITIES REQUIRED
ELEVATION OF WALL
OR FRAME
SECTION CUTS
ENLARGED PLAN/DETAIL
REFERENCE
G
F
E
D
P
O
N
W
V
U
C
B
ABBREVIATIONS
A
M
L
K
J
I
T
S
H
R
X
(ALL ABBREVIATIONS/SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
A/E
AB
ACI
ADDL
ADJ
AFF
AISC
APPROX
ARCH
ASCE
ASTM
ARCHITECT/ENGINEER
ANCHOR BOLT, ANCHOR ROD
AMERICAN CONCRETE INSTITUTE
ADDITIONAL
ADJACENT
ABOVE FINISH FLOOR
AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
APPROXIMATE (-LY)
ARCHITECTURAL
AMERICAN SOCIETY OF CIVIL ENGINEERS
AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BB
BC
BL
BACK TO BACK
BOTTOM CHORD
BASE LINE
BUILDING
BEAM
BOTTOM
BASE PLATE
BEARING
BOTH SIDES
BASEMENT
BEVELED
BOTH WAYS
C
CG
CIP
CJ
CL
CLR
CMU
COE
COL
CONC
CONST
CONT
CONX
COR
COMPRESSION, CHANNEL SECTION
CENTER OF GRAVITY
CAST-IN-PLACE CONCRETE
CONSTRUCTION JOINT, CONTROL JOINT
CENTERLINE
CLEAR, CLEARANCE
CONCRETE MASONRY UNIT
CORPS OF ENGINEER'S
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS OR CONTINUED
CONNECTION
CONTRACTING OFFICER'S REPRESENTATIVE
D
DETL
DIA
DIAG
DIM
DL
DN
DP
DWG
DWL
DEPTH
DETAIL
DIAMETER
DIAGONAL
DIMENSION
DEAD LOAD
DOWN
DAMP PROOFING
DRAWING (-S)
DOWEL
E
EA
EF
EJ
ELEC
ELEV, EL
EQ
EQUIP
EW
EXIST
EXP
EXT
EAST
EACH
EACH FACE
EXPANSION JOINT
ELECTRICAL
ELEVATION
EQUAL
EQUIPMENT
EACH WAY
EXISTING
EXPANSION
EXTERIOR
FAB
FD
FDN
FF
FIN
FLR
FS
FT
FTG
FABRICATION
FLOOR DRAIN
FOUNDATION
FINISH FLOOR
FINISH (-ED)
FLOOR
FAR SIDE
FOOT/FEET
FOOTING
XFMR TRANSFORMER
GA
GALV
GB
GAGE OR GAUGE
GALVANIZED
GRADE BEAM
HORIZ
HP
HS
HSS
HT
HORIZONTAL
HIGH POINT
HEADED STUD
HOLLOW STRUCTURAL SECTION
HEIGHT
ID
IN
INT
INSIDE DIAMETER
INCH (-ES)
INTERIOR
JST
JT
JOIST
JOINT
K
KO
KIPS (1000 LBS)
KNOCKOUT
L
LB, #
LD
LG
LH
LL
LLH
LLV
LONG
LP
LW
LWC
ANGLE SHAPE
POUND
DEVELOPMENT LENGTH
LIGHT-GAGE, LIGHT-GAUGE
LEFT HAND
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LOW POINT
LONG WAY
LIGHTWEIGHT CONCRETE
MAS
MATL
MAX
MC
MECH
MEP
MEZZ
MFR
MID
MIN
MISC
MS
MT
MTL
MASONRY
MATERIAL
MAXIMUM
MISCELLANEOUS CHANNEL SHAPE
MECHANICAL
MECHANICAL, ELECTRICAL, PLUMBING
MEZZANINE
MANUFACTURE (-R)
MIDDLE
MINIMUM
MISCELLANEOUS
MIDDLE STRIP
STRUCTURAL TEE CUT FROM
NON-STANDARD I-SHAPE
METAL
N/A
NF
NIC
NO
NOM
NS
NTS
NOT APPLICABLE
NEAR FACE
NOT IN CONTRACT
NUMBER
NOMINAL
NEAR SIDE
NOT TO SCALE
OA
OC
OD
OF
OPNG
OPP
OPP HND
OPT
OVS
OVERALL
ON CENTER
OUTSIDE DIAMETER
OUTSIDE FACE
OPENING (-S)
OPPOSITE
OPPOSITE HAND
OPTIONAL
OVERSIZE
PC
PERP
PL
PLUMB
PREFAB
PRELIM
PRMLD
PROJ
PSTG
P/T
PT
PVC
PVT
PRECAST CONCRETE
PERPENDICULAR
PLATE GIRDER
PLATE
PLUMBING
PREFABRICATED
PRELIMINARY
PREMOLDED
PROJECTION
PRESTRESSED GIRDER
POST-TENSION (-ED, -ING)
POINT
POLYVINYL CHLORIDE
PAVEMENT
R
RAD
RD
RE:
REINF
REM
REQD
REV
RH
RJ
RND
RO
RW
RIGHT, RISER
RADIUS
ROOF DRAIN
REFER TO
REINFORCING (-ED,-MENT)
REMAINDER
REQUIRED
REVISION
RIGHT HAND
RUSTICATION JOINT
ROUND
ROUGH OPENING
RETAINING WALL
S
SC
SCHED
SDI
SECT
SHT
SIM
SJ
SJI
SL
SPA
SPEC
SQ
SS
STD
STIFF
STIR
STL
STRUCT
SW
SYM
SOUTH, STANDARD SHAPE
SHEAR CONNECTORS, SLIP CRITICAL
SCHEDULE(D)
STEEL DECK INSTITUTE
SECTION
SHEET
SIMILAR
SAW JOINT
STEEL JOIST INSTITUTE
SLOPE
SPACE
SPECIFICATION(S)
SQUARE
STAINLESS STEEL
STANDARD
STIFFENER
STIRRUP
STEEL
STRUCTURE, STRUCTURAL
SHEAR WALL
SYMMETRICAL
UNLESS NOTED OTHERWISEUNO
VERT VERTICAL
W w/ w/o
WP
WPJ
WT
WWF
WWM
WEST, WIDTH, WIDE FLANGE
WITH
WITHOUT
WORK POINT
WEAKENED PLANE JOINT
WEIGHT, STRUCTURAL TEE CUT
FROM WIDE FLANGE BEAM
WELDED WIRE FABRIC
WELDED WIRE MESH
T TOP, TENSION
T/ TOP OF
T&B TOP & BOTTOM
TEMP TEMPERATURE
THRD THREADED
THK THICKNESS
TOS TOP OF STEEL
TRD TREAD (-S)
TRNV TRANSVERSE
TW TILT WALL
TYP TYPICAL
BLDG
BM
BOT
BP
BRG
BS
BSMT
BVL
BW
PRECAST
CONCRETE
G5
S-6050
G5
S-6050
G5
S-6050
PG
ROCKEARTH
NON-SHRINK
GROUT
CMU STRUCTURAL STEEL
IN CROSS SECTION
EXISTING
CONCRETE
MATERIAL GRAPHIC SYMBOLS
SHEET SYMBOLS
UNLESS OTHERWISE NOTEDUON
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BUCKLING-RESTRAINED BRACEBRB
CFMF COLD-FORMED METAL FRAMING
CJP COMPLETE JOINT PENETRATION
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CS COLUMN STRIP
DEG DEGREES
DEMO DEMOLISH, DEMOLITION
EMBED EMBEDMENT
EOR ENGINEER OF RECORD
FRP FIBER REINFORCED POLYMER
FP FIRE PROTECTION
IE INVERT ELEVATION
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
KN KEYNOTE
OH OVERHEAD, OPPOSITE HAND
POUNDS PER CUBIC FOOTPCF
PRE-ENGINEERED METAL BUILDINGPEMB
PREMOLDED JOINT FILLERPJF
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RTU ROOFTOP UNIT
TF TOP OF STEPPED FOOTING
THRU THROUGH
UNDERWRITERS LABORATORIESUL
VIF VERIFY IN FIELD
WWR WELDED WIRE REINFORCING
OSB ORIENTED STRAND BOARD
ELEVATION POINT (TOP OF
ELEMENT INDICATED)
SURFACE - SLOPE (2) WAYS
TOP OF CONCRETE ELEVATION
SURFACE - SLOPE DOWN
SURFACE - STEPPED
SURFACE - SLOPE UP
WORKPOINT
TOP OF STEEL ELEVATION
WP
T/WALL
SLOPE INDICATOR
EL.= X'-XX"
T/STEEL
EL.= X'-XX"
T/CONC
EL.= X'-XX"
( +3" )
COLUMN PASSING
THRU THIS LEVEL
(DIRECTION OF SPAN)
TOP OF STEEL ± DEVIATION
FROM TYPICAL
STRUCTURAL ARROW
X'-X"
TARGET ELEVATION
• TARGET ELEVATIONS
WITHOUT LEADERS INDICATE
LEVEL PLANES. AT SOME
SMALL LEVEL PLANES (SUCH
AS TOPS OF STEPPED
FOOTINGS) A COMPACT
NOTATION IS USED WHICH
HAS A LEADER AND NO
TARGET SYMBOL
• TARGET ELEVATIONS WITH
LEADERS INDICATE
ELEVATIONS OF WORK
POINTS FOR SLOPING
PLANES.
6#7EXAMPLE TOP BAR
DESIGNATIONS
#4@12
6#7EXAMPLE BOTTOM BAR
DESIGNATIONS
#4@12
BAR QUANTITY AND SIZE
BAR SIZE AND SPACING
BAR QUANTITY AND SIZE
BAR SIZE AND SPACING
RE: 1/S-301
DRAWING/DETAIL SHEET NUMBER
REFERENCED TO
DRAWING/DETAIL NUMBER
REFER TO
DRAWING/DETAIL REFERENCE KEY
W10X49
BPXX
PXX -1'-0"
FXX
(-5'-0")
STEEL COLUMN SECTION
CONCRETE PEDESTAL MARK
T/CONCRETE PEDESTAL EL
CONCRETE FOOTING MARK
T/CONCRETE FOOTING EL
W F
X X
CONCRETE WALL FOOTING MARK
T/CONCRETE WALL FOOTING EL
CONCRETE BEAM MARK
BXXX
CONCRETE COLUMN MARK
FXX
(-5'-0")
CONCRETE FOOTING MARK
T/CONCRETE FOOTING EL
BASE PLATE MARK
C W
X X
CONCRETE WALL MARK
TF (-3'-0")
TOP OF STEPPED FOOTING ELEVATION
C
XX
SHEET OF
T D C J
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
IS
S
U E
D F
O R
D A
T E
D A
T E
P R
O J E
C T
N A
M E
IN
S T
A L L H
V A
C
B
L D
G
M
R
E N
G
IN
E E
R
J A
C O
B S
F -2
D A
T E
/0
/2
U N
IT
S T
IL
E
S
D R
A W
N B
Y
G
P E
L A
G
IO
S C
A L E
A
S S
H O
W N
Texas Engineering Registration F-2966
NAVID NAZEMI
OF TEXASS
TATE
ALNOI
SS
E
F O
R P
ENG
IN
E E
R
NSEDECI
L 145373
IS
S
U E
D F
O R
P R
O P
O S
A L
/0
/2
11/08/2024
S-001
ABBREVIATIONS,
SYMBOLS AND
LEGEND
NOTE:
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE TYPE
AND QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR MANUFACTURER NAMES
SHALL BE INTERPRETED TO INCLUDE THE LANGUAGE “OR A/E APPROVED EQUAL”. ANY
BRAND OR MANUFACTURER MEETING SPECIFICATIONS WILL BE CONSIDERED,
IRRESPECTIVE OF THE LANGUAGE “OR A/E APPROVED EQUAL” APPEARING IN
CONJUNCTION WITH THE BRAND OR MANUFACTURER NAME.
1. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE.
THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES.
2. SPECIFICATIONS ARE PART OF THE CONSTRUCTION DOCUMENTS AND SHALL BE USED IN CONJUNCTION
WITH THE DRAWINGS.
3. THE CONTRACTOR IS RESPONSIBLE FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH
THE WORK THAT CONFORMS WITH THE REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEATH
ADMINISTRATION (OSHA) SAFETY AND HEALTH STANDARDS FOR THE CONSTRUCTION INDUSTRY.
4. CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON COMPLETED FRAMED FLOORS OR
ROOF. LOAD SHALL NOT EXCEED 80% OF THE DESIGN LIVE LOAD PER SQUARE FOOT.
5. DESIGN OF THE STRUCTURE HAS NOT INCORPORATED CONSIDERATION OF LOADINGS FROM
CONTRACTOR'S ERECTION CRANES OR EQUIPMENT. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING
ADEQUACY OF THE STRUCTURE AS CONSTRUCTED TO SUPPORT ALL TEMPORARY CONSTRUCTION
LOADINGS. CONTRACTOR SHALL SUBMIT CONSTRUCTION LOADING AND SHORING PLAN FOR REVIEW BY
THE ENGINEER OF RECORD PRIOR TO COMMENCING WORK.
6. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH STANDARDS SHALL
BE THE LATEST EDITION AND/OR ADDENDUM.
7. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, ELECTRICAL
AND PLUMBING WITH APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO
CONSTRUCTION. DO NOT PENETRATE OR CUT ANY STRUCTURAL ELEMENTS (BEAM, COLUMNS, WALLS, SLABS, STEEL DECKS, ETC.) WITHOUT PRIOR WRITTEN APPROVAL FROM ENGINEER OF RECORD.
8. ALL DIMENSIONS, ELEVATIONS AND ASSUMED EXISTING CONDITIONS ARE TO BE VERIFIED IN THE FIELD.
SUCH VERIFICATION IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ARCHITECT AND ENGINEER OF RECORD OF ANY DISCREPANCIES OR
CONFLICTS.
9. DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS.
10. OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHANGES NECESSARY IF AN OPTION IS SELECTED, AND THE CONTRACTOR SHALL COORDINATE ALL
DETAILS.
11. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND TYPICAL-DETAILS. TYPICAL-DETAILS ARE INDICATED AS TYPICAL-DETAILS IN THE DETAIL TITLE BLOCK. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK
ON THE PROJECT.
12. TYPICAL-DETAILS ARE NOT CUT ON DRAWINGS, BUT APPLY UNLESS NOTED OTHERWISE.
13. WHERE ANY DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN. WHERE FURTHER CLARIFICATION IS
REQUIRED, NOTIFY ENGINEER OF RECORD.
14. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF A QUALIFIED ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED. DELEGATE
ENGINEER'S RESPONSIBILITIES SHALL CONFORM TO THE PROJECT SPECIFICATIONS.
GENERAL NOTES
1. BUILDING AND DESIGN CODES (LATEST EDITION ADOPTED BY GOVERNING CODES UNLESS OTHERWISE
NOTED)
A. IBC (INTERNATIONAL BUILDING CODE) 2018 EDITION
B. ASCE 7 - 16 (MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES)
C. ACI 318 - 14 (BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE)
D. AISC 360 - 16 (SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS)
1. DESIGN LOADS
A. BUILDING RISK CATEGORY ---------------------------------------------------------------------- III
B. MINIMUM DESIGN LIVE LOADS: (FOLLOWING LOADS ARE TAKEN FROM EXISTING BUILDING
DRAWINGS, REFER TO #049 STILES UNIT BEAUMONT, TX, S3-1 DATED OCT 29TH, 1990.)
a. MECHANICAL AREA --------------------------------------------------------------------------- 150 PSF
b. PARTITION ALLOWANCE (IN ADDITION TO a) -------------------------------- 20 PSF
c. ROOF ---------------------------------------------------------------------------------------------- 20 PSF
d. MEP EQUIPMENT SPECIFIC DESIGN LOADS
• MEP EQUIPMENT SUPPORTED ON CONCRETE PAD --------------------- REFER TO S-010
• MEP EQUPMENT SUPPORTED ON THIRD FLOOR (AHU'S) -------------- REFER TO S-010
C. SNOW LOADS:
a. GROUND SNOW LOAD, Pg ---------------------------------------------------------------- 0 PSF
D. WIND LOADS:
a. MAIN FORCE-RESISTING SYSTEM
• BASIC DESIGN WIND SPEED, V (3-SECOND GUST, MPH) -------------- 148 PSF
• ALLOWABLE STRESS DESIGN WIND SPEED, VASD (MPH) -------------- 114.6 PSF
• WIND EXPOSURE --------------------------------------------------------------------- C
• INTERNAL PRESSURE COEFFICIENT, GCpi ---------------------------------- ±0.18
• BUILDING CLASSIFICATION ------------------------------------------------------- ENCLOSED
b. WIND LOADS ON EQUIPMENT (ULTIMATE) - CHILLERS
• 40 PSF LATERAL FORCE ACTING ON THE VERTICAL PROJECTED AREA OF THE EQUIPMENT
• 36 PSF VERTICAL UPLIFT FORCE ACTING ON THE HORIZONTAL PROJECTED AREA OF THE
EQUIPMENT
c. WIND LOADS ON EQUIPMENT (ULTIMATE) - GENERATORS
• 40 PSF LATERAL FORCE ACTING ON THE VERTICAL PROJECTED AREA OF THE EQUIPMENT
• 36 PSF VERTICAL UPLIFT FORCE ACTING ON THE HORIZONTAL PROJECTED AREA OF THE
EQUIPMENT
E. SEISMIC LOADS
a. SEISMIC IMPORTANCE FACTOR, Ie --------------------------------------------------- 1.25
b. SITE CLASS ----------------------------------------------------------------------------------- D
c. SEISMIC DESIGN CATEGORY ----------------------------------------------------------- B
d. SPECTRAL RESPONSE ACCELERATIONS
• SS = 0.077
• S1 = 0.045
• SDS = 0.082
• SD1 = 0.072
e. AHU ON THIRD FLOOR:
• SYSTEM TYPE - MECHANICAL AND ELECTRICAL COMPONENTS
• Fp = 0.04 Wp
• ap = 1.0
• Rp = 2.5
• Ω0 = 2.0
f. AIR COOLED CHILLER ON GRADE LEVEL:
• SYSTEM TYPE - NON-BUILDING STRUCTURES NOT SIMILAR TO BUILDINGS
• V = 0.061 Wp
• R = 1.25
• Ω0 = 2.0
• Cd = 2.5
DESIGN CRITERIA
1. THE GENERAL CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP DRAWINGS AND PRODUCT DATA FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS PRIOR TO SUBMISSION. ANY SHOP DRAWINGS OR PRODUCT DATA NOT REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR WILL BE RETURNED
WITHOUT REVIEW.
2. ANY SHOP DRAWING NOT CHECKED AND INITIALED BY THE SUPPLIER/DETAILER PRIOR TO SUBMITTING
FOR REVIEW WILL BE RETURNED WITHOUT REVIEW.
3. REPRODUCTION OF CONSTRUCTION DOCUMENTS FOR USE AS SHOP DRAWINGS (PAPER OR
ELECTRONIC) IS NOT PERMITTED. SHOP DRAWINGS SHALL NOT REPRODUCE CONSTRUCTION
DOCUMENT TITLE BLOCK INFORMATION REFERENCING PROJECT DESIGN ENTITIES OR PROFESSIONAL
SEAL.
SHOP DRAWING NOTES
1. DEMOLITION OF EXISTING STRUCTURE TO BE REMOVED SHALL BE PERFORMED BY THE CONTRACTOR
USING MEANS AND METHODS NECESSARY TO PREVENT DAMAGE TO THE EXISTING STRUCTURE,
FOUNDATIONS, UTILITIES, ETC.,TO REMAIN. DAMAGE TO THE EXISTING STRUCTURE TO REMAIN SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE USING METHODS REVIEWED BY THE REGISTERED DESIGN
PROFESSIONAL OF RECORD.
2. IF EXISTING CONDITIONS DIFFER FROM THOSE SHOWN IN THE CONTRACT DOCUMENTS, CONTACT
REGISTERED DESIGN PROFESSIONAL OF RECORD PRIOR TO PROCEEDING WITH WORK.
DEMOLITION NOTES
1. INFORMATION BY OTHERS SHOWN AS EXISTING WAS SUPPLIED BY THE OWNER. THE RECORD
DRAWINGS WERE PREPARED BY HDR, DATED OCT 29, 1990. REFERENCE NUMBER IS #049 STILES UNIT
BEAUMONT, TX, MWR 049B2879 PAGE 228.
2. EXISTING INFORMATION AND RECORD DRAWINGS PROVIDED BY OTHERS FOR USE IN DESIGN ARE ASSUMED TO BE ACCURATE. VERIFICATION OF ACTUAL CONDITIONS AND COMPARISON OF EXISTING DRAWINGS HAS BEEN PERFORMED TO THE EXTENT PRACTICAL PRIOR TO USE IN DESIGN. CONTRACTOR SHALL VERIFY ACCURACY WITH ACTUAL FIELD CONDITIONS, AND WHERE DISCREPANCIES ARE FOUND
NOTIFY OWNER AND ENGINEER OF RECORD PRIOR TO COMMENCING WORK.
EXISTING DRAWING NOTES
1. GEOTECHNICAL CONSULTANT: ETTL ENGINEERS & CONSULTANTS
2. FINAL GEOTECHNICAL REPORT: TDCJ STILES UNIT HVAC INSTALLATION PROJECT, ETTL JOB NO.
G 6282-249, DATED APRIL 08, 2024
3. MAT FOOTINGS SHALL BEAR ON COMPACTED, ENGINEERED FILL OR WHERE APPLICABLE ROCK. FOR FILL REQUIREMENTS, SEE BUILDING PAD PREPARATION NOTES. FOOTINGS ARE DESIGNED USING THE
FOLLOWING DESIGN CRITERIA
A. ALLOWABLE BEARING PRESSURE FOR MAT LARGER THAN 20'X12' --------------- 1600 PSF B. ALLOWABLE BEARING PRESSURE FOR 20'X12' MAT OR SMALLER ------------------- 1800 PSF
4. SHORE EXISTING IMPROVEMENTS TO PREVENT DAMAGE OR SUBSIDENCE DUE TO EXCAVATION OR EARTH WORK FOR THIS WORK. CONTRACTOR IS RESPONSIBLE FOR DESIGN OF ANY REQUIRED SHORING
OR UNDERPINNING.
5. MAT FOUNDATION MODULUS OF SUBGRADE REACTION IS 100 PCI.
6. NONBUILDING FOUNDATIONS BEARING ON A 12-INCH THICK FLEXIBLE BASE MATERIAL ARE DESIGNED FOR AN ALLOWABLE BEARING PRESSURE OF 1,600 PSF, AN ULTIMATE COEFFICIENT OF SLIDING FRICTION OF 0.5, AND A MODULUS OF SUGRADE REACTION (FOR A 1-FOOT BY 1-FOOT AREA) OF 100 PCI.
7. SLABS ON GRADE ARE DESIGNED WITH A MODULUS OF SUBGRADE REACTION OF 100 PCI.
8. PROTECT PIPES AND CONDUITS RUNNING THROUGH WALLS AND SLABS WITH 2 INCH EXPANSION MATERIAL. LOWER CONTINUOUS FOOTINGS AND GRADE BEAMS PERPENDICULAR TO PIPE RUNS TO ALLOW PIPES TO PASS ABOVE THE FOOTINGS OR THROUGH THE GRADE BEAMS. ALTERNATIVELY, PROVIDE A CONCRETE JACKET IF PIPES ARE LOW ENOUGH TO BE PLACED BELOW THE FOOTINGS AND
GRADE BEAMS. LOWER FOOTINGS AND GRADE BEAMS PARALLEL TO PIPE RUNS TO AVOID
SURCHARGEONTO ADJACENT TRENCH EXCAVATIONS.
9. DO NOT PLACE GRADE BEAMS OR SLABS AGAINST SUBGRADE CONTAINING FREE WATER, FROST, OR
ICE.
10. MAINTAIN PROPER SITE DRAINAGE DURING CONSTRUCTION TO ENSURE SURFACE RUNOFF AWAY FROM
STRUCTURES AND TO PREVENT PONDING OF SURFACE RUNOFF NEAR THE STRUCTURES.
11. KEEP OPEN EXCAVATIONS AROUND BUILDING PERIMETER DRY. BACKFILL AGAINST FOUNDATIONS AND GRADE BEAMS AS SOON AS PRACTICAL. PUMP WATER OUT OF OPEN EXCAVATIONS IF FLOODED PRIOR
TO BACKFILLING.
12. PROVIDE A DRILLING RIG CAPABLE OF DRILLING THE HOLES BASED ON THE BORING LOGS IN THE
PROVIDED GEOTECHNICAL REPORT.
FOUNDATION DESIGN NOTES
SUBGRADE PREPARATION NOTES
1. REMOVE THE SURFICIAL VEGETATION AND ORGANIC TOPSOIL. TREE ROOT ZONES (TYPICAL 3 TO 5 FEET
DEEP) AND ABANDONED UTILITIES SHOULD BE COMPLETELY REMOVED AND REPLACED BY SELECT FILL.
ANY AREAS DISTURBED BY SITE PREPARATION/DEMOLITION SHOULD BE UNDERCUT AND REPLACED WITH SELECT FILL. OVEREXCAVATION TO BE CARRIED OUT TO DEPTH OF MINIMUM 3' BELOW THE EXISTING GRADE. EXTEND THE OVER-EXCAVATION A MINIMUM OF 3 FEET BEYOND THE FOOTING LINES AND SHOULD TAPER UP TO FINISHED GRADE AT A 1:1 SLOPE. ONCE THE EXCAVATION DEPTH IS REACHED THE EXPOSED SUBGRADE SHOULD BE INSPECTED BY THE GEOTECHNICAL ENGINEER. THE GEOTECHNICAL ENGEINEER SHOULD DETERMINE THE ACTUAL DEPTH OF REMOVAL AT THE TIME OF CONSTRUCTION.
2. PROOF ROLL EXPOSED SOIL IN ACCORDANCE WITH ITEM 216 OF TXDOT, "STANDARD SPECIFICATION FOR CONSTRUCTION OF HIGHWAYS, STREETS AND BRIDGES" TO LOCATE ANY SOFT OR LOOSE AREAS.
3. SCARIFY THE EXPOSED SUBGRADE TO A DEPTH OF 12 INCHES, ADJUST THE MOISTURE CONTENT TO, AND MAINTAIN IT WITHIN A RANGE OF OPTIMUM TO OPTIMUM +4% AND RECOMPACT TO A DENSITY OF AT LEAST 95% OF THE MAXIMUM DENSITY DEFINED BY ASTM D 698 (STANDARD PROCTOR). MAINTAIN
SPECIFIED MOISTURE CONTENT UNTIL THE SUBGRADE IS COVERED WITH FILL OR SLAB.
4. PLACE SUBSEQUENT LIFTS OF SELECT FILL IN THIN, LOOSE LAYERS NOT EXCEEDING 9 INCHES IN THICKNESS TO THE DESIRED ROUGH GRADE AND COMPACT TO A MINIMUM OF 98% OF THE MAXIMUM DENSITY DEFINED BY ASTM D 698 (STANDARD PROCTOR). MAINTAIN MOISTURE WITHIN A RANGE OF OPTIMUM TO OPTIMUM +4% ((PERIODIC SPRINKLING MAY BE REQUIRED)). PLACE SELECT FILL TO
FINISHED SLAB SUBGRADE.
5. SELECT FILL SHALL CONSIST OF HOMOGENEOUS SOILS (I.E., NOT SAND WITH CLAY LUMPS) CLASSIFYING AS SC OR CL, FREE OF ORGANIC MATTER AND ROCKS LARGER THAN 3 INCHES IN DIAMETER AND POSSESSING AN ATTERBERG PLASTICITY INDEX (PI) OF 5 TO 20, WITH A LIQUID LIMIT OF 45 OR LESS AND A PERCENT PASSING THE #200 SIEVE BETWEEN 30 AND 75. PERMEABILITY SHOULD NOT EXCEED 1 X 10-5
CM/SEC AT IN-PLACE DENSITY (TESTING TO CONFIRM IS RECOMMENDED).
6. CONDUCT IN-PLACE FIELD DENSITY TESTS AT A RATE OF ONE TEST PER 3,000 SQUARE FEET OF LIFT AREA FOR EVERY LIFT WITH A MINIMUM OF 2 TESTS PER LIFT. DENSITY TESTING IS ESSENTIAL TO ASSURE THAT
THE SOIL BENEATH THE STRUCTURE IS PROPERLY PLACED.
1. CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301, "STANDARD SPECIFICATIONS
FOR STRUCTURAL CONCRETE" AND ACI 318, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE". REFERENCE PROJECT SPECIFICATION SECTION 03 30 00 - CAST-IN-PLACE CONCRETE FOR
ADDITIONAL INFORMATION.
2. CONCRETE PROPERTIES:
3. ADDITION OF WATER TO THE BATCH FOR MATERIAL WITH INSUFFICIENT SLUMP WILL NOT BE PERMITTED, UNLESS THE SUPPLIER HAS SPECIFICALLY WITHHELD WATER FROM THE BATCH AT THE PLANT. IN SUCH CASE, THE MIX DESIGN AND TRUCK TICKET SHALL CLEARLY STATE THE MAXIMUM AMOUNT OF WATER THAT CAN BE ADDED TO THE BATCH ON SITE. IN NO CASE SHALL THE DESIGN WATER TO CEMENTITIOUS
MATERIAL RATIO BE EXCEEDED.
4. CONCRETE CONTAINING SUPERPLASTICIZING ADMIXTURE SHALL HAVE A SLUMP OF 4 INCHES ± 1 INCH, TO BE FIELD VERIFIED, PRIOR TO ADDING ADMIXTURE, AND NOT EXCEEDING 8 INCHES AT PLACEMENT.
5. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT THAT SLABS ON GRADE NEED BE
VIBRATED ONLY AROUND UNDER-FLOOR DUCTS, SLAB EDGES, REINFORCING, KEY, ETC.
6. ALL EXTERIOR CONCRETE SHALL BE AIR ENTRAINED TO 5.5 +/- PERCENT.
7. DO NOT USE ADMIXTURES CONTAINING CALCIUM CHLORIDE.
8. WHERE CONSTRUCTION JOINTS ARE INDICATED ON STRUCTURAL DRAWINGS OR DETAILS, THE INTERFACE SHALL BE ROUGHENED TO AN AMPLITUDE OF 1/4 INCH. CONSTRUCTION JOINTS NOT SHOWN SHALL BE LOCATED BY THE CONTRACTOR, AND APPROVED BY THE ARCHITECT AND ENGINEER OF
RECORD.
9. CHAMFER EXPOSED EDGES 3/4 INCH UNLESS OTHERWISE NOTED.
10. CONTRACTOR SHALL COORDINATE EMBEDDED ITEMS, INSERTS AND ANCHORAGE TO CAST-IN-PLACE CONCRETE. REFERENCE OTHER DISCIPLINE'S DRAWINGS FOR UNDERSLAB PIPING, FLOOR DRAINS, AND SLAB AND WALL PENETRATIONS. CONTRACTOR SHALL COORDINATE EMBEDS AND ANCHORAGES FOR
WORKS TO BE ATTACHED OR ANCHORED TO CAST-IN-PLACE STRUCTURES.
11. EMBED PLATES AND BARS UNLESS OTHERWISE NOTED SHALL BE:
A. STAINLESS STEEL, 304, CONDITION-A HOT-FINISHED PER ASTM A276, FOR EXTERIOR CONDITIONS.
B. ASTM A36 FOR INTERIOR CONDITIONS.
12. NO PIPES OR CONDUIT SHALL BE PLACED HORIZONTALLY WITHIN SLABS WITHOUT ENGINEER OF
RECORD APPROVAL.
13. FOR PIPES AND CONDUIT PASSING PERPENDICULARLY THROUGH SLABS, GRADE BEAMS AND WALLS, PROVIDE SLEEVED HOLES 1 INCH IN DIAMETER LARGER THAN THE OUTSIDE DIAMETER OF THE
PIPE/CONDUIT. SLEEVES SHALL EXTEND THE FULL THICKNESS OF THE SECTION. ALL PENETRATIONS
SHALL BE APPROVED BY ENGINEER OF RECORD.
14. NO ALUMINUM CONDUIT, PRODUCTS CONTAINING ALUMINUM, OR OTHER INJURIOUS MATERIAL SHALL BE EMBEDDED IN CONCRETE. DO NOT USE ALUMINUM EQUIPMENT FOR CONVEYING OR FINISHING
CONCRETE.
15. FORMWORK DESIGN, INSTALLATION AND REMOVAL IS BY THE CONTRACTOR AND SHALL BE SIGNED AND
SEALED BY AN ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS CONSTRUCTED.
FORMWORK IS CONSIDERED A MEANS AND METHODS ITEM. FORMWORK FOR BEAM BOTTOMS AND
SHORING FOR FLOOR SYSTEMS SHALL NOT BE REMOVED UNTIL CONCRETE ATTAINS AT LEAST 80 PERCENT OF IT'S SPECIFIED 28-DAY COMPRESSIVE STRENGTH (f'c).
16. MEMBERS WITH A THICKNESS OF 3 FEET 6 INCHES AND GREATER ARE CONSIDERED MASS CONCRETE.
17. REFER TO DIVISION 03 OF THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
CONCRETE NOTES
NOTES:
A. SLUMP AT POINT OF DELIVERY WITHOUT WATER REDUCERS OR FIBERS. FOR MASS CONCRETE, LISTED SLUMP SHALL BE 2" +/- 1/2"
B. PROVIDE AIR CONTENT IN ACCORDANCE WITH ACI 318
TYPE OF
CONSTRUCTION
EXPOSURE
CATEGORY
AND CLASS
MINIMUM
COMPRESSIVE
STRENGTH
(SEE NOTE A)
MAX w/cm
RATIO
SLUMP (SEE
NOTE B)
ALL CONCRETE 5000 PSI 0.45
4 INCHES +/- 1
INCH
F1
MAXIMUM
AGGREGATE
SIZE (IN)
3/4
AIR
CONTENT %
(SEE NOTE C)
1. DO NOT USE PNEUMATIC-PRESSURE OR DRY-PACKING METHODS FOR PLACING GROUT.
2. CLEAN METAL SURFACES TO BE FREE OF ALL PAINT, OIL, GREASE, LOOSE RUST, AND OTHER FOREIGN SURFACES THAT WILL BE IN CONTACT WITH THE GROUT. PROVIDE SURFACE PREP FOR ORIGINAL
CONCRETE SURFACE IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
3. GROUT SOLID BENEATH ALL BASE PLATES, BEARING PLATES, AND WHERE INDICATED.
4. IF GROUT CANNOT BE PLACED FROM ONE EDGE AND FLOWED TO THE OPPOSITE EDGE, AIR VENTS SHALL BE PROVIDED THROUGH THE PLATE TO PREVENT AIR ENTRAPMENT. ALL VENTING SHALL BE COORDINATED AND APPROVED BY STRUCTURAL ENGINEER OF RECORD PRIOR TO FABRICATION AND
ERECTION.
5. GROUT SHALL NOT PROJECT ABOVE BOTTOM OF BASE PLATE.
6. GROUT SHALL BE FORMED WITH A SIDE SLOPE OF 1:1 PROJECTING DOWN FROM THE EDGE OF THE
SUPPORTED ELEMENT TO THE CONCRETE SURFACE UNLESS NOTED.
7. GROUT PER THE FOLLOWING:
A. NON-SHRINK NON-STAINING CEMENTITIOUS GROUT SPECIFIED COMPRESSIVE STRENGTHS ARE FOR
28 DAY PER ASTM C1107.
B. EPOXY GROUT SPECIFIED COMPRESSIVE STRENGTHS ARE FOR 7-DAY PER ASTM C579.
C. AT STEEL BASE PLATES BEARING ON CONCRETE, THE MINIMUM COMPRESSIVE STRENGTH SHALL BE
AT LEAST 1.5x THE CONCRETE MINIMUM COMPRESSIVE STRENGTH BELOW THE GROUT, BUT IN NO
CASE LESS THAN 7000 PSI.
D. AT BEARING CONNECTIONS OF PRECAST ELEMENTS ON STRUCTURAL CONCRETE OR OTHER
PRECAST ELEMENTS, USE NON-SHRINK GROUT. THE STRENGTH REQUIREMENTS OF NON-SHRINK
GROUT SHALL BE AS REQUIRED BY THE PRECAST MANUFACTURER'S ENGINEER OF RECORD, BUT
NOT LESS THAN 1.5x THE SPECIFIED CONCRETE COMPRESSIVE STRENGTH OF THE HIGHER
STRENGTH ELEMENT.
FLOWABLE GROUT NOTES
1. INSTALL BOLTS IN ACCORDANCE WITH CURRENT ICC-ES REPORT FOR THE BOLT AND
RECOMMENDATIONS OF THE MANUFACTURER.
2. INSTALL BOLTS PERPENDICULAR TO THE FACE OF CONCRETE. DEVIATION FROM PERPENDICULAR
GREATER THAN 10 DEGREES WILL NOT BE ACCEPTABLE.
3. CREATE A TEMPLATE AT EACH EXPANSION BOLT CONNECTION LOCATION PRIOR TO FABRICATING HOLES IN CONNECTION PLATES. MAKE TEMPLATE BY LOCATING EXISTING REBAR WITH A PACHOMETER.
REPOSITION BOLTS A MAXIMUM OF 1-1/2 INCHES TO AVOID CONFLICTS WITH EXISTING REINFORCING.
4. DRILL HOLES TO DEPTH AND DIAMETER RECOMMENDED BY MANUFACTURER. DO NOT ENLARGE OR
REDIRECT HOLES ALONG LENGTH OF BOLT.
5. DRILL HOLES IN CONTINUOUS OPERATION. BLOW DUST FROM THE HOLE USING COMPRESSED AIR.
6. FILL ABANDONED HOLES WITH EPOXY GROUT.
7. AIM WEDGES AWAY FROM CONCRETE EDGES LESS THAN 9 INCHES FROM THE CENTER LINE OF THE
HOLE. TIGHTEN NUTS AGAINST SMOOTH WASHERS TO MINIMUM TORQUE RECOMMENDED BY
MANUFACTURER.
8. PROVIDE HOLES IN CONNECTION PLATES NO MORE THAN 1/16 INCH LARGER THAN THE BOLT DIAMETER.
9. POST-INSTALLED ANCHOR SYSTEMS SHALL COMPLY WITH ICC-ES ACCEPTANCE CRITERIA AND HAVE A
VALID ICC-ES REPORT IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE.
10. REFER TO CONCRETE ANCHORAGE SPECIFICATION FOR ADDITIONAL QUALIFIED ANCHORS.
11. EXPANSION BOLTS IN CONCRETE SHALL BE AS INDICATED ON THE CONSTRUCTION DOCUMENTS.
WHERE MANUFACTURER IS NOT SPECIFIED PROVIDE ONE OF THE FOLLOWING:
A. HILTI HSL-3 CARBON STEEL HEAVY DUTY EXPANSION ANCHOR (ICC-ES REPORT ESR-1545).
B. HILTI HDA CARBON AND STAINLESS STEEL UNDERCUT ANCHOR (ICC-ES REPORT ESR-1546).
C. HILTI BOLT TZ2 CARBON AND STAINLESS STEEL ANCHORS (ICC-ES REPORT ESR-4266).
D. DEWALT POWER-STUD + SD2 ANCHOR (ICC-ES REPORT ESR-2502).
E. DEWALT POWER-STUD + SD1 ANCHOR (ICC-ES REPORT ESR-2818).
F. SIMPSON STRONG-TIE STRONG-BOLT 2 ANCHOR (ICC-ES REPORT ESR-3037).
G. SIMPSON STRONG-TIE TCA SELF-UNDERCUTTING ANCHOR (ICC-ES REPORT ESR-2705).
12. SCREW ANCHORS IN CONCRETE SHALL BE AS INDICATED ON THE CONSTRUCTION DOCUMENTS. WHERE
MANUFACTURER IS NOT SPECIFIED PROVIDE ONE OF THE FOLLOWING:
A. HILTI KH-EZ SCREW ANCHOR (ICC-ES REPORT ESR-3027).
B. SIMPSON STRONG-TIE TITEN HD SCREW ANCHOR (ICC-ES REPORT ESR-2713).
C. DEWALT SCREW-BOLT+ ANCHOR (ICC-ES REPORT ESR-3889).
13. ADHESIVE ANCHORS AND REINFORCING DOWELS IN CONCRETE SHALL BE AS INDICATED ON THE
CONSTRUCTION DOCUMENTS. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A
MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. WHERE MANUFACTURER IS NOT
SPECIFIED, PROVIDE ONE OF THE FOLLOWING:
A. HILTI HIT-HY 200 ADHESIVE WITH HAS THREADED ANCHOR ROD, HIT-Z ANCHOR ROD, OR
REINFORCING DOWEL (ICC-ES REPORT ESR-3187).
B. HILTI HIT-RE 500 V3 ADHESIVE WITH HAS THREADED ANCHOR ROD OR REINFORCING DOWEL
(ICC-ES REPORT ESR-3814).
C. SIMPSON STRONG-TIE SET-XP EPOXY ADHESIVE WITH THREADED ANCHOR ROD OR
REINFORCING DOWEL (ICC-ES REPORT ESR-2508).
D. DEWALT AC200+ ADHESIVE WITH THREADED ANCHOR ROD OR REINFORCING DOWEL (ICC-ES
REPORT ESR-4027).
E. DEWALT PURE200+ ADHESIVE WITH THREADED ANCHOR ROD OR REINFORCING DOWEL (ICC-
ES REPORT ESR-5144).
14. ANCHORS INSTALLED IN THE UNDERSIDE OF CONCRETE OVER STEEL DECK SHALL BE INSTALLED IN THE
BOTTOM FLUTE ONLY.
15. ANCHORS ARE NOT TO BE INSTALLED UNTIL CONCRETE OR GROUT HAS REACHED ITS DESIGN
STRENGTH.
16. ANCHORS SHALL NOT BE INSTALLED WITHIN 1/2 INCH OF A MASONRY MORTAR JOINT NOR LESS THAN
ANCHOR MANUFACTURER APPROVED DISTANCE, WHICHEVER IS MORE RESTRICTIVE.
17. FOR ANCHOR EMBEDMENT, SEE DRAWINGS OR TYPICAL-DETAIL. USE EMBEDMENT RECOMMENDED BY
MANUFACTURER WHERE NO EMBEDMENT IS SHOWN.
18. MANUFACTURER'S INSTALLATION TRAINING AND CERTIFICATION IS REQUIRED ON ALL POST-INSTALLED
ANCHORS FOR ANCHOR INSTALLER.
19. DO NOT CUT CONCRETE REINFORCEMENT/TENDONS DURING INSTALLATION OF POST-INSTALLED ANCHORS. USE NON-DESTRUCTIVE TESTING TO LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO INSTALLATION OF ANCHORS. WHEN DRAWINGS IDENTIFY ALTERNATE HOLE
LOCATIONS, USE THE NEAREST ALTERNATE HOLE LOCATION WHEN CONDITIONS PREVENT
INSTALLATION OF ANCHOR IN DESIGNATED HOLE. IF REINFORCEMENT PREVENTS INSTALLATION OF ANCHOR IN DESIGNATED HOLE, INSTALL ANCHOR IN NEAREST ALTERNATE HOLE. WHEN CONDITIONS PREVENT ANCHOR INSTALLATION IN THE DESIGNATED AND ALTERNATE HOLE, CONTACT ENGINEER OF
RECORD FOR REVISED CONNECTION DETAIL.
POST-INSTALLED ANCHOR NOTES
SHEET OF
T D C J
TITLE:
TEXAS DEPARTMENT
OF
CRIMINAL JUSTICE
ENGINEERING SERVICE
PO BOX 4011
TWO FINANCIAL PLAZA,
SUITE 400
HUNTSVILLE, TX 77340
G
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
N O
1 2 3 4 5 1 2
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
IS
S
U E
D F
O R
D A
T E
D A
T E
P R
O J E
C T
N A
M E
IN
S T
A L L H
V A
C
B
L
R
E N
G
IN
E E
R
J A
C O
B S
F -2
D A
T E
/0
/2
U N
IT
S T
IL
E
S
D R
A W
N B
Y
G
P E
L A
G
IO
S C
A L E
A
S S
H O
W N
Texas Engineering Registration F-2966
NAVID NAZEMI
OF TEXASS
TATE
ALNOI
SS
E
F O
R P
ENG
IN
E E
R
NSEDECI
L 145373
IS
S
U E
D F
O R
P R
O P
O S
A L
/0
/2
11/08/2024
S-002
GENERAL
NOTES
7 52
NOTE:
BRAND OR MANUFACTURER'S REFERENCES ARE DESCRIPTIVE ONLY, AND INDICATE TYPE
AND QUALITY TO BE PROVIDED. ALL REFERENCES TO BRAND OR MANUFACTURER NAMES
SHALL BE INTERPRETED TO INCLUDE THE LANGUAGE “OR A/E APPROVED EQUAL”. ANY
BRAND OR MANUFACTURER MEETING SPECIFICATIONS WILL BE CONSIDERED,
1. ALL STRUCTURAL STEEL SHALL BE FABRICATED BY A FABRICATOR WITH ANY ONE OF THE FOLLOWING
MINIMUM QUALIFICATIONS. QUALIFICATIONS SHALL BE IN EFFECT AT TIME OF PROPOSAL.
A. INTERNATIONAL ACCREDITATION SERVICE, INC (IAS) APPROVED FABRICATOR.
B. AISC CERTIFIED FABRICATOR (STD).
NOTE: FABRICATOR SHALL SUBMIT DOCUMENTATION OF THEIR CERTIFICATION WITH THE FIRST
SHOP DRAWING SUBMITTAL.
2. STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" WITH AMENDMENTS AND THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" WITH AMENDMENTS. THE SHOP DRAWINGS REVIEW TIME OF SECTION 4.4 OF THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES IS REVISED TO MATCH THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS. THE WORD 'APPROVED' IN
SECTION 4.4 IS REDEFINED AS 'REVIEWED'.
3. STEEL PROPERTIES
4. ALL STRUCTURAL STEEL OTHER THAN A36 SHALL BE CLEARLY IDENTIFIED ACCORDING TO GRADE.
5. IF IT IS NECESSARY TO SPLICE ANY MEMBER, SPLICE LOCATIONS ARE SUBJECT TO REVIEW BY
STRUCTURAL ENGINEER OF RECORD. SPLICES SHALL BE COMPLETE PENETRATION WELDED AND
TESTED. SEE SPECIAL INSPECTION PROVISIONS. INDICATE ALL SPLICE LOCATIONS, AND WELDING
PROCEDURES ON SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION.
6. FIELD VERIFY LOCATION OF EXISTING FRAMING PRIOR TO FABRICATION OF NEW FRAMING.
7. ALL EXTERIOR STRUCTURAL STEEL SHALL BE GALVANIZED. WHERE NEW WELDED CONNECTIONS ARE MADE TO EXISTING GALVANIZED STEEL, REMOVE EXISTING HOT-DIPPED GALVANIZED FINISH PRIOR TO WELDING, AND REPAIR AFTER WELDING WITH GALVANIZED REPAIR COMPOUND PER SPECIFICATIONS.
PROVIDE TOUCH UP TO EXISTING GALVANIZED FINISH WHERE NEW HOLES ARE DRILLED INTO EXISTING GALVANIZED FRAMING. SEAL WELD CAP PLATES AND PENETRATIONS AT GALVANIZED EXTERIOR STEEL TUBES TO RESIST WATER INFILTRATION AND PROVIDE WEEP HOLES AT LOW POINTS OF TUBES. PLUG
ALL GALVANIZED HOLES FLUSH WITH TAPERED ALUMINUM PLUGS.
8. FLANGES OF HOT ROLLED SHAPES AND PLATES THICKER THAN 1-1/2 INCHES SHALL COMPLY WITH AISC 360, SECTIONS A3.1C, A3.1D, J1.6, J2.6 AND M2.2 (AS LISTED FOR MATERIALS THICKER THAN 2 INCHES) FOR MATERIAL CUTTING AND WELDING. FOR SHAPES REQUIRING SPLICES USING COMPLETE JOINT
PENETRATION WELDS, THE STEEL SHALL BE SUPPLIED WITH CHARPY V-NOTCH TESTING IN
ACCORDANCE WITH ASTM A6, SUPPLEMENTARY REQUIREMENT S5 OR S30 (AS APPLICABLE). THE IMPACT
TEST SHALL MEET A MINIMUM AVERAGE VALUE OF 20 FT-LB ABSORBED ENERGY AT +70º F.
9. ALL BEAMS SHALL BE ERECTED WITH THE NATURAL CAMBER UPWARDS.
10. ALL BOLTS SHALL BE INSTALLED WITH STEEL WASHERS.
11. FILL ALL ERECTION BOLT HOLES WITH BOLTS, WASHERS AND NUTS, WITH BOLT PROJECTION NO MORE
THAN 1 INCH PAST NUT. FASTENER FINISH TO MATCH STEEL FINISH.
12. ALL REFERENCE TO HEADED STUDS SHALL INDICATE AUTOMATIC WELDED HIGH STRENGTH HEADED
STUDS (NELSON OR EQUIVALENT). STUDS SHALL CONFORM TO ALL REQUIREMENTS OF THE
"RECOMMENDED PRACTICES FOR STUDS WELDING" AND THE "STRUCTURAL WELDING CODE - STEEL" PUBLISHED BY THE AMERICAN WELDING SOCIETY. CONFORMANCE SHALL INCLUDE, BUT NOT BE LIMITED
TO, ALL QUALITY CONTROL TESTING PROVISIONS OF THE AFOREMENTIONED PUBLICATIONS.
13. HEADED SHEAR CONNECTOR STUDS ON COMPOSITE STEEL BEAMS SHALL BE UNIFORMLY SPACED. FOR LENGTH AND SPACING REQUIREMENTS, SEE TYPICAL-DETAIL. USE NOT MORE THAN ONE STUD PER RIB
WHERE THE NUMBER OF STUDS REQUIRED IS LESS THAN OR EQUAL TO THE NUMBER OF RIBS
AVAILABLE. WHERE THE NUMBER OF STUDS EXCEEDS THE NUMBER OF RIBS AVAILABLE, PLACE A MINIMUM OF ONE STUD PER RIB FULL LENGTH OF BEAM. PLACE ADDED STUDS (NO MORE THAN TWO PER RIB TOTAL) IN EACH RIB BEGINNING AT THE SUPPORTS AT EACH END AND MOVING TOWARDS MIDSPAN UNTIL REQUIRED NUMBER OF STUDS ARE SUPPLIED. MAXIMUM LONGITUDINAL STUD SPACING IS 32 INCHES CENTER TO CENTER. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR REVIEW PRIOR TO
INSTALLATION. IF HEADED STUD LENGTH IS SHOWN ON DRAWINGS, THAT LENGTH SHALL BE
INTERPRETED AS THE FINISHED LENGTH AFTER INSTALLATION.
14. DEFORMED BAR ANCHORS (DBA) SHALL BE NELSON DEFORMED BAR ANCHORS (OR APPROVED EQUAL), AND SHALL BE MADE FROM LOW CARBON STEEL CONFORMING TO ASTM A496. ANCHORS SHALL BE AUTOMATICALLY END-WELDED WITH SUITABLE WELDING EQUIPMENT IN THE SHOP OR IN THE FIELD.
WELDING SHALL BE IN ACCORDANCE WITH RECOMMENDATIONS OF THE NELSON STUD WELDING
COMPANY.
15. ALL WELDING SHALL BE PERFORMED BY WELDERS HOLDING VALID CERTIFICATES AND HAVING CURRENT EXPERIENCE IN TYPE OF WELD SHOWN ON THE DRAWINGS OR NOTES. CERTIFICATES SHALL BE THOSE
ISSUED BY AN INDEPENDENT TESTING AGENCY.
STRUCTURAL STEEL NOTES
STRUCTURAL
PLATES/BARS UP TO 4"
THICKNESS
ASTM A572 (Fy = 50 KSI)
STRUCTURAL
PLATES/BARS GREATER
THAN 4" THICKNESS
ASTM A36 (Fy = 32 KSI)
W - AND WT - SHAPES ASTM A992 (Fy = 50 KSI)
M - AND S - SHAPES ASTM A992 (Fy = 50 KSI)
C - AND MC - SHAPES ASTM A992 (Fy = 50 KSI)
ANGLES ASTM A572 (Fy = 50 KSI)
PIPE ASTM A53 GRADE B (Fy = 35 KSI)
RECTANGULAR HSS ASTM A500 GRADE C (Fy = 50 KSI)
ROUND HSS ASTM A500 GRADE C (Fy = 50 KSI)
HIGH-STRENGTH BOLTS
ASTM F3125 GRADE F1852, TYPE 1 (TWIST-OFF TENSION CONTROL BOLTS)
WITH THREADS INCLUDED IN SHEAR PLANE, INSTALLED AND PRETENSIONED
PER SECTION 8.2 AND INSPECTED PER SECTION 9 OF THE RCSC
SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS,
DATED JUNE 11, 2020. GRADE A325 BOLTS INSTALLED TO EQUIVALENT
TORSION AND INSPECTION REQUIREMENTS IS ACCEPTABLE AT
CONTRACTOR'S OPTION AS INDICATED ON THE PLANS AND DETAILS.
CONNECTION TYPE IS PRETENSIONED UNLESS OTHERWISE NOTED. BOLTS
NOTED AS TYPE SC (SLIP-CRITICAL) IN DETAILS SHALL BE INSTALLED AS SLIP
CRITICAL WITH FLAYING SURFACES PREPARED AS CLASS B SURFACE PER
AISC 360.
WHERE NOTED ON PLANS, PROVIDE ASTM F3125 GRADE 2280 TYPE 1
(TWIST-OFF TENSION CONTROL BOLTS) WITH THREADS INCLUDED IN SHEAR
PLANE, INSTALLED AND PRETENSIONED PER SECTION 8.2 AND INSPECTED
PER SECTION 9 OF THE RCSC SPECIFICATION FOR STRUCTURAL JOINTS
USING HIGH-STRENGTH BOLTS, DATED JUNE 11, 2020. GRADE A490 BOLTS
INSTALLED TO EQUIVALENT TORSION AND INSPECTION REQUIREMENTS ARE
ACCEPTABLE AT CONTRACTOR'S OPTION AS INDICATED ON THE PLANS AND
DETAILS. CONNECTION TYPE IS PRETENSIONED UNLESS OTHERWISE NOTED.
BOLTS NOTED AS TYPE SC (SLIP-CRITICAL) IN DETAILS SHALL BE INSTALLED
AS SLIP-CRITICAL WITH FAYING SURFACES PREPARED AS CLASS B SURFACE
PER AISC 360.
WHERE NOTED ON PLANS, PROVIDE BLIND EXPANSION BOLTS WITH AN
ICC-ES REPORT APPROVED FOR USE IN SEISMIC DESIGN. BOLTS TO BE
INSTALLED PER MANUFACTURER AND ICC-ES REPORT REQUIREMENTS.
NUTS ASTM A563
WASHERS FOR HIGH-
STRENGTH BOLTS
ASTM A436
THREADED RODS ASTM A36
ANCHOR RODS ASTM F1554, GRADE 55 (WELDABLE) - UNLESS OTHERWISE NOTED
WASHERS FOR ANCHOR
RODS
ASTM A572 GRADE 50 (Fy = 50 KSI)
16. ALL WELDING SHALL BE PERFORMED PER THE AISC AND AWS STANDARDS. IN SITUATIONS WHERE BOTH STANDARDS ADDRESS THE SAME ITEM, THE PROVISIONS OF AISC SHALL SUPERSEDE THOSE OF THE AWS. ALL WELDS ON DRAWINGS ARE SHOWN AS SHOP WELDS. CONTRACTOR MAY SHOP WELD OR FIELD WELD AT CONTRACTOR'S DISCRETION. SHOP WELDS OR FIELD WELDS SHALL BE SHOWN ON SHOP
DRAWINGS.
17. SLAG SHALL BE REMOVED FROM ALL COMPLETED WELDS, AND THE WELD AND ADJACENT BASE METAL SHALL BE CLEANED BY BRUSHING OR OTHER SUITABLE MEANS. WELDED JOINTS SHALL NOT BE PAINTED UNTIL AFTER WELDING HAS BEEN COMPLETED AND THE WELD ACCEPTED. ALL COMPLETE PENETRATION
WELDS SHALL BE TESTED. SEE SPECIAL INSPECTION PROVISIONS.
18. WELDS USED IN MEMBERS AND CONNECTIONS DESIGNATED IN THE DRAWINGS AS PART OF SEISMIC FORCE RESISTING SYSTEM (SFRS) SHALL BE MADE WITH FILLER METALS MEETING THE REQUIREMENTS IN AWS D1.8, CLAUSES 6.1, 6.2 AND 6.3 (AISC 341-16 SECTION A3.4A AND A3.4B). WELDS USED IN MEMBERS AND CONNECTIONS DESIGNATED IN THE DRAWINGS AS DEMAND CRITICAL (DC) SHALL BE MADE WITH FILLER METALS AND MEETING THE REQUIREMENTS IN AWS D1.8 SECTION 6.3, INCLUDING SUB-CLAUSES
6.3.5, 6.3.6, 6.3.7 AND 6.3.8.
19. SUBMIT A WELDING PROCEDURE SPECIFICATION IN ACCORDANCE WITH THE LATEST EDITION OF AWS D1.1. WHERE WELDS ARE FOR MEMBERS DESIGNATED AS PART OF THE SFRS OR LABELED DEMAND
CRITICAL, WELDING PROCEDURES SHALL CONFORM TO AWS D1.8 AND MANUFACTURER'S
RECOMMENDATIONS (WHERE APPLICABLE). APPROVED PROCEDURES TO BE SUBMITTED TO SPECIAL
INSPECTOR FOR REVIEW AND APPROVAL, THEN TO THE ENGINEER FOR REVIEW.
20. LOWEST ANTICIPATED SERVICE TEMPERATURE (LAST) SHALL BE 50 DEGREES FAHRENHEIT FOR INDOOR
CONDITIONED STRUCTURES AND 0 DEGREES FAHRENHEIT FOR OUTDOOR/UNCONDITIONED
STRUCTURES.
21. NO CONNECTIONS OR ATTACHMENTS ARE PERMITTED WITHIN PROTECTED ZONES.
22. DESIGN AND PROVISION OF ERECTION AIDS SUCH AS BOLTS, CLIPS, SHIMS, SEATS OR ANY OTHERS REQUIRED TO FACILITATE THE CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR AND
SHALL NOT EFFECT THE FINAL STRUCTURE. ERECTION AIDS SHALL BE REMOVED AND DAMAGED
SURFACES REPAIRED WITH PROTECTIVE COATINGS TOUCHED UP IN THE FIELD AFTER STEEL ERECTION.
DESIGN OF ERECTION AIDS SHALL BE IN CONFORMANCE WITH ALL LOCAL, STATE AND FEDERAL
REGULATIONS GOVERNING FABRICATION AND ERECTION.
23. REFER TO SPECIFICATION SECTION 05 12 00 OF THE PROJECT MANUAL FOR ADDITIONAL INFORMATION.
STRUCTURAL STEEL NOTES
1. PROVIDE DETAILING, FABRICATION, AND INSTALLATION OF REINFORCING AND ACCESSORIES IN
ACCORDANCE WITH ACI 301, ACI 315 AND ACI 318.
2. TYPICAL REINFORCING BAR STRENGTHS:
3. CONCRETE COVER FOR CAST-IN-PLACE NON-PRESTRESSED CONCRETE MEMBERS UNLESS NOTED
ON DRAWINGS:
NOTE: REFERENCE LATEST EDITION OF ACI 301 FOR ADDITIONAL CONCRETE COVER REQUIREMENTS
FOR PRESTRESSED AND PRECAST CONCRETE MEMBERS.
4. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE. POSITION TIE WIRE ENDS AWAY
FROM EXPOSED CONCRETE SURFACES. REINFORCING BAR SPACINGS GIVEN ARE MAXIMUM ON
CENTERS.
5. ALL REINFORCING TO BE WELDED SHALL BE WELDED IN ACCORDANCE WITH AWS D1.4.
NO TACK WELDING OF REINFORCING BARS IS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE
BY STRUCTURAL ENGINEER OF RECORD.
6. REINFORCING LAP…