ESBD_386901_1734639574287_Attachment A - 10000gal Tank with recirc pipe.pdf
PDF 477 KB Posted
- Solicitation number
- IFB-25-012
- Issued by
- Hockley County, Texas
About this file
This is a technical specification document from WW Fiberglass Tank Co. for Texas A&M Forest Service detailing the design of a 10,000-gallon single-wall fiberglass tank. The tank measures 11'10" x 12' and is designed to store Phos-Check LC95A fire retardant with a density of 12½ lbs/gal. The document includes detailed nozzle schedules, construction specifications, and multiple technical drawings showing the tank's components including inlet/outlet ports, circulation lines, manways, vents, ladder attachments, and pipe supports. The tank is designed to ASTM-D-3299 and API 12P specifications, with a white gel coat finish and ISO resin construction.
The technical drawings provide comprehensive thickness specifications ranging from 225-800 mils for different sections of the tank, with detailed measurements for all fittings and attachments. The tank features a 22" plastic manway, multiple 3" ports for inlet/outlet and circulation, a 6" goose neck vent with stainless steel bird screen, galvanized D-rings, sight glass fittings, and a 10' ladder assembly. The tank is designed for atmospheric pressure and ambient temperature operation, with all fittings and elevations precisely specified to within ¼" tolerance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
270° 90°
45°
315°
135° 225°
0°
180°
B
B
C,D
C,D
E1,2
E3
E3
E1
E2
F,G
F
G
A1
A1,J1-3
H,I
H,I
J1-3
A2
A2
K1
K2
K3
K4
K1-4
L
M
N4
N3
N2
N1
N1-4
NOZZLE SCHEDULE
MARK SIZE FITTING DESCRIPTION PROJ. DEG
ELV. ℄ COMMENT
A1 3" INLET 2" CNTR
A2 3" CIRCULATION LINE CNTR SEE DETAIL OF A2
B 22" PLASTIC MANWAY 1" 180 TOP 22" FROM EDGE
C 3" T.O.E OUTLET 2" 168.75 12" UP
D 3" FG ELBOW 168.75 1
" OFF BOTTOM
E1 GALVANIZED D-RINGS 2" 225 12" DOWN
E2 GALVANIZED D-RINGS 2" 225 12" UP
E3 GALVANIZED D-RINGS 2" 45 12" DOWN
F
" T.O.E FOR SIGHT GLASS 2" 135 7" UP
G
" T.O.E FOR SIGHT GLASS 2" 135 11'-6" UP
H 3" T.O.E OUTLET 2" 149.75 12" UP 2' RIGHT OF 180°
I 3" FG ELBOW 149.75 1
" OFF BOTTOM
J1 6" T.O.E VENT 2" 0 TOP 24" FROM CNTR
J2 6" MALE T.O.E
CNT TO BOTTOM
OF J3
J3 6"
GOOSE NECK VENT w/ SS
BIRD SCREEN
CNT TO J1
K1 LADDER LUGS 180 3' UP 19" APART
K2 LADDER LUGS 180 6'-11" UP 19" APART
K3 LADDER LUGS 180 11' UP 19" APART
K4 10' LADDER 180
L 16" STRIKER PLATE 177.75 BOTTOM 10" FROM EDGE
M
12" x 4'-9"
REINFORCEMENT PAD
BOTTOM
10" LEFT OF A2,
3'-4
" FROM EDGE
TO CNTR OF PAD
N1 3" EXTERNAL INLET PIPE 157.5 4" UP CNT TO TOP OF A1
N2 PIPE SUPPORT 157.5 18" UP
N3 PIPE SUPPORT 157.5 6'-5" UP
N4 PIPE SUPPORT 157.5 11' UP
CUSTOMER: Texas A&M Forest Service QUOTE DATE:
PROJECT: SALES DATE: 01-03-2023
CONTACT:
TANK SIZE: 11'-10" x 12', 10,000gal Tank
ITEM No.: TANK242-11.10-222IE
SALESMAN: Diana Irlbeck
SHEET: 1 / 4
SHEET TYPE: FULL VIEW / NOZZLE SCHEDULE
TANK CONSTRUCTION: SINGLE WALL
LINER RESIN: ISO
STRUCTURAL RESIN: ISO
PIGMENT: NONE
GEL COAT: WHITE
DESIGN SPEC: ASTM-D-3299, API 12P
TANK CONTENTS: PHOS-CHECK LC95A
FIRE RETARDANT / 12
lbs/gal
MAX FLUID TEMP.: AMBIENT
MAX PRESSURE: ATMOSPHERIC
CUSTOMER APPROVAL:______________________
APPROVAL DATE:____________________________
NOTES DATE BY
REFERENCE NUM.: SO - 502376
CONFIDENTIAL
This document includes proprietary information belonging to WW Fiberglass Tank Co., and is loaned only for quotations or manufacturing purposes, with the express understanding that it will not be reproduced, that its contents and concepts are received in confidence and will not be copied nor divulged to unauthorized persons or companies, that the same shall not be used for any purpose other than that for which loaned, and that the same shall be returned promptly upon demand.
PO #:
REVISION: #0
TANK LOCATION:
DRAWN: Joel A. Shutts
ALL TOLERANCES +/-
ELEVATION OF FITTINGS IS MEASURE FROM OUTSIDE TANK BOTTOM.
PROJECTION OF FITTINGS IS MEASURED FROM OUTSIDE TANK WALL.
REVISION
DATE BYREV. #
ROTATE TOP 180° 01-03-2023 JAS
Attachment A
2'
2'-6"
3"
" HOLE
@ 270°
" HOLE
@ 0°
(4)
" HOLE
@ 225°
6"
3" 90° ELBOW
ITEMS
C & D
3" PIPE
TOP VIEW
DETAIL OF A2
3" FG T.O.E
2" PVC REDUCER
1" PVC REDUCER
10"
2'
3" SUPPORT
2'-6"
" HOLE
@ 180°
2'-6"
" HOLE
@ 90°
1'-3"
1'-11
NOZZLE POINTED
@ 247.5°
B
B
SECTION BB
NOZZLE POINTED
DOWN 22.5°
(4) 1" HOLES
POINTED
DOWN 45°
A2
A2
(3) 3" x 6" PIPE SUPPORT
4'-8"
3"Ø PIPE
2'-6"
" HOLE
@ 0°
13'-4"
3" PIPE
2"
6" FEMALE T.O.E
6" FG
GOOSE NECK
w/ SS BIRD SCREEN
6" MALE THREAD
STAINLESS MESH
1” FRP RING CUT
FROM END OF GOOSENECK
ADHERE w/ SIKAFORCE 7800
WRAP WITH
FIBERGLASS
C,H
D,I
1'
DETAIL OF C,D & H,I
3" FEMALE T.O.E
3" 90° ELBOW
3"Ø x 6"
PIPE
CUSTOMER: Texas A&M Forest Service QUOTE DATE:
PROJECT: SALES DATE: 01-03-2023
CONTACT:
TANK SIZE: 11'-10" x 12', 10,000gal Tank
ITEM No.: TANK242-11.10-222IE
SALESMAN: Diana Irlbeck
SHEET: 2 / 4
SHEET TYPE: DETAIL SHEET #1
REFERENCE NUM.: SO - 502376
CONFIDENTIAL
This document includes proprietary information belonging to WW Fiberglass Tank Co., and is loaned only for quotations or manufacturing purposes, with the express understanding that it will not be reproduced, that its contents and concepts are received in confidence and will not be copied nor divulged to unauthorized persons or companies, that the same shall not be used for any purpose other than that for which loaned, and that the same shall be returned promptly upon demand.
PO #:
REVISION: #0
TANK LOCATION:
DRAWN: Joel A. Shutts
ALL TOLERANCES +/-
ELEVATION OF FITTINGS IS MEASURE FROM OUTSIDE TANK BOTTOM.
PROJECTION OF FITTINGS IS MEASURED FROM OUTSIDE TANK WALL.
4" FROM GROUND
TO BOTTOM OF PIECE
8"
12'-6"
3" PIPE
1'-6"
6'-5"
11'
6'
3" PIPE
3" 90° ELBOW
3" FEMALE T.O.E
3" 90° ELBOW3" 90° ELBOW
TOP OF A2
PIPE SUPPORT
2" x 7" FG L-BAR
PIPE SUPPORT
2" x 7" FG L-BAR
PIPE SUPPORT
2" x 7" FG L-BAR
DETAIL OF N1-4
CUSTOMER: Texas A&M Forest Service QUOTE DATE:
PROJECT: SALES DATE: 01-03-2023
CONTACT:
TANK SIZE: 11'-10" x 12', 10,000gal Tank
ITEM No.: TANK242-11.10-222IE
SALESMAN: Diana Irlbeck
SHEET: 3 / 4
SHEET TYPE: DETAIL SHEET #2
REFERENCE NUM.: SO - 502376
CONFIDENTIAL
This document includes proprietary information belonging to WW Fiberglass Tank Co., and is loaned only for quotations or manufacturing purposes, with the express understanding that it will not be reproduced, that its contents and concepts are received in confidence and will not be copied nor divulged to unauthorized persons or companies, that the same shall not be used for any purpose other than that for which loaned, and that the same shall be returned promptly upon demand.
PO #:
REVISION: #0
TANK LOCATION:
DRAWN: Joel A. Shutts
ALL TOLERANCES +/-
ELEVATION OF FITTINGS IS MEASURE FROM OUTSIDE TANK BOTTOM.
PROJECTION OF FITTINGS IS MEASURED FROM OUTSIDE TANK WALL.
CUSTOMER: Texas A&M Forest Service QUOTE DATE:
PROJECT: SALES DATE: 01-03-2023
CONTACT:
TANK SIZE: 11'-10" x 12', 10,000gal Tank
ITEM No.: TANK242-11.10-222IE
SALESMAN: Diana Irlbeck
SHEET: 4 / 4
SHEET TYPE: THICKNESS CHART
REFERENCE NUM.: SO - 502376
CONFIDENTIAL
This document includes proprietary information belonging to WW Fiberglass Tank Co., and is loaned only for quotations or manufacturing purposes, with the express understanding that it will not be reproduced, that its contents and concepts are received in confidence and will not be copied nor divulged to unauthorized persons or companies, that the same shall not be used for any purpose other than that for which loaned, and that the same shall be returned promptly upon demand.
PO #:
REVISION: #0
TANK LOCATION:
DRAWN: Joel A. Shutts
ALL TOLERANCES +/-
ELEVATION OF FITTINGS IS MEASURE FROM OUTSIDE TANK BOTTOM.
PROJECTION OF FITTINGS IS MEASURED FROM OUTSIDE TANK WALL.
THICKNESS CHART
FEET
SOLID ISO
SHELL
TOTAL ACTUAL
TOP 225mils 325mils
1' 300mils 300mils
2' 300mils 300mils
3' 300mils 300mils
4' 300mils 300mils
5' 300mils 300mils
6' 300mils 300mils
7' 300mils 300mils
8' 350mils 350mils
9' 350mils 350mils
10' 400mils 400mils
11' 400mils 400mils
12' / KNUCKLE 800mils 800mils
BOTTOM 400mils 400mils
TOP THICKNESS DETAIL
STANDARD
TOP
KNUCKLE
TO 6"
RIGHT
HOUSE
LEFT
HOUSE
RIBS 36" CENTER
SOLID ISO
SHELL
400mils 225mils 225mils 250mils 225mils 250mils
TOTAL
THICKNESS
500mils 325mils 325mils 350mils 325mils 350mils
ACTUAL
BOTTOM THICKNESS DETAIL
KNUCKLE
TO 12"
24" 36" CENTER
SOLID ISO
SHELL
800mils 400mils 400mils 400mils
TOTAL
THICKNESS
800mils 400mils 400mils 400mils
ACTUAL
TANK CONSTRUCTION: SINGLE WALL
LINER RESIN: ISO
STRUCTURAL RESIN: ISO
PIGMENT: NONE
GEL COAT: WHITE
DESIGN SPEC: ASTM-D-3299, API 12P
TANK CONTENTS: PHOS-CHECK LC95A
FIRE RETARDANT / 12
lbs/gal
MAX FLUID TEMP.: AMBIENT
MAX PRESSURE: ATMOSPHERIC
File details come from the government source that posted it. Updated .